Protection relays are the “decision makers” of an electrical power system. They watch current, voltage, frequency and other signals, spot a fault, and tell a circuit breaker to open. This guide explains every main type in plain English, with ANSI numbers, simple examples and clear tables.
Table of contents
- Quick answer: what are the types of protection relays?
- What is a protection relay?
- How does a protection relay work?
- What makes a good protection system?
- How are protection relays classified?
- Types of protection relays by technology
- Electromechanical relays
- Static relays
- Digital and numerical relays
- Intelligent electronic devices (IEDs)
- Types of protection relays by function
- Overcurrent relay (ANSI 50/51)
- Earth fault relay (ANSI 50N/51N)
- Directional overcurrent relay (ANSI 67)
- Distance relay (ANSI 21)
- Differential relay (ANSI 87)
- Voltage and frequency relays (ANSI 27, 59, 81)
- Reverse power, negative sequence and thermal relays (ANSI 32, 46, 49)
- Loss of excitation and overexcitation relays (ANSI 40, 24)
- Buchholz relay (ANSI 63)
- Restricted earth fault relay (REF)
- Arc flash relay
- Breaker failure, auto-reclose, synchro-check and lockout relays
- Pilot and communication-based protection
- Types of protection relays by operating time
- Protection relays by protected equipment
- Protection zones, primary protection and backup
- Numerical relays, IEC 61850 and cybersecurity
- ANSI device numbers, IEC symbols and key standards
- Why protection relays misoperate
- How big is the protection relay market?
- Frequently asked questions
- What are the main types of protection relays?
- What is the most commonly used protection relay?
- Does a protection relay interrupt fault current?
- What is the difference between a numerical and a digital relay?
- What does ANSI device number 21 mean?
- What is an ANSI 50/51 relay?
- What is the function of a differential relay?
- Which relays protect a transformer?
- What is an IDMT relay?
- What is the difference between primary and backup protection?
- Conclusion
- Sources
Quick answer: what are the types of protection relays?
There is no single list. Engineers sort protection relays in four ways:
- By technology: electromechanical, static (solid-state), digital and numerical relays (also called IEDs).
- By function: overcurrent, earth fault, directional, distance, differential, voltage, frequency, reverse power, thermal and other specialist relays.
- By operating time: instantaneous, definite-time and inverse-time (IDMT) relays.
- By protected equipment: generator, transformer, motor, feeder, transmission line, busbar and capacitor bank relays.
The most important of these is classification by function, because it tells you what the relay actually detects. Section 5 covers each one with its ANSI device number.
What is a protection relay?
A protection relay is a device that continuously checks electrical quantities, compares them with set limits, and sends a trip signal when something abnormal happens. Abnormal conditions include short circuits, overloads, earth faults, overvoltage, undervoltage, abnormal frequency and phase imbalance.
One point causes a lot of confusion: the relay does not interrupt the fault current itself. It only makes the decision. The circuit breaker does the physical work of opening. If you want to see how breakers do this, read our guide to the different types of circuit breakers.
| Device | Role | Interrupts fault current? |
|---|---|---|
| Protection relay | Detects the fault and decides to trip | No |
| Circuit breaker | Opens the circuit when told to | Yes |
| Fuse | Senses and breaks the fault in one device (it melts) | Yes |
| Control relay | Switching, interlocking and signalling (not fault detection) | No |
How does a protection relay work?
A relay is one link in a chain called the protection system. Every link must work, or the fault stays on the network.
- Current transformers (CTs) and voltage transformers (VTs) reduce high system values to safe levels, such as 1 A or 5 A and 110 V.
- The relay reads these signals and compares them with its settings.
- If the settings are exceeded, the relay closes a trip contact or sends a digital trip command.
- A DC battery supply powers the trip coil, so tripping still works if the AC supply fails.
- The circuit breaker opens and isolates the faulty section.
What makes a good protection system?
| Requirement | Meaning in simple words |
|---|---|
| Sensitivity | Detects even the smallest fault it is meant to detect |
| Selectivity | Trips only the faulty section, so healthy parts stay live |
| Speed | Clears faults fast to limit damage and keep the grid stable |
| Dependability | Operates when it should |
| Security | Stays quiet when it should not operate |
How are protection relays classified?
Each method answers a different question, so do not mix them in one flat list. A numerical relay (technology) can contain overcurrent (function) with an inverse-time curve (operating time) and protect a transformer (equipment) all at once.
Types of protection relays by technology
Relay technology has moved through four generations. Old relays are still working in many substations, so you will often meet all of them on one site.
| Feature | Electromechanical | Static (solid-state) | Digital | Numerical / IED |
|---|---|---|---|---|
| How it works | Magnetic force moves a disc, armature or plunger | Analogue electronic circuits | Samples signals and processes them digitally | Microprocessor runs several protection programs |
| Functions per device | Usually one | Few | Several | Many, plus control and monitoring |
| CT burden | High | Lower | Low | Very low |
| Self-monitoring | None | Limited | Better | Continuous self-checks |
| Fault records | None | Very limited | Event records | Event, fault and disturbance records |
| Communication | Hardwired contacts | Limited | Some protocols | IEC 61850, DNP3, Modbus |
| Maintenance | Frequent mechanical checks | Moderate | Firmware-aware testing | Configuration and cyber checks |
| Status today | Legacy, still installed | Legacy | Common | Standard for new projects |
Electromechanical relays
These work by magnetic attraction or induction. Attracted-armature relays use a plunger or hinged armature. Induction-disc and induction-cup relays use torque on a rotating disc or cup, which is why their operating time falls as current rises. They are rugged and simple, but they do one job each and need regular calibration.
Static relays
Static relays replace moving parts with transistors, diodes and amplifiers. They are faster, smaller and place less load on the CT than electromechanical designs. They are a stepping stone between the old and new generations.
Digital and numerical relays
Digital relays convert the measured signals into numbers and process them in a microprocessor. Numerical relays take this further, running many protection algorithms in one box with programmable logic, event recording and communication. In practice, manufacturers often use “digital” and “numerical” loosely, so treat the line between them as flexible rather than a strict rule.
Intelligent electronic devices (IEDs)
An IED is a numerical relay that also measures, controls and communicates. In a digital substation, IEDs share data over an Ethernet network using IEC 61850, which replaces large amounts of copper wiring. More on this in the numerical relay section below.
Types of protection relays by function
This is the classification that matters most when you choose or read about a relay. Each type below measures something different and guards against a different problem.
| Relay type | ANSI no. | IEC symbol | Measures | Protects against | Typical use |
|---|---|---|---|---|---|
| Instantaneous overcurrent | 50 | I>> | Phase current | Severe phase faults | Feeders, transformers, motors |
| Time overcurrent | 51 | I> | Phase current | Overloads, lower-level faults | Feeders, transformers, motors |
| Earth fault | 50N / 51N, 50G / 51G | I0> | Residual or neutral current | Faults to earth | Feeders, transformers |
| Directional overcurrent | 67 / 67N | Directional I> | Current and direction | Faults in one direction | Ring mains, parallel feeders |
| Distance | 21 | Z< | Impedance (V ÷ I) | Line faults by distance | Transmission lines |
| Differential | 87 (87T, 87G, 87B, 87L, 87M) | ΔI | Current in versus out | Internal faults | Transformers, generators, busbars |
| Undervoltage | 27 | U< | Voltage | Low voltage | Motors, buses |
| Overvoltage | 59 | U> | Voltage | High voltage | Generators, capacitor banks |
| Underfrequency | 81U | f< | Frequency | Generation shortage | Load shedding |
| Overfrequency | 81O | f> | Frequency | Excess generation | Generators, islands |
| Reverse power | 32 | P< | Direction of active power | Generator motoring | Generators |
| Negative sequence | 46 | I2> | Unbalanced current | Rotor heating | Motors, generators |
| Thermal overload | 49 | θ> | Heating model | Sustained overload | Motors, cables, transformers |
| Loss of excitation | 40 | — | Impedance or reactive power | Loss of generator field | Synchronous generators |
| Overexcitation (V/Hz) | 24 | V/Hz> | Volts per hertz | Core overheating | Transformers, generators |
| Buchholz (gas) | 63 family | — | Gas and oil surge | Internal transformer faults | Oil-filled transformers |
| Breaker failure | 50BF | — | Current after trip command | A breaker that fails to open | Substations |
| Auto-reclose | 79 | — | Breaker and line state | Temporary faults | Overhead lines |
| Synchro-check | 25 | — | Voltage, frequency, angle | Unsafe closing | Generators, bus couplers |
| Lockout | 86 | — | Trip logic | Unwanted reclosing | Transformer, generator schemes |
Overcurrent relay (ANSI 50/51)
The simplest and most common type. It operates when current rises above a set pickup value. The 50 element trips with no intentional delay for large faults; the 51 element trips after a delay that shortens as current increases. It suits radial feeders, motors and transformers, and often acts as backup elsewhere.
Earth fault relay (ANSI 50N/51N)
A normal overcurrent relay is set above load current, so it can miss small earth faults. An earth fault relay measures only the residual (neutral) current, which is close to zero in a healthy system, so it can be set far more sensitively. The “N” suffix means the residual current is calculated from the three phases, while “G” means it comes from a separate core-balance CT.
Directional overcurrent relay (ANSI 67)
Where power can flow both ways, such as ring mains and parallel feeders, a standard overcurrent relay could trip for a fault behind it. A directional relay compares current with a voltage reference and operates only for faults in its set direction.
Distance relay (ANSI 21)
A distance relay divides voltage by current to calculate impedance. Because line impedance is roughly proportional to length, a lower value means a closer fault. Its settings are arranged in zones: Zone 1 trips instantly for faults on most of the protected line, while Zones 2 and 3 are time-delayed backup. Common characteristics are impedance, reactance and mho. It is the main protection for transmission lines.
Differential relay (ANSI 87)
This relay applies Kirchhoff’s current law: current entering a protected zone should equal current leaving it. Any difference means a fault inside. Because it responds only to internal faults, it is fast and very sensitive. Variants include 87T (transformer), 87G (generator), 87B (busbar), 87L (line) and 87M (motor).
Voltage and frequency relays (ANSI 27, 59, 81)
Undervoltage (27) and overvoltage (59) relays watch voltage. Underfrequency (81U) relays support load shedding when generation falls short, and overfrequency (81O) relays protect against too much generation or islanding.
Reverse power, negative sequence and thermal relays (ANSI 32, 46, 49)
A reverse power relay detects a generator drawing power from the grid and acting as a motor, which can damage the prime mover. A negative sequence relay detects unbalanced currents that overheat rotors. A thermal overload relay uses a heating model of the motor, cable or transformer to trip before damage occurs. For motor circuits, it also helps to understand the breakers beside them; see MCB vs MCCB vs ACB.
Loss of excitation and overexcitation relays (ANSI 40, 24)
Loss of excitation (40) protects a synchronous generator if its field is lost. Overexcitation (24) measures volts per hertz and trips when a transformer or generator core risks overheating from over-fluxing.
Buchholz relay (ANSI 63)
A Buchholz relay is a mechanical device between the transformer tank and its conservator. Slow gas build-up from a minor fault triggers an alarm; a sudden oil surge from a serious fault trips the transformer. It detects problems that electrical relays may miss.
Restricted earth fault relay (REF)
REF is a high-sensitivity differential scheme that covers only the winding to earth. It detects low-level earth faults near the neutral of a transformer or generator that a full differential relay might not see.
Arc flash relay
Arc flash relays use light sensors, often with a current check, to detect an arc inside switchgear and trip within a few milliseconds. Their speed greatly reduces damage and risk to people. They are used inside switchgear panels.
Breaker failure, auto-reclose, synchro-check and lockout relays
- Breaker failure (50BF): if current still flows after a trip command, it trips the neighbouring breakers.
- Auto-reclose (79): recloses a line after a trip. Most overhead-line faults, such as lightning, are temporary, so supply is restored quickly. A permanent fault trips it again and locks out.
- Synchro-check (25): allows a breaker to close only when voltage, frequency and phase angle on both sides match.
- Lockout (86): latches the trip and blocks closing until someone resets it by hand.
Pilot and communication-based protection
Pilot schemes compare information from both ends of a line over a communication link. Line differential and phase comparison protection are examples. They clear faults along the whole line quickly, which distance relays alone cannot always do.
Types of protection relays by operating time
| Type | How it behaves | Best for |
|---|---|---|
| Instantaneous | Trips with no intentional delay once pickup is exceeded | Severe, close-in faults |
| Definite time | Trips after a fixed delay, whatever the current | Simple grading where fault current barely changes |
| Inverse time (IDMT) | Higher current means faster trip | Feeders and transformers needing coordination |
IDMT stands for inverse definite minimum time. Two settings shape the curve: the pickup current (Is), and the time multiplier setting (TMS), which moves the whole curve up or down. IEC 60255-151 and IEEE C37.112 define the standard shapes. The IEC formula is:
t = TMS × k ÷ ((I ÷ Is)α − 1)
| IEC curve | k | α | At 2 × Is | At 5 × Is | At 10 × Is | At 20 × Is |
|---|---|---|---|---|---|---|
| Standard inverse (SI) | 0.14 | 0.02 | 10.03 s | 4.28 s | 2.97 s | 2.27 s |
| Very inverse (VI) | 13.5 | 1 | 13.50 s | 3.38 s | 1.50 s | 0.71 s |
| Extremely inverse (EI) | 80 | 2 | 26.67 s | 3.33 s | 0.81 s | 0.20 s |
| Long-time inverse (LTI) | 120 | 1 | 120.00 s | 30.00 s | 13.33 s | 6.32 s |
Notice how the extremely inverse curve is slowest at low current but fastest at high current. That steep shape suits fuse coordination and motor feeders, while long-time inverse suits protection that must ride through long starting currents.
Protection relays by protected equipment
Different equipment fails in different ways, so each gets its own mix of relays. The table shows typical functions. It is a guide, not a design recipe.
| Equipment | Typical relay functions |
|---|---|
| Generator | 87G differential, 40 loss of excitation, 32 reverse power, 46 negative sequence, 49 thermal, 24 V/Hz, 27/59 voltage, 81 frequency, 50BF |
| Transformer | 87T differential, REF, 50/51 and 50N/51N overcurrent, 63 Buchholz, 24 over-excitation, 49 thermal, 86 lockout |
| Motor | 49 thermal overload, 50/51 overcurrent, 46 unbalance, 27 undervoltage, 50N/51N earth fault, 87M for large motors |
| Feeder | 50/51 and 50N/51N, 67/67N where power flows both ways, 79 auto-reclose, 50BF |
| Transmission line | 21 distance, 87L line differential, 67/67N backup, 79 auto-reclose, pilot schemes, 50BF |
| Busbar | 87B busbar differential (high or low impedance), 50BF, 86 lockout |
| Capacitor bank | 59 overvoltage, unbalance protection, 50/51 overcurrent, 50N/51N earth fault |
Most of these relays sit in switchgear panels at substations and plants, which is where you will usually see them in the field.
Protection zones, primary protection and backup
A protection zone is the part of the system a given relay is responsible for. Zones overlap at circuit breakers so that no gap exists between them.
- Primary protection acts first for faults in its own zone.
- Backup protection acts if the primary relay or its breaker fails. Local backup sits at the same location; remote backup sits at the next substation.
- Coordination means setting the time and current of each relay so the nearest one to the fault operates first.
Numerical relays, IEC 61850 and cybersecurity
Modern substations are moving to digital designs. Numerical relays are the building blocks, and IEC 61850 is the language they speak.
- GOOSE messages let IEDs send fast trip and blocking signals to each other over Ethernet instead of copper wires.
- Sampled values carry digitised CT and VT data across the network.
- Recorders store fault and disturbance data, helping engineers find the cause after a trip.
- Self-supervision raises an alarm if the relay itself develops a fault.
Connected relays also create cyber risk. IEC 62351 covers security for power-system communications, and NERC CIP applies to critical assets in North America. Good practice includes controlled access, network separation, secure configuration, firmware control and logging.
ANSI device numbers, IEC symbols and key standards
ANSI numbers (from IEEE C37.2) name the function of a device, such as 51 for time overcurrent. IEC symbols such as I>, U< and Z< describe the measured quantity. They work side by side but are different systems, so never treat them as exact matches. In India you will see both on drawings, along with CEA regulations, CBIP guidance and utility specifications.
| Standard | What it covers |
|---|---|
| IEEE C37.2 | Device function numbers, acronyms and contact designations |
| IEC 60255-151 | Functional requirements for over- and under-current protection (Edition 1.0, 2009) |
| IEEE C37.112 | Inverse-time characteristic equations for overcurrent relays (2018) |
| IEC 61850 | Communication networks and systems for power utility automation |
| IEC 62351 | Cybersecurity for power-system communications |
| IEEE C37.90 | Relay performance and environmental requirements |
Why protection relays misoperate
A misoperation means the protection failed to operate, operated too slowly, or tripped when it should not. The ReliabilityFirst 2025 assessment recorded 133 misoperations in its region in 2024, down from a high of 277 in 2016. Its 2020–2024 analysis shows where the causes lie:
Human performance and equipment problems account for most cases. The practical lessons are simple:
- Check relay settings and logic against the approved settings file after every change.
- Test CT and VT wiring, polarity and ratios during commissioning.
- Test the trip circuit and DC supply, not only the relay.
- Review event and fault records after each operation.
- Follow the manufacturer’s and utility’s test routines. Secondary injection checks the relay; primary injection checks the whole CT-to-relay path.
How big is the protection relay market?
Published market sizes vary because each research firm uses a different scope. The estimates for 2025 range from about USD 2.27 billion to USD 3.8 billion, so treat them as a range, not a fixed figure. Reports agree that Asia-Pacific is the largest region and that digital and numerical relays are growing fastest.
Frequently asked questions
What are the main types of protection relays?
The main types by function are overcurrent, earth fault, directional, distance, differential, voltage, frequency, reverse power and thermal relays. By technology they are electromechanical, static, digital and numerical.
What is the most commonly used protection relay?
The overcurrent relay (ANSI 50/51) is the most widely used because it is simple and suits feeders, motors and transformers.
Does a protection relay interrupt fault current?
No. The relay detects the fault and sends a trip signal. The circuit breaker interrupts the current.
What is the difference between a numerical and a digital relay?
Both process signals digitally. Numerical relays are the more advanced multifunction type with programmable logic, recording and networking. Manufacturers often use the terms loosely.
What does ANSI device number 21 mean?
It is a distance relay, which measures impedance to find how far along a line a fault lies.
What is an ANSI 50/51 relay?
ANSI 50 is an instantaneous overcurrent function and ANSI 51 is a time-delayed overcurrent function.
What is the function of a differential relay?
It compares current entering and leaving a protected zone and trips if they differ, which indicates an internal fault.
Which relays protect a transformer?
Typically differential (87T), Buchholz (63), restricted earth fault, overcurrent (50/51) and earth fault (50N/51N), plus thermal and over-excitation protection.
What is an IDMT relay?
An inverse definite minimum time relay trips faster as fault current rises. The TMS setting moves its curve up or down.
What is the difference between primary and backup protection?
Primary protection acts first in its own zone. Backup protection acts only if the primary protection or its breaker fails.
Conclusion
Protection relays can be sorted by technology, function, operating time and protected equipment. For day-to-day work, function is the most useful lens: overcurrent and earth fault for feeders, distance for lines, differential for transformers, generators and busbars, and voltage, frequency and thermal relays for supporting roles. Pair that with the right zones, backup and coordination, and numerical relays give a fast, well-recorded and reliable protection system.
Disclaimer: This article is for education. Relay selection, settings, testing and commissioning must be carried out by qualified protection engineers following manufacturer instructions, local regulations and utility requirements.