ANSI device numbers are short numeric codes that tell you what a protection, control or switching device does in a power system. They come from the IEEE C37.2 standard. For example, 50 is instantaneous overcurrent, 51 is time-delayed overcurrent, 52 is an AC circuit breaker, 86 is a lockout relay and 87 is differential protection. The full list, suffix letters and IEC 61850 equivalents are all below.
Table of contents
- ANSI Device Numbers: Quick Answer Table
- What Are ANSI Device Numbers?
- IEEE C37.2: The Standard Behind the Numbers
- Complete ANSI Device Numbers List (1–94)
- ANSI Device Numbers 1–20: Control and Machine Functions
- ANSI Device Numbers 21–40: Protection and Generator Functions
- ANSI Device Numbers 41–60: Protection and Switching Functions
- ANSI Device Numbers 61–80: Monitoring and Protection Functions
- ANSI Device Numbers 81–94: Frequency, Differential and Auxiliary Functions
- How the Device Numbers Are Grouped
- ANSI Device Number Suffix Letters and Their Meanings
- Difference Between 50N, 50G, 51N and 51G
- Combined ANSI Device Numbers
- ANSI Device Numbers by Protected Equipment
- ANSI Device Numbers vs IEC 61850 Logical Nodes
- ANSI Numbers vs IEC Graphical Symbols
- How to Read ANSI Device Numbers on a Single-Line Diagram
- Worked Examples of Relay Labels
- Common Misconceptions About ANSI Device Numbers
- Frequently Asked Questions About ANSI Device Numbers
- What are ANSI device numbers?
- What is the ANSI device number for an instantaneous overcurrent relay?
- What is the difference between ANSI 50 and 51?
- What does ANSI 87 mean?
- What is an ANSI 86 lockout relay?
- Why is a circuit breaker called device 52?
- What does the N suffix mean?
- What does G mean in ANSI relay numbers?
- What is ANSI 79 used for?
- What does ANSI 81 mean?
- What is the IEC equivalent of ANSI device numbers?
- Are ANSI device numbers used in India?
- How many ANSI device numbers are there?
- Conclusion
ANSI Device Numbers: Quick Answer Table
These are the numbers you will meet most often on single-line diagrams and relay settings sheets. Use this table first, then jump to the full list if you need a rarer number.
| ANSI no. | Function | What it does |
|---|---|---|
| 21 | Distance relay | Measures impedance to find line faults |
| 24 | Volts-per-hertz relay | Detects over-fluxing |
| 25 | Synchronism check | Allows two supplies to be paralleled safely |
| 27 | Undervoltage relay | Operates when voltage is too low |
| 32 | Directional power relay | Detects reverse or directional power flow |
| 40 | Loss-of-excitation relay | Detects generator field failure |
| 46 | Phase-balance current relay | Detects current unbalance |
| 47 | Phase-sequence / voltage-balance relay | Detects wrong phase sequence or unbalanced voltage |
| 49 | Thermal relay | Protects against overheating |
| 50 | Instantaneous overcurrent | Trips at once on very high current |
| 51 | AC time overcurrent | Trips after a delay that depends on current |
| 52 | AC circuit breaker | Opens and closes the AC circuit |
| 59 | Overvoltage relay | Operates when voltage is too high |
| 63 | Pressure device | Detects abnormal pressure, such as gas surge in a transformer |
| 64 | Ground protective relay | Detects earth faults |
| 67 | Directional overcurrent | Detects overcurrent in one direction only |
| 79 | AC reclosing relay | Recloses a breaker automatically after a trip |
| 81 | Frequency relay | Detects over- or underfrequency |
| 86 | Lockout relay | Latches a trip until someone resets it |
| 87 | Differential relay | Compares current in and out of a protected zone |
What Are ANSI Device Numbers?
An ANSI device number identifies a function, not a specific box. The number is printed on drawings, relay nameplates, settings files and alarm lists, so everyone reads the same thing. A “51” on a drawing means time-delayed overcurrent protection, whoever made the relay.
In older electromechanical schemes, one number usually meant one relay. Modern numerical relays, also called intelligent electronic devices (IEDs), can run dozens of numbered functions in a single unit. Device number 11 is used for such a multifunction device. If you are new to the hardware side, our guide to the types of protection relays explains how these devices have changed over time.
You will see the numbers on:
- Single-line diagrams (SLDs) and protection schematics
- Relay panels and nameplates
- Numerical relay configuration and settings documents
- Substation drawings, commissioning records and alarm schedules
IEEE C37.2: The Standard Behind the Numbers
The governing standard is IEEE C37.2, titled IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations. The current edition is C37.2-2022, published on 14 December 2022. It replaces C37.2-2008.
The 2022 edition assigns 95 device numbers and 22 acronyms. The 2008 edition assigned 95 numbers and 17 acronyms. The extra acronyms cover modern substation functions such as arc-flash detection, phasor measurement and trip-circuit monitoring. The numbering system itself dates back to 1928, when it began as AIEE Standard No. 26.
The numbers are used well beyond the United States, including in India, the UK, the Middle East and Latin America. Europe and many newer digital substations also use IEC symbols and IEC 61850 logical nodes, covered later in this guide.
Complete ANSI Device Numbers List (1–94)
Not every integer from 1 to 99 is an assigned function. The standard assigns 95 numbers, and numbers 95 to 99 are for specific applications where no other number fits. The table below covers 1 to 94 in plain language. Names are standard-style and the meanings are written in our own words. Always confirm exact wording against the purchased IEEE C37.2-2022 text before using a number in a contract or drawing.
ANSI Device Numbers 1–20: Control and Machine Functions
| No. | Device name | Plain-language meaning | Category | Typical application |
|---|---|---|---|---|
| 1 | Master element | Starts or permits a control sequence | Control | Control switch |
| 2 | Time-delay starting or closing relay | Adds a deliberate delay before starting or closing | Control | Motor starting sequences |
| 3 | Checking or interlocking relay | Allows an action only when set conditions are met | Control | Interlock schemes |
| 4 | Master contactor | Main control contactor in a scheme (legacy use) | Control | Older control schemes |
| 5 | Stopping device | Shuts equipment down | Machine control | Motor stop circuits |
| 6 | Starting circuit breaker | Connects a machine for starting | Machine control | Motor starters |
| 7 | Rate-of-change relay | Reacts to how fast a quantity changes | Protection | ROCOF schemes |
| 8 | Control-power disconnecting device | Isolates the control supply | Auxiliary | Control supply fuses and switches |
| 9 | Reversing device | Reverses direction or phase rotation | Machine control | Reversing starters |
| 10 | Unit sequence switch | Steps a unit through its sequence | Control | Multi-unit plant |
| 11 | Multifunction device | One unit performing several numbered functions | Control | Numerical relays and IEDs |
| 12 | Overspeed device | Detects excessive speed | Machine control | Turbines, motors |
| 13 | Synchronous-speed device | Detects that speed has reached synchronous speed | Machine control | Synchronous machines |
| 14 | Underspeed device | Detects speed below a set value | Machine control | Turbines, motors |
| 15 | Speed or frequency matching device | Matches speed or frequency before paralleling | Generator | Generator synchronising |
| 16 | Data communications device | Handles data links between devices | Auxiliary | Gateways, Ethernet switches |
| 17 | Shunting or discharge switch | Shorts or discharges a circuit | Switching | Field and capacitor circuits |
| 18 | Accelerating or decelerating device | Controls how quickly speed changes | Machine control | Drives |
| 19 | Start-to-run transition contactor | Moves a motor from starting to running connection | Machine control | Reduced-voltage starters |
| 20 | Electrically operated valve | Valve operated by a solenoid or motor | Control | Plant auxiliaries |
ANSI Device Numbers 21–40: Protection and Generator Functions
| No. | Device name | Plain-language meaning | Category | Typical application |
|---|---|---|---|---|
| 21 | Distance relay | Trips when measured impedance falls inside a set reach | Protection | Transmission lines, feeders |
| 22 | Equalizer circuit breaker | Connects equalising paths | Switching | DC and older schemes |
| 23 | Temperature control device | Keeps temperature within limits | Auxiliary | Panel heaters |
| 24 | Volts-per-hertz relay | Detects too much voltage for the frequency | Protection | Transformers, generators |
| 25 | Synchronism-check device | Permits closing only when voltage, phase and frequency match | Generator | Generators, bus-ties |
| 26 | Apparatus thermal device | Detects abnormal equipment temperature | Auxiliary | Transformer winding temperature |
| 27 | Undervoltage relay | Operates when voltage falls below its setting | Protection | Buses, motors, feeders |
| 28 | Flame detector | Senses presence of flame | Auxiliary | Burner systems |
| 29 | Isolating contactor or switch | Isolates a circuit for safety or maintenance | Switching | Auxiliary circuits |
| 30 | Annunciator relay | Gives a visible or audible warning of a condition | Auxiliary | Alarm panels |
| 31 | Separate excitation device | Connects a separate excitation source | Generator | Excitation systems |
| 32 | Directional power relay | Detects the direction of power flow | Protection | Generators, interconnections |
| 33 | Position switch | Shows when a part reaches a set position | Auxiliary | Switchgear mechanisms |
| 34 | Master sequence device | Governs a series of operations | Control | Automated schemes |
| 35 | Brush-operating or slip-ring short-circuiting device | Lifts brushes or shorts slip rings | Machine control | Wound-rotor machines |
| 36 | Polarity or polarising-voltage device | Sets or monitors polarity | Control | Special schemes |
| 37 | Undercurrent or underpower relay | Detects loss of load | Protection | Motors, pumps, generators |
| 38 | Bearing protective device | Detects bearing temperature or distress | Auxiliary | Rotating machines |
| 39 | Mechanical condition monitor | Detects vibration or mechanical faults | Auxiliary | Rotating machines |
| 40 | Field relay (loss of excitation) | Detects loss or abnormal level of field current | Generator | Synchronous generators |
ANSI Device Numbers 41–60: Protection and Switching Functions
| No. | Device name | Plain-language meaning | Category | Typical application |
|---|---|---|---|---|
| 41 | Field circuit breaker | Connects or removes the field supply | Generator | Excitation systems |
| 42 | Running circuit breaker | Connects a machine for normal running | Machine control | Motor circuits |
| 43 | Manual transfer or selector device | Lets an operator select a mode or supply | Control | Local/remote selectors |
| 44 | Unit sequence starting relay | Starts the next unit in a sequence | Control | Multi-unit plant |
| 45 | Atmospheric condition monitor | Detects smoke, fumes or other hazardous conditions | Auxiliary | Substations, plant rooms |
| 46 | Reverse-phase or phase-balance current relay | Detects unbalanced or reversed phase currents | Protection | Motors, generators |
| 47 | Phase-sequence or voltage-balance relay | Detects wrong phase order or unbalanced voltage | Protection | Motors, incomers |
| 48 | Incomplete-sequence relay | Detects a start sequence that did not finish | Machine control | Motor starters |
| 49 | Machine or transformer thermal relay | Models heating to protect against overload | Protection | Motors, transformers |
| 50 | Instantaneous overcurrent relay | Trips with no deliberate delay on high current | Protection | Feeders, motors, transformers |
| 51 | AC time overcurrent relay | Trips after a delay that shortens as current rises | Protection | Feeders, motors, transformers |
| 52 | AC circuit breaker | Makes and breaks the AC circuit, including fault current | Switching | All AC switchgear |
| 53 | Exciter or DC generator relay | Controls build-up of excitation | Generator | Older excitation systems |
| 54 | Turning-gear engaging device | Engages turning gear on a shaft | Generator | Turbine-generators |
| 55 | Power-factor relay | Operates at a set power factor | Generator | Synchronous machines |
| 56 | Field-application relay | Applies field at the right moment | Generator | Synchronous motors |
| 57 | Short-circuiting or grounding device | Shorts or earths a circuit | Switching | Maintenance earthing |
| 58 | Rectification failure relay | Detects a rectifier fault | Control | Rectifiers, chargers |
| 59 | Overvoltage relay | Operates when voltage rises above its setting | Protection | Buses, generators |
| 60 | Voltage or current balance relay | Detects imbalance between two circuits | Protection | Capacitor banks, VT supervision |
ANSI Device Numbers 61–80: Monitoring and Protection Functions
| No. | Device name | Plain-language meaning | Category | Typical application |
|---|---|---|---|---|
| 61 | Density switch or sensor | Detects insulating-gas density | Auxiliary | SF6 switchgear |
| 62 | Time-delay stopping or opening relay | Delays a stop or open command | Control | Sequence control |
| 63 | Pressure switch or detector | Detects abnormal pressure or gas surge | Protection | Transformers, GIS |
| 64 | Ground protective relay | Detects an earth fault | Protection | Generators, transformers |
| 65 | Governor | Controls prime-mover speed or output | Generator | Turbines, engines |
| 66 | Notching or jogging device | Limits starts per hour or allows jogging | Machine control | Motors |
| 67 | AC directional overcurrent relay | Overcurrent protection that looks at current direction | Protection | Parallel feeders, ring mains |
| 68 | Blocking or power-swing blocking relay | Blocks tripping during power swings | Protection | Transmission lines |
| 69 | Permissive control device | Allows a control action when conditions suit | Control | Interlocks |
| 70 | Rheostat | Variable resistor | Auxiliary | Older control circuits |
| 71 | Liquid or gas level switch | Detects level | Auxiliary | Transformer oil, tanks |
| 72 | DC circuit breaker | Makes and breaks a DC circuit | Switching | Battery and DC systems |
| 73 | Load-resistor contactor | Switches a load resistor in or out | Switching | DC and braking circuits |
| 74 | Alarm relay | Gives an alarm output | Auxiliary | Substation alarms |
| 75 | Position-changing mechanism | Moves a device between positions | Switching | Draw-out breaker drives |
| 76 | DC overcurrent relay | Overcurrent protection for DC circuits | Protection | DC systems |
| 77 | Telemetering device | Sends measured values to a remote point | Auxiliary | SCADA transducers |
| 78 | Phase-angle or out-of-step relay | Detects loss of synchronism between systems | Protection | Generators, interconnections |
| 79 | AC reclosing relay | Recloses a breaker after a trip | Protection | Overhead lines, feeders |
| 80 | Liquid or gas flow relay | Detects flow, or loss of flow | Auxiliary | Cooling systems |
ANSI Device Numbers 81–94: Frequency, Differential and Auxiliary Functions
| No. | Device name | Plain-language meaning | Category | Typical application |
|---|---|---|---|---|
| 81 | Frequency relay | Operates on over- or underfrequency | Protection | Grids, generators |
| 82 | DC reclosing relay | Recloses a DC circuit breaker | Protection | DC systems |
| 83 | Automatic selective control or transfer relay | Switches automatically between supplies | Control | Bus transfer schemes |
| 84 | Operating mechanism | Stored-energy or motor drive for a switch | Switching | Breaker mechanisms |
| 85 | Pilot communications relay | Uses a communication channel for protection signals | Auxiliary | Teleprotection |
| 86 | Lockout relay | Latches a trip and blocks closing until reset | Protection | Transformers, buses, generators |
| 87 | Differential protective relay | Trips when current in and out of a zone does not balance | Protection | Transformers, buses, generators, lines |
| 88 | Auxiliary motor or motor-generator | Drives auxiliary equipment | Machine control | Pumps, fans, motor-generator sets |
| 89 | Line switch (isolator) | Isolates equipment; not normally used to break load | Switching | Substations |
| 90 | Regulating device | Holds a quantity such as voltage steady | Control | Tap changers, AVRs |
| 91 | Voltage directional relay | Responds to voltage direction | Protection | Special schemes |
| 92 | Voltage and power directional relay | Responds to voltage and power direction together | Protection | Special schemes |
| 93 | Field-changing contactor | Changes the field connection or value | Generator | Excitation systems |
| 94 | Tripping or trip-free relay | Starts or assists a trip command | Protection | Trip circuits |
Numbers 95 to 99: these are for specific applications that no other number covers. IEEE C37.2-2022 also adds modern acronyms alongside the numbers, so check the current standard for exact assignments before you quote them.
How the Device Numbers Are Grouped
We grouped numbers 1 to 94 by their main job. Protection is the largest group, which is why most day-to-day work revolves around a small set of numbers. This grouping is our own editorial one, so another author may place a few numbers differently.
numbers
- Protection: 27 (29%)
- Auxiliary and monitoring: 17 (18%)
- Control and sequencing: 16 (17%)
- Machine control: 13 (14%)
- Generator and synchronising: 11 (12%)
- Switching and isolating: 10 (11%)
The switching group includes numbers 52 and 89. To see how breakers differ in practice, read our guide to types of circuit breakers or the comparison of MCB, MCCB and ACB.
ANSI Device Number Suffix Letters and Their Meanings
Letters added after a number narrow down what the function measures or protects. So 50 is “instantaneous overcurrent”, while 50N is the same function connected to neutral current. Suffix meanings depend on context and sometimes on the manufacturer, so always check the relay manual.
| Suffix | Common meaning | Example | Note |
|---|---|---|---|
| N | Neutral or residual | 50N, 51N | Measures earth current through the neutral or residual connection |
| G | Ground, or generator | 51G, 87G | Ground in overcurrent codes; generator in differential codes |
| P | Phase | 50P, 51P | Phase-fault elements |
| T | Transformer | 87T | Can also mean time delay in other codes |
| B | Bus | 87B | Busbar zone |
| L | Line | 87L | Line current differential |
| M | Motor | 87M | Context dependent |
| U | Under (or unit) | 81U | Underfrequency in 81U |
| O | Over | 81O | Overfrequency in 81O |
| BF | Breaker failure | 50BF | Backup if a breaker does not clear a fault |
| X, Y, Z | Auxiliary devices | 27X | Usually auxiliary relays tied to the main function |
Difference Between 50N, 50G, 51N and 51G
All four are earth-fault overcurrent functions. The difference is where the current signal comes from. N elements usually use the residual current of the three phase CTs (or a neutral CT). G elements usually use a dedicated ground CT, such as a core-balance CT around the cable. The numbers still carry the timing: 50 trips without deliberate delay, 51 trips after a time delay. Some manufacturers use the letters the other way round, so confirm against the relay manual.
Combined ANSI Device Numbers
Numbers are often written together because one relay performs several functions. A slash separates them.
| Label | Meaning | Where it is used |
|---|---|---|
| 50/51 | Instantaneous and time-delayed phase overcurrent in one relay | Feeders, motors, transformer incomers |
| 50N/51N | Instantaneous and time-delayed neutral overcurrent | Earth-fault protection on solidly or resistance earthed systems |
| 50G/51G | Instantaneous and time-delayed ground overcurrent | Cable feeders with a core-balance CT |
| 27/59 | Undervoltage and overvoltage functions | Buses, generators, grid interconnections |
| 81O/81U | Overfrequency and underfrequency | Generators, load shedding |
| 87T/50/51 | Transformer differential with overcurrent backup | Power transformer protection panels |
| 50BF | Breaker-failure protection | Substations with a bus-wide trip scheme |
| 64REF / 87N | Restricted earth-fault protection | Transformer windings (naming varies by vendor) |
ANSI Device Numbers by Protected Equipment
This matrix shows which numbers are commonly found on each type of equipment. It is a guide to what you may see on drawings, not a design rule. The actual scheme depends on the equipment, system and utility requirements.
| Equipment | Commonly used numbers | Notes |
|---|---|---|
| Generator | 25, 27, 32, 40, 46, 49, 51V, 59, 64, 81, 87G | 32 detects reverse power; 40 detects loss of field; 87G is generator differential |
| Power transformer | 24, 49, 50/51, 51N, 63, 87T | 63 covers gas or sudden-pressure devices; 87T is the main fast protection |
| Motor | 37, 46, 47, 49, 50/51, 66, 87M | 46 and 47 catch unbalance and wrong sequence; 49 models heating |
| Line or feeder | 21, 50/51, 67, 79, 87L | 21 on longer lines; 79 on overhead lines where faults are often temporary |
| Busbar | 50BF, 86, 87B | 87B trips all connected breakers; 86 holds the trip |
| Capacitor bank | 27, 50/51, 59, 60 | 60 is often used for unbalance; scheme varies with bank design |
Many of these functions are fitted inside switchgear panels, where the relay, breaker (52) and isolator (89) sit together in one lineup.
ANSI Device Numbers vs IEC 61850 Logical Nodes
IEC 61850 does not replace ANSI numbers with one symbol each. It describes functions as logical nodes, which are software building blocks that digital substation devices use to share data. Each logical node has a four-letter name, such as PDIS for distance protection. ANSI numbers describe what the function is. Logical nodes describe how it is modelled and communicated.
| ANSI function | IEC 61850 logical node | Function |
|---|---|---|
| 21 | PDIS | Distance protection |
| 50 / 51 / 67 | PTOC (some vendors use PIOC for 50, PDEF for earth-fault direction) | Overcurrent protection |
| 27 | PTUV | Undervoltage protection |
| 59 | PTOV | Overvoltage protection |
| 81O | PTOF | Overfrequency protection |
| 87 | PDIF | Differential protection |
| 50BF | RBRF | Breaker-failure protection |
| 79 | RREC | Auto-reclosing |
| 52 | XCBR | Circuit breaker |
| 89 | XSWI | Isolator or switch |
These are representative examples, not a universal one-to-one conversion. Mappings differ between manufacturers and between relay models, so use the relay’s own IEC 61850 conformance document when you need exact names. ANSI numbers and IEC 61850 normally sit side by side in modern relays: the number appears on drawings and settings, and the logical node is used in the communication model.
ANSI Numbers vs IEC Graphical Symbols
IEC graphical symbols (IEC 60617) draw a device on a diagram, for example a relay coil or a breaker. An ANSI number says what the device does. Drawings can use both together, such as an IEC symbol for a relay labelled “51”. European and IEC-led projects tend to lean on symbols and logical nodes; North American, Indian and many international projects use ANSI numbers widely.
How to Read ANSI Device Numbers on a Single-Line Diagram
A single-line diagram shows the main equipment as one line. Device numbers appear in small circles or boxes next to the breaker, transformer or feeder they act on. The number tells you which protection function is present, and the suffix tells you what it watches. Primary protection (such as 87T) acts fastest on its own zone, while backup protection (such as 51 or 50BF) acts later or covers a neighbouring zone.
Worked Examples of Relay Labels
| Label | How to read it |
|---|---|
| 50/51 | Base functions 50 and 51: instantaneous plus time-delayed phase overcurrent. |
| 50N/51N | The same pair, with suffix N: both use neutral or residual earth current. |
| 87T | Base 87 (differential) with suffix T: transformer differential protection. |
| 87T/50/51N | Transformer differential, plus phase instantaneous and time-delayed overcurrent, plus neutral time-delayed overcurrent, usually all in one IED. |
To decode any label, split it at the slashes, read each base number from the list, then apply the suffix. Our guide on fuse vs circuit breaker is a useful companion if you want to understand what happens after the relay sends its trip signal.
Common Misconceptions About ANSI Device Numbers
| Misconception | Reality |
|---|---|
| They are only used in the United States. | They are used worldwide, including India and the UK, alongside IEC practice. |
| Each number is a separate physical relay. | One modern IED can host many numbered functions. |
| Every number from 1 to 99 has a defined function. | The standard assigns 95 numbers; 95–99 are for specific applications. |
| A suffix letter always means the same thing. | G, T, B and others change meaning with context. |
| ANSI numbers and IEC 61850 logical nodes are identical. | They describe different things and do not map one-to-one. |
Frequently Asked Questions About ANSI Device Numbers
What are ANSI device numbers?
They are standard numeric codes from IEEE C37.2 that identify the function of a protection, control or switching device in a power system.
What is the ANSI device number for an instantaneous overcurrent relay?
It is 50.
What is the difference between ANSI 50 and 51?
Device 50 trips with no deliberate delay when current passes its setting. Device 51 trips after a time delay that gets shorter as current rises.
What does ANSI 87 mean?
It means differential protection. The relay compares current entering and leaving a protected zone and trips if they do not balance.
What is an ANSI 86 lockout relay?
It is a latching relay that trips the connected breakers and blocks reclosing until it is reset by hand or remotely.
Why is a circuit breaker called device 52?
Because IEEE C37.2 assigns number 52 to the AC circuit breaker. The number is a convention, not a calculation.
What does the N suffix mean?
It usually means the function uses neutral or residual current, as in 50N and 51N.
What does G mean in ANSI relay numbers?
It usually means ground in overcurrent codes such as 51G, and generator in differential codes such as 87G.
What is ANSI 79 used for?
It is automatic reclosing. It closes a breaker again after a trip, which helps on overhead lines where many faults clear themselves.
What does ANSI 81 mean?
It is a frequency relay. 81O acts on overfrequency and 81U on underfrequency.
What is the IEC equivalent of ANSI device numbers?
There is no exact one-to-one equivalent. IEC 61850 uses logical nodes such as PTOC, PDIS and PDIF, and IEC 60617 provides graphical symbols.
Are ANSI device numbers used in India?
Yes. They are widely used on Indian utility, EPC and industrial drawings and relay settings, often alongside IEC practice.
How many ANSI device numbers are there?
IEEE C37.2-2022 assigns 95 device numbers and 22 acronyms.
Conclusion
ANSI device numbers give engineers a shared shorthand for what each device does. Learn the core set first (21, 27, 50, 51, 52, 59, 81, 86 and 87), then add suffixes and combined labels as you meet them on drawings. Bookmark this page as a quick reference, and see our overview of protection relays for the hardware behind the numbers.
Disclaimer: this is a general reference. Relay selection, settings, coordination, testing and commissioning must be carried out by qualified protection engineers in line with IEEE C37.2-2022, local regulations, utility requirements and project design documents.
Sources: IEEE Standards Association: C37.2-2022; Wikipedia: ANSI device numbers; IEC 61850-7-4 preview.