ANSI Device Numbers List: Complete Guide to IEEE C37.2 Relay Functions

By Rajiv Gupta 15 min read

ANSI device numbers are short numeric codes that tell you what a protection, control or switching device does in a power system. They come from the IEEE C37.2 standard. For example, 50 is instantaneous overcurrent, 51 is time-delayed overcurrent, 52 is an AC circuit breaker, 86 is a lockout relay and 87 is differential protection. The full list, suffix letters and IEC 61850 equivalents are all below.

Table of contents
  1. ANSI Device Numbers: Quick Answer Table
  2. What Are ANSI Device Numbers?
  3. IEEE C37.2: The Standard Behind the Numbers
  4. Complete ANSI Device Numbers List (1–94)
  5. ANSI Device Numbers 1–20: Control and Machine Functions
  6. ANSI Device Numbers 21–40: Protection and Generator Functions
  7. ANSI Device Numbers 41–60: Protection and Switching Functions
  8. ANSI Device Numbers 61–80: Monitoring and Protection Functions
  9. ANSI Device Numbers 81–94: Frequency, Differential and Auxiliary Functions
  10. How the Device Numbers Are Grouped
  11. ANSI Device Number Suffix Letters and Their Meanings
  12. Difference Between 50N, 50G, 51N and 51G
  13. Combined ANSI Device Numbers
  14. ANSI Device Numbers by Protected Equipment
  15. ANSI Device Numbers vs IEC 61850 Logical Nodes
  16. ANSI Numbers vs IEC Graphical Symbols
  17. How to Read ANSI Device Numbers on a Single-Line Diagram
  18. Worked Examples of Relay Labels
  19. Common Misconceptions About ANSI Device Numbers
  20. Frequently Asked Questions About ANSI Device Numbers
  21. What are ANSI device numbers?
  22. What is the ANSI device number for an instantaneous overcurrent relay?
  23. What is the difference between ANSI 50 and 51?
  24. What does ANSI 87 mean?
  25. What is an ANSI 86 lockout relay?
  26. Why is a circuit breaker called device 52?
  27. What does the N suffix mean?
  28. What does G mean in ANSI relay numbers?
  29. What is ANSI 79 used for?
  30. What does ANSI 81 mean?
  31. What is the IEC equivalent of ANSI device numbers?
  32. Are ANSI device numbers used in India?
  33. How many ANSI device numbers are there?
  34. Conclusion

ANSI Device Numbers: Quick Answer Table

These are the numbers you will meet most often on single-line diagrams and relay settings sheets. Use this table first, then jump to the full list if you need a rarer number.

ANSI no.FunctionWhat it does
21Distance relayMeasures impedance to find line faults
24Volts-per-hertz relayDetects over-fluxing
25Synchronism checkAllows two supplies to be paralleled safely
27Undervoltage relayOperates when voltage is too low
32Directional power relayDetects reverse or directional power flow
40Loss-of-excitation relayDetects generator field failure
46Phase-balance current relayDetects current unbalance
47Phase-sequence / voltage-balance relayDetects wrong phase sequence or unbalanced voltage
49Thermal relayProtects against overheating
50Instantaneous overcurrentTrips at once on very high current
51AC time overcurrentTrips after a delay that depends on current
52AC circuit breakerOpens and closes the AC circuit
59Overvoltage relayOperates when voltage is too high
63Pressure deviceDetects abnormal pressure, such as gas surge in a transformer
64Ground protective relayDetects earth faults
67Directional overcurrentDetects overcurrent in one direction only
79AC reclosing relayRecloses a breaker automatically after a trip
81Frequency relayDetects over- or underfrequency
86Lockout relayLatches a trip until someone resets it
87Differential relayCompares current in and out of a protected zone

What Are ANSI Device Numbers?

An ANSI device number identifies a function, not a specific box. The number is printed on drawings, relay nameplates, settings files and alarm lists, so everyone reads the same thing. A “51” on a drawing means time-delayed overcurrent protection, whoever made the relay.

In older electromechanical schemes, one number usually meant one relay. Modern numerical relays, also called intelligent electronic devices (IEDs), can run dozens of numbered functions in a single unit. Device number 11 is used for such a multifunction device. If you are new to the hardware side, our guide to the types of protection relays explains how these devices have changed over time.

You will see the numbers on:

  • Single-line diagrams (SLDs) and protection schematics
  • Relay panels and nameplates
  • Numerical relay configuration and settings documents
  • Substation drawings, commissioning records and alarm schedules

IEEE C37.2: The Standard Behind the Numbers

The governing standard is IEEE C37.2, titled IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations. The current edition is C37.2-2022, published on 14 December 2022. It replaces C37.2-2008.

The 2022 edition assigns 95 device numbers and 22 acronyms. The 2008 edition assigned 95 numbers and 17 acronyms. The extra acronyms cover modern substation functions such as arc-flash detection, phasor measurement and trip-circuit monitoring. The numbering system itself dates back to 1928, when it began as AIEE Standard No. 26.

Acronyms assigned by IEEE C37.2 edition 17 22 C37.2-2008 C37.2-2022 Device numbers assigned in both editions: 95
Source: IEEE Standards Association page for C37.2-2022.

The numbers are used well beyond the United States, including in India, the UK, the Middle East and Latin America. Europe and many newer digital substations also use IEC symbols and IEC 61850 logical nodes, covered later in this guide.

Complete ANSI Device Numbers List (1–94)

Not every integer from 1 to 99 is an assigned function. The standard assigns 95 numbers, and numbers 95 to 99 are for specific applications where no other number fits. The table below covers 1 to 94 in plain language. Names are standard-style and the meanings are written in our own words. Always confirm exact wording against the purchased IEEE C37.2-2022 text before using a number in a contract or drawing.

ANSI Device Numbers 1–20: Control and Machine Functions

No.Device namePlain-language meaningCategoryTypical application
1Master elementStarts or permits a control sequenceControlControl switch
2Time-delay starting or closing relayAdds a deliberate delay before starting or closingControlMotor starting sequences
3Checking or interlocking relayAllows an action only when set conditions are metControlInterlock schemes
4Master contactorMain control contactor in a scheme (legacy use)ControlOlder control schemes
5Stopping deviceShuts equipment downMachine controlMotor stop circuits
6Starting circuit breakerConnects a machine for startingMachine controlMotor starters
7Rate-of-change relayReacts to how fast a quantity changesProtectionROCOF schemes
8Control-power disconnecting deviceIsolates the control supplyAuxiliaryControl supply fuses and switches
9Reversing deviceReverses direction or phase rotationMachine controlReversing starters
10Unit sequence switchSteps a unit through its sequenceControlMulti-unit plant
11Multifunction deviceOne unit performing several numbered functionsControlNumerical relays and IEDs
12Overspeed deviceDetects excessive speedMachine controlTurbines, motors
13Synchronous-speed deviceDetects that speed has reached synchronous speedMachine controlSynchronous machines
14Underspeed deviceDetects speed below a set valueMachine controlTurbines, motors
15Speed or frequency matching deviceMatches speed or frequency before parallelingGeneratorGenerator synchronising
16Data communications deviceHandles data links between devicesAuxiliaryGateways, Ethernet switches
17Shunting or discharge switchShorts or discharges a circuitSwitchingField and capacitor circuits
18Accelerating or decelerating deviceControls how quickly speed changesMachine controlDrives
19Start-to-run transition contactorMoves a motor from starting to running connectionMachine controlReduced-voltage starters
20Electrically operated valveValve operated by a solenoid or motorControlPlant auxiliaries

ANSI Device Numbers 21–40: Protection and Generator Functions

No.Device namePlain-language meaningCategoryTypical application
21Distance relayTrips when measured impedance falls inside a set reachProtectionTransmission lines, feeders
22Equalizer circuit breakerConnects equalising pathsSwitchingDC and older schemes
23Temperature control deviceKeeps temperature within limitsAuxiliaryPanel heaters
24Volts-per-hertz relayDetects too much voltage for the frequencyProtectionTransformers, generators
25Synchronism-check devicePermits closing only when voltage, phase and frequency matchGeneratorGenerators, bus-ties
26Apparatus thermal deviceDetects abnormal equipment temperatureAuxiliaryTransformer winding temperature
27Undervoltage relayOperates when voltage falls below its settingProtectionBuses, motors, feeders
28Flame detectorSenses presence of flameAuxiliaryBurner systems
29Isolating contactor or switchIsolates a circuit for safety or maintenanceSwitchingAuxiliary circuits
30Annunciator relayGives a visible or audible warning of a conditionAuxiliaryAlarm panels
31Separate excitation deviceConnects a separate excitation sourceGeneratorExcitation systems
32Directional power relayDetects the direction of power flowProtectionGenerators, interconnections
33Position switchShows when a part reaches a set positionAuxiliarySwitchgear mechanisms
34Master sequence deviceGoverns a series of operationsControlAutomated schemes
35Brush-operating or slip-ring short-circuiting deviceLifts brushes or shorts slip ringsMachine controlWound-rotor machines
36Polarity or polarising-voltage deviceSets or monitors polarityControlSpecial schemes
37Undercurrent or underpower relayDetects loss of loadProtectionMotors, pumps, generators
38Bearing protective deviceDetects bearing temperature or distressAuxiliaryRotating machines
39Mechanical condition monitorDetects vibration or mechanical faultsAuxiliaryRotating machines
40Field relay (loss of excitation)Detects loss or abnormal level of field currentGeneratorSynchronous generators

ANSI Device Numbers 41–60: Protection and Switching Functions

No.Device namePlain-language meaningCategoryTypical application
41Field circuit breakerConnects or removes the field supplyGeneratorExcitation systems
42Running circuit breakerConnects a machine for normal runningMachine controlMotor circuits
43Manual transfer or selector deviceLets an operator select a mode or supplyControlLocal/remote selectors
44Unit sequence starting relayStarts the next unit in a sequenceControlMulti-unit plant
45Atmospheric condition monitorDetects smoke, fumes or other hazardous conditionsAuxiliarySubstations, plant rooms
46Reverse-phase or phase-balance current relayDetects unbalanced or reversed phase currentsProtectionMotors, generators
47Phase-sequence or voltage-balance relayDetects wrong phase order or unbalanced voltageProtectionMotors, incomers
48Incomplete-sequence relayDetects a start sequence that did not finishMachine controlMotor starters
49Machine or transformer thermal relayModels heating to protect against overloadProtectionMotors, transformers
50Instantaneous overcurrent relayTrips with no deliberate delay on high currentProtectionFeeders, motors, transformers
51AC time overcurrent relayTrips after a delay that shortens as current risesProtectionFeeders, motors, transformers
52AC circuit breakerMakes and breaks the AC circuit, including fault currentSwitchingAll AC switchgear
53Exciter or DC generator relayControls build-up of excitationGeneratorOlder excitation systems
54Turning-gear engaging deviceEngages turning gear on a shaftGeneratorTurbine-generators
55Power-factor relayOperates at a set power factorGeneratorSynchronous machines
56Field-application relayApplies field at the right momentGeneratorSynchronous motors
57Short-circuiting or grounding deviceShorts or earths a circuitSwitchingMaintenance earthing
58Rectification failure relayDetects a rectifier faultControlRectifiers, chargers
59Overvoltage relayOperates when voltage rises above its settingProtectionBuses, generators
60Voltage or current balance relayDetects imbalance between two circuitsProtectionCapacitor banks, VT supervision

ANSI Device Numbers 61–80: Monitoring and Protection Functions

No.Device namePlain-language meaningCategoryTypical application
61Density switch or sensorDetects insulating-gas densityAuxiliarySF6 switchgear
62Time-delay stopping or opening relayDelays a stop or open commandControlSequence control
63Pressure switch or detectorDetects abnormal pressure or gas surgeProtectionTransformers, GIS
64Ground protective relayDetects an earth faultProtectionGenerators, transformers
65GovernorControls prime-mover speed or outputGeneratorTurbines, engines
66Notching or jogging deviceLimits starts per hour or allows joggingMachine controlMotors
67AC directional overcurrent relayOvercurrent protection that looks at current directionProtectionParallel feeders, ring mains
68Blocking or power-swing blocking relayBlocks tripping during power swingsProtectionTransmission lines
69Permissive control deviceAllows a control action when conditions suitControlInterlocks
70RheostatVariable resistorAuxiliaryOlder control circuits
71Liquid or gas level switchDetects levelAuxiliaryTransformer oil, tanks
72DC circuit breakerMakes and breaks a DC circuitSwitchingBattery and DC systems
73Load-resistor contactorSwitches a load resistor in or outSwitchingDC and braking circuits
74Alarm relayGives an alarm outputAuxiliarySubstation alarms
75Position-changing mechanismMoves a device between positionsSwitchingDraw-out breaker drives
76DC overcurrent relayOvercurrent protection for DC circuitsProtectionDC systems
77Telemetering deviceSends measured values to a remote pointAuxiliarySCADA transducers
78Phase-angle or out-of-step relayDetects loss of synchronism between systemsProtectionGenerators, interconnections
79AC reclosing relayRecloses a breaker after a tripProtectionOverhead lines, feeders
80Liquid or gas flow relayDetects flow, or loss of flowAuxiliaryCooling systems

ANSI Device Numbers 81–94: Frequency, Differential and Auxiliary Functions

No.Device namePlain-language meaningCategoryTypical application
81Frequency relayOperates on over- or underfrequencyProtectionGrids, generators
82DC reclosing relayRecloses a DC circuit breakerProtectionDC systems
83Automatic selective control or transfer relaySwitches automatically between suppliesControlBus transfer schemes
84Operating mechanismStored-energy or motor drive for a switchSwitchingBreaker mechanisms
85Pilot communications relayUses a communication channel for protection signalsAuxiliaryTeleprotection
86Lockout relayLatches a trip and blocks closing until resetProtectionTransformers, buses, generators
87Differential protective relayTrips when current in and out of a zone does not balanceProtectionTransformers, buses, generators, lines
88Auxiliary motor or motor-generatorDrives auxiliary equipmentMachine controlPumps, fans, motor-generator sets
89Line switch (isolator)Isolates equipment; not normally used to break loadSwitchingSubstations
90Regulating deviceHolds a quantity such as voltage steadyControlTap changers, AVRs
91Voltage directional relayResponds to voltage directionProtectionSpecial schemes
92Voltage and power directional relayResponds to voltage and power direction togetherProtectionSpecial schemes
93Field-changing contactorChanges the field connection or valueGeneratorExcitation systems
94Tripping or trip-free relayStarts or assists a trip commandProtectionTrip circuits

Numbers 95 to 99: these are for specific applications that no other number covers. IEEE C37.2-2022 also adds modern acronyms alongside the numbers, so check the current standard for exact assignments before you quote them.

How the Device Numbers Are Grouped

We grouped numbers 1 to 94 by their main job. Protection is the largest group, which is why most day-to-day work revolves around a small set of numbers. This grouping is our own editorial one, so another author may place a few numbers differently.

94
numbers
  • Protection: 27 (29%)
  • Auxiliary and monitoring: 17 (18%)
  • Control and sequencing: 16 (17%)
  • Machine control: 13 (14%)
  • Generator and synchronising: 11 (12%)
  • Switching and isolating: 10 (11%)
ANSI device numbers 1–94 by main category (editorial grouping based on the tables above).

The switching group includes numbers 52 and 89. To see how breakers differ in practice, read our guide to types of circuit breakers or the comparison of MCB, MCCB and ACB.

ANSI Device Number Suffix Letters and Their Meanings

Letters added after a number narrow down what the function measures or protects. So 50 is “instantaneous overcurrent”, while 50N is the same function connected to neutral current. Suffix meanings depend on context and sometimes on the manufacturer, so always check the relay manual.

SuffixCommon meaningExampleNote
NNeutral or residual50N, 51NMeasures earth current through the neutral or residual connection
GGround, or generator51G, 87GGround in overcurrent codes; generator in differential codes
PPhase50P, 51PPhase-fault elements
TTransformer87TCan also mean time delay in other codes
BBus87BBusbar zone
LLine87LLine current differential
MMotor87MContext dependent
UUnder (or unit)81UUnderfrequency in 81U
OOver81OOverfrequency in 81O
BFBreaker failure50BFBackup if a breaker does not clear a fault
X, Y, ZAuxiliary devices27XUsually auxiliary relays tied to the main function
50 Instantaneous overcurrent 50NFed from the neutral or residual connection 50GFed from a ground (earth) CT 50BFBreaker-failure backup tripping
How suffix letters change the meaning of base number 50.

Difference Between 50N, 50G, 51N and 51G

All four are earth-fault overcurrent functions. The difference is where the current signal comes from. N elements usually use the residual current of the three phase CTs (or a neutral CT). G elements usually use a dedicated ground CT, such as a core-balance CT around the cable. The numbers still carry the timing: 50 trips without deliberate delay, 51 trips after a time delay. Some manufacturers use the letters the other way round, so confirm against the relay manual.

Combined ANSI Device Numbers

Numbers are often written together because one relay performs several functions. A slash separates them.

LabelMeaningWhere it is used
50/51Instantaneous and time-delayed phase overcurrent in one relayFeeders, motors, transformer incomers
50N/51NInstantaneous and time-delayed neutral overcurrentEarth-fault protection on solidly or resistance earthed systems
50G/51GInstantaneous and time-delayed ground overcurrentCable feeders with a core-balance CT
27/59Undervoltage and overvoltage functionsBuses, generators, grid interconnections
81O/81UOverfrequency and underfrequencyGenerators, load shedding
87T/50/51Transformer differential with overcurrent backupPower transformer protection panels
50BFBreaker-failure protectionSubstations with a bus-wide trip scheme
64REF / 87NRestricted earth-fault protectionTransformer windings (naming varies by vendor)

ANSI Device Numbers by Protected Equipment

This matrix shows which numbers are commonly found on each type of equipment. It is a guide to what you may see on drawings, not a design rule. The actual scheme depends on the equipment, system and utility requirements.

EquipmentCommonly used numbersNotes
Generator25, 27, 32, 40, 46, 49, 51V, 59, 64, 81, 87G32 detects reverse power; 40 detects loss of field; 87G is generator differential
Power transformer24, 49, 50/51, 51N, 63, 87T63 covers gas or sudden-pressure devices; 87T is the main fast protection
Motor37, 46, 47, 49, 50/51, 66, 87M46 and 47 catch unbalance and wrong sequence; 49 models heating
Line or feeder21, 50/51, 67, 79, 87L21 on longer lines; 79 on overhead lines where faults are often temporary
Busbar50BF, 86, 87B87B trips all connected breakers; 86 holds the trip
Capacitor bank27, 50/51, 59, 6060 is often used for unbalance; scheme varies with bank design

Many of these functions are fitted inside switchgear panels, where the relay, breaker (52) and isolator (89) sit together in one lineup.

ANSI Device Numbers vs IEC 61850 Logical Nodes

IEC 61850 does not replace ANSI numbers with one symbol each. It describes functions as logical nodes, which are software building blocks that digital substation devices use to share data. Each logical node has a four-letter name, such as PDIS for distance protection. ANSI numbers describe what the function is. Logical nodes describe how it is modelled and communicated.

ANSI functionIEC 61850 logical nodeFunction
21PDISDistance protection
50 / 51 / 67PTOC (some vendors use PIOC for 50, PDEF for earth-fault direction)Overcurrent protection
27PTUVUndervoltage protection
59PTOVOvervoltage protection
81OPTOFOverfrequency protection
87PDIFDifferential protection
50BFRBRFBreaker-failure protection
79RRECAuto-reclosing
52XCBRCircuit breaker
89XSWIIsolator or switch

These are representative examples, not a universal one-to-one conversion. Mappings differ between manufacturers and between relay models, so use the relay’s own IEC 61850 conformance document when you need exact names. ANSI numbers and IEC 61850 normally sit side by side in modern relays: the number appears on drawings and settings, and the logical node is used in the communication model.

ANSI Numbers vs IEC Graphical Symbols

IEC graphical symbols (IEC 60617) draw a device on a diagram, for example a relay coil or a breaker. An ANSI number says what the device does. Drawings can use both together, such as an IEC symbol for a relay labelled “51”. European and IEC-led projects tend to lean on symbols and logical nodes; North American, Indian and many international projects use ANSI numbers widely.

How to Read ANSI Device Numbers on a Single-Line Diagram

A single-line diagram shows the main equipment as one line. Device numbers appear in small circles or boxes next to the breaker, transformer or feeder they act on. The number tells you which protection function is present, and the suffix tells you what it watches. Primary protection (such as 87T) acts fastest on its own zone, while backup protection (such as 51 or 50BF) acts later or covers a neighbouring zone.

Incoming line 52 breaker Transformer 87T · 63 · 49 Busbar: 87B · 86 lockout 52 breaker Feeder: 50/51 · 50N/51N · 79 50BF on each breaker
Illustrative example only, not a design recommendation.

Worked Examples of Relay Labels

LabelHow to read it
50/51Base functions 50 and 51: instantaneous plus time-delayed phase overcurrent.
50N/51NThe same pair, with suffix N: both use neutral or residual earth current.
87TBase 87 (differential) with suffix T: transformer differential protection.
87T/50/51NTransformer differential, plus phase instantaneous and time-delayed overcurrent, plus neutral time-delayed overcurrent, usually all in one IED.

To decode any label, split it at the slashes, read each base number from the list, then apply the suffix. Our guide on fuse vs circuit breaker is a useful companion if you want to understand what happens after the relay sends its trip signal.

Common Misconceptions About ANSI Device Numbers

MisconceptionReality
They are only used in the United States.They are used worldwide, including India and the UK, alongside IEC practice.
Each number is a separate physical relay.One modern IED can host many numbered functions.
Every number from 1 to 99 has a defined function.The standard assigns 95 numbers; 95–99 are for specific applications.
A suffix letter always means the same thing.G, T, B and others change meaning with context.
ANSI numbers and IEC 61850 logical nodes are identical.They describe different things and do not map one-to-one.

Frequently Asked Questions About ANSI Device Numbers

What are ANSI device numbers?

They are standard numeric codes from IEEE C37.2 that identify the function of a protection, control or switching device in a power system.

What is the ANSI device number for an instantaneous overcurrent relay?

It is 50.

What is the difference between ANSI 50 and 51?

Device 50 trips with no deliberate delay when current passes its setting. Device 51 trips after a time delay that gets shorter as current rises.

What does ANSI 87 mean?

It means differential protection. The relay compares current entering and leaving a protected zone and trips if they do not balance.

What is an ANSI 86 lockout relay?

It is a latching relay that trips the connected breakers and blocks reclosing until it is reset by hand or remotely.

Why is a circuit breaker called device 52?

Because IEEE C37.2 assigns number 52 to the AC circuit breaker. The number is a convention, not a calculation.

What does the N suffix mean?

It usually means the function uses neutral or residual current, as in 50N and 51N.

What does G mean in ANSI relay numbers?

It usually means ground in overcurrent codes such as 51G, and generator in differential codes such as 87G.

What is ANSI 79 used for?

It is automatic reclosing. It closes a breaker again after a trip, which helps on overhead lines where many faults clear themselves.

What does ANSI 81 mean?

It is a frequency relay. 81O acts on overfrequency and 81U on underfrequency.

What is the IEC equivalent of ANSI device numbers?

There is no exact one-to-one equivalent. IEC 61850 uses logical nodes such as PTOC, PDIS and PDIF, and IEC 60617 provides graphical symbols.

Are ANSI device numbers used in India?

Yes. They are widely used on Indian utility, EPC and industrial drawings and relay settings, often alongside IEC practice.

How many ANSI device numbers are there?

IEEE C37.2-2022 assigns 95 device numbers and 22 acronyms.

Conclusion

ANSI device numbers give engineers a shared shorthand for what each device does. Learn the core set first (21, 27, 50, 51, 52, 59, 81, 86 and 87), then add suffixes and combined labels as you meet them on drawings. Bookmark this page as a quick reference, and see our overview of protection relays for the hardware behind the numbers.

Disclaimer: this is a general reference. Relay selection, settings, coordination, testing and commissioning must be carried out by qualified protection engineers in line with IEEE C37.2-2022, local regulations, utility requirements and project design documents.

Sources: IEEE Standards Association: C37.2-2022; Wikipedia: ANSI device numbers; IEC 61850-7-4 preview.

About the author