Standard Circuit Breaker Sizes: NEC vs IEC Ratings

By editor Updated 6 min read
Four circuit breakers on a DIN rail comparing NEC ratings of 15, 20, 30 and 60 amps with IEC ratings of 16, 20, 32 and 63 amps

Standard NEC circuit breaker sizes run from 15 A through 6000 A, including 15, 20, 30, 40, 50, 60, 100, 200, 400 and 800 A. A common IEC miniature breaker series is 6, 10, 13, 16, 20, 25, 32, 40, 50 and 63 A. Neither list sets one minimum size for every job. The right breaker must be large enough for the load and small enough to protect the conductor.

Check your edition: A recent EC&M code article says Table 240.6(A) now covers 38 ratings from 10 A to 6000 A, while the older published list below starts at 15 A and has 37 values. Use the table in the NEC edition adopted where you work.

NEC Standard Circuit Breaker Sizes

RangeStandard ratings (A)
15-60 A15, 20, 25, 30, 35, 40, 45, 50, 60
70-225 A70, 80, 90, 100, 110, 125, 150, 175, 200, 225
250-800 A250, 300, 350, 400, 450, 500, 600, 700, 800
1000-6000 A1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000
NEC 240.6 ratings for fuses and inverse time breakers, as published by IAEI Magazine (2005 NEC). Confirm against your edition.

The NEC also lists additional standard ratings for fuses of 1, 3, 6, 10 and 601 A. Fuses and inverse time breakers with non-standard ratings are permitted, so you may see a real device that is not on this list.

For an adjustable-trip breaker, the rating is its maximum long-time pickup setting. If access to the adjustment is restricted as described in 240.6(C), the rating can be the adjusted setting instead.

IEC Standard MCB Sizes

IEC miniature circuit breakers (MCBs) are commonly supplied in the series below. ABB’s comparison guide shows these values for B and C characteristics, and its data covers ratings up to 63 A.

CurveStandardABB rangeInstantaneous trip rangeTypical use
BIEC/EN 60898-16-63 A3-5 × InCable protection
CIEC/EN 60898-10.5-63 A5-10 × InCable protection
DIEC/EN 60898-10.5-63 A10-20 × InCable protection, high inrush
KIEC/EN 60947-20.5-63 A10-14 × InMotors and transformers
ZIEC/EN 60947-20.5-63 A2-3 × InControl and semiconductor circuits
From ABB’s Comparison of Tripping Characteristics for MCBs. Ranges are for that ABB product data.

For larger currents, you move from MCBs to moulded case and air circuit breakers. See our guide to MCB vs MCCB vs ACB for where each one fits.

NEC vs IEC Sizes Compared

NEC and IEC breaker ratingsA scale shows NEC ratings of 15 to 60 amps above the line and IEC miniature breaker ratings of 6 to 63 amps below it. Only 20, 25, 40 and 50 amps appear in both.NEC and IEC ratings up to 63 ANECIEC1520253035404550606101316202532405063IndustrialBasicsindustrialbasics.com
Figure 1: The two series share 20, 25, 40 and 50 A. The other values differ.
TopicNECIEC
Typical small ratings15, 20, 30, 40, 50, 60 A6, 10, 16, 20, 32, 40, 50, 63 A
Rating listTable 240.6(A)Product standard and maker’s range
Sizing relationshipArticle 240 conductor protectionIb ≤ In ≤ Iz and I2 ≤ 1.45 Iz
Trip curvesSet by product type and makerB, C and D on IEC 60898-1 MCBs
A summary. Each system has more detail than can fit in a table.
Important: Do not treat a 16 A IEC breaker as a drop-in for a 15 A NEC breaker, or the reverse. Install only devices certified for your market and approved for that panel. Matching numbers do not mean matching standards.

How Minimum Breaker Size Is Decided

Under IEC

IEC 60364-4-43, as summarized by ABB, gives a simple window for overload protection:

Ib ≤ In ≤ Iz and I2 ≤ 1.45 × Iz
Breaker sizing windowThe breaker rating must be at least the design current of 28 amps and no more than the cable capacity of 36 amps, so a 32 amp breaker fits.The breaker must fit between the load and the cableLoad currentIb = 28 ABreaker ratingIn = 32 ACable capacityIz = 36 A≤≤Too small: nuisance trips. Too large: the cable is not protected.IndustrialBasicsindustrialbasics.com
Figure 2: The IEC 60364-4-43 sizing relationship, as given by ABB.

Ib is the design current, In the breaker rating, Iz the cable’s current-carrying capacity and I2 the current that ensures operation within the conventional time. For B, C and D MCBs, ABB gives I2 as 1.45 × In.

Under the NEC

The conductor sets the upper limit. At 800 A or less, NEC 240.4(B) can allow the next higher standard rating when the conductor’s ampacity does not match a standard size and the conditions are met. Above 800 A, conductor ampacity must equal or exceed the device rating.

NEC next size up decisionAt 800 amps or less, the next standard size may be allowed if the conditions are met. Above 800 amps, conductor ampacity must equal or exceed the breaker rating.Can you round up under NEC 240.4(B)?Is the breakerrated 800 A or less?Yes: next standard size may be allowedIf all 240.4(B) conditions are met and 240.4(D) is not exceededNo: over 800 AConductor ampacity must equal or exceed the breaker ratingIndustrialBasicsindustrialbasics.com
Figure 3: A simplified view. Read the full rule in your adopted code edition.
ConductorMaximum overcurrent protection
14 AWG copper15 A
12 AWG copper20 A
10 AWG copper30 A
12 AWG aluminum or copper-clad aluminum15 A
10 AWG aluminum or copper-clad aluminum25 A
NEC 240.4(D), as published by IAEI Magazine (2005 NEC). Specific exceptions apply in 240.4(E) through (G).

Load rules set the lower limit, and they differ by circuit type. Branch circuits and feeders are covered in Articles 210 and 215, while motor circuits have their own rules. Our guides to MCA and MOP and AWG wire ampacity can help you take the next step.

Worked Examples

NEC: rounding up

A conductor has a corrected ampacity of 115 A. There is no 115 A standard rating, and the next standard size above it is 125 A. Because this is below 800 A, 240.4(B) may allow the 125 A breaker if all its conditions are met. If the conductor were limited by 240.4(D), that limit would still apply.

IEC: checking the window

  1. Design current: Ib = 28 A, so the next series value is 32 A.
  2. Cable capacity: Iz = 36 A, so 28 ≤ 32 ≤ 36 passes.
  3. Overload check: I2 = 1.45 × 32 = 46.4 A, which is below 1.45 × 36 = 52.2 A.
  4. Temperature check: ABB says operating current falls about 6% per 10 °C above the 30 °C reference. At 40 °C, 32 × 0.94 ≈ 30.1 A, still above 28 A.
Reader tip: Grouping matters too. ABB gives a factor of 0.8 for 4 or 5 adjacent, heavily loaded MCBs. Applied to this example, 30.1 × 0.8 ≈ 24 A, which is below the 28 A load, so the layout or the design would need to change.

Breaker rating is only part of the selection. You also need the correct interrupting rating, curve and coordination with other devices. See types of circuit breakers for the wider picture.

Before choosing a breaker for a service or feeder, work out the load with the NEC 220 demand factor method.

Frequently Asked Questions

What are the standard circuit breaker sizes in the NEC?

The commonly published list runs 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 A. Check Table 240.6(A) in your adopted edition.

What is the minimum circuit breaker size?

There is no single minimum that fits every circuit. The breaker must suit the load and protect the conductor, and the smallest available rating depends on the code edition, product and market.

Is a 16 A IEC breaker the same as a 15 A NEC breaker?

No. They belong to different rating series and product standards. Use a device that is certified for your market and installation.

What are standard IEC MCB sizes?

A common series is 6, 10, 13, 16, 20, 25, 32, 40, 50 and 63 A. Manufacturers also offer other ratings.

Can I use the next size up breaker?

Under NEC 240.4(B), often yes at 800 A or less, if all conditions are met. It cannot be used to exceed the small conductor limits or for tap conductors.

What size breaker does 12 AWG copper need?

NEC 240.4(D) generally limits 12 AWG copper to 20 A, unless a specific exception applies, such as certain motor circuits.

Are non-standard breaker ratings allowed?

Yes. The NEC permits fuses and inverse time breakers with non-standard ampere ratings.

How is an adjustable breaker rated?

Its rating is normally its maximum long-time pickup setting. With restricted access to the adjustment under 240.6(C), the rating can be the adjusted setting.

Sources and Further Reading

About the author

editor

Leave a Comment