Class 1 Div 1 vs Div 2: Hazardous Locations, Groups and T-Codes

By editor 9 min read
Diagram comparing Class I Division 1 and Division 2 hazardous areas around a flammable liquid tank

Class I, Division 1 (C1D1) is a location where ignitable concentrations of flammable gases or vapors exist, or may exist, under normal operating conditions. Class I, Division 2 (C1D2) is a location where they exist only under abnormal conditions, such as a leak, rupture or equipment failure. Division 1 is the more hazardous and requires explosion-proof, intrinsically safe or purged and pressurized equipment; Division 2 also permits nonincendive circuits, hermetically sealed contacts and, in many cases, general-purpose equipment. Equipment rated for Division 1 can be used in Division 2 of the same class, group and temperature class, but not the reverse.

Div 1
hazard under normal conditions
Div 2
hazard only if something goes wrong
Groups A–D
Class I gases
T1–T6
surface temperature codes
Safety note: Area classification, equipment selection and installation in hazardous locations are life-safety work. Use this article to understand the terms; rely on a qualified area classification study, the NEC edition your jurisdiction has adopted, listed equipment and the authority having jurisdiction for real installations.

Class I Division 1 vs Division 2 at a Glance

Class I, Division 1Class I, Division 2
When the hazard existsUnder normal operating conditions, all or some of the timeOnly under abnormal conditions (leaks, failures)
Zone equivalentZone 0 + Zone 1Zone 2
ExampleVapor space of a vented tank and the area close to its ventSurroundings of closed process equipment that could leak
Protection methodsExplosion-proof, intrinsically safe, purged/pressurizedAll Div 1 methods plus nonincendive, hermetically sealed, and others
Boxes and fittingsIdentified for Class I, Division 1Explosion-proof where required; relief provisions in Art. 501
Equipment interchangeCan be used in Div 2Cannot be used in Div 1
From EC&M’s NEC class and division basics and Article 501 summary, and the Wikipedia hazardous areas article.
Comparison of Class I Division 1 and Division 2 locationsDivision 1: ignitable gas or vapor is present under normal operating conditions, requiring explosion-proof, intrinsically safe or purged equipment. Division 2: it is present only under abnormal conditions such as leaks, and nonincendive circuits, hermetically sealed contacts and some general-purpose equipment are also permitted.Division 1 vs Division 2 in one pictureClass I, Division 1Ignitable gas or vapor presentunder NORMAL operating conditionsall or part of the timeEquipment: explosion-proof,intrinsically safe, purged/pressurizedBoxes and fittings identified for Div 1Class I, Division 2Ignitable gas or vapor presentonly under ABNORMAL conditions(leaks, failures, upsets)Also allowed: nonincendive circuits,hermetically sealed contacts,general-purpose enclosures in many casesDiv 1 equipment may be used in Div 2 of the same class, group and temperature class, not the other way round.IndustrialBasicsindustrialbasics.com
Figure 2: Definitions from EC&M and Wikipedia; Division 2 relief provisions per EC&M’s NEC Article 501 summary. Always check the NEC edition adopted in your jurisdiction.

Classes, Divisions and Groups Explained

EC&M summarizes NEC Article 500 like this: a location is Class I if flammable or combustible gases or vapors may be present in ignitable quantities, Class II if combustible dust is the threat, and Class III if ignitable fibers or flyings are. In Classes I and II, it is Division 1 if the threat is present during ordinary conditions and Division 2 if it is present only during abnormal conditions. Class I is the most stringent class and Division 1 is more stringent than Division 2.

ClassGroupRepresentative materials
Class I (gases, vapors)AAcetylene
Class IBHydrogen
Class ICEthylene
Class IDPropane, methane
Class II (dusts)EMetal dusts such as magnesium (Division 1 only)
Class IIFCarbonaceous dusts such as carbon and charcoal
Class IIGNon-conductive dusts such as flour, grain, wood and plastic
Class III (fibers, flyings)—Cotton lint, flax, rayon
NEC groups and representative materials from the Wikipedia hazardous areas article.

Within Class I, the group describes how easily the material ignites and how violent the explosion is: Group A (acetylene) is the most severe and Group D (propane, methane) the least. Equipment must be listed for the specific group, and Wikipedia notes that the zone system’s IIC, IIB and IIA groups map onto NEC Groups A/B, C and D.

Division 1 vs Zone 0 and Zone 1

Illustrative Division 1 and Division 2 areas around a flammable liquid tankAn illustrative vented tank of flammable liquid. The vapor space inside is the most hazardous (Zone 0, part of Division 1), the area close to the vent is Division 1, a wider envelope is Division 2 where vapor appears only during leaks or upsets, and beyond that the area is unclassified.How classified areas typically surround a vented flammable-liquid tank (illustrative)gradeflammable liquidventvapor space:Zone 0 → Div 1Division 1near ventDivision 2(only if a leakor upset occurs)Unclassifiedbeyond theboundaryIndustrialBasicsindustrialbasics.com
Figure 1: For illustration only. Actual extents come from the area classification study, NFPA 497 and the NEC, not from this sketch. Zone 0 example from Wikipedia.

Wikipedia explains that a Class I, Division 1 area “encompasses the combination of Zone 0 and Zone 1”. Zone 0 is where ignitable concentrations are present continuously or for long periods, such as the vapor space above the liquid in a tank, with a guide of more than 1,000 hours a year. Zone 1 is where they are likely under normal operation (about 10 to 1,000 hours a year). Division 2 equals Zone 2, where they should be present for less than about 10 hours a year. The NEC allows either system: Article 500 for divisions and Article 505 for zones.

Temperature Codes (T-codes)

T-codeMax surface temp (°C)T-codeMax surface temp (°C)
T1450T3A180
T2300T3B165
T2A280T3C160
T2B260T4135
T2C230T4A120
T2D215T5100
T3200T685
US temperature classes from the Wikipedia hazardous areas article. IEC uses only T1 to T6.

A T-code tells you the hottest any surface of the equipment can get. Wikipedia’s example: equipment marked T3 will not rise above 200 °C. That temperature must stay below the autoignition temperature of every flammable material in the area, which you find on its safety data sheet. Hot process surfaces matter too; Wikipedia notes a high-pressure steam pipe can exceed the autoignition temperature of some fuel-air mixtures.

Temperature Code Check
IndustrialBasics checker, for understanding labels only. The T-code is the maximum surface temperature the equipment can reach; it must be below the autoignition temperature of the materials present. Class, division and group must also match, and the installation must comply with the NEC and the area classification. This tool does not approve equipment.

Protection Methods

MethodHow it prevents ignitionTypical use
Explosion-proof (flameproof)Contains an internal explosion and cools escaping gases through flame paths so the outside atmosphere is not ignitedMotors, lighting, junction boxes, control stations
Intrinsically safeLimits electrical and thermal energy below what can ignite the atmosphere, even under faultInstrumentation, sensors, 4-20 mA loops
Purged / pressurizedKeeps clean air or inert gas at positive pressure inside the enclosureAnalyzers, control panels, motors
Nonincendive (Division 2)Circuits that cannot ignite the atmosphere in normal operationInstrument and control wiring in Div 2
Hermetically sealed / encapsulatedKeeps the atmosphere away from arcing contactsRelays, switches
Protection methods from the Wikipedia hazardous areas article and EC&M’s Article 501 summary.

EC&M stresses what “explosion-proof” means: the goal is to contain combustion inside the electrical system so it does not spread, not to survive an explosion that starts outside. That is why Article 501 has extensive sealing and drainage requirements for Class I conduits, more than three pages compared with under a quarter page for Class II. Wikipedia lists NEMA Type 7 (indoor) and Type 9 (dust) enclosures as certified for Class I Groups A–D and Class II Groups E–G respectively.

Wiring Differences Between Division 1 and Division 2

  • Wiring methods: EC&M notes the NEC permits specific conduit types in Class I, and that tubing is not among the permitted wiring methods.
  • Boxes and fittings: in Division 1 they must be identified for Class I, Division 1; in Division 2 the requirements are relaxed (EC&M).
  • Seals: conduit seals limit the passage of gases and flames between areas and at the Division 1/Division 2 boundary.
  • Division 2 relief: nonincendive circuits and hermetically sealed contacts are allowed, which is why many Division 2 instrument installations look much like ordinary ones.

For the wider picture of electrical risk in plants, see electrical hazards in industry; for instrument loops that are often made intrinsically safe, see our 4-20 mA guide.

Reading a Hazardous Location Label

Wikipedia notes that a North American label always lists the class and division and may list the group and temperature code, next to the mark of the listing agency. A marking such as Class I, Division 1, Groups C and D, T4 means: suitable for gases and vapors, in areas hazardous under normal conditions, for ethylene- and propane-type atmospheres, with surfaces that never exceed 135 °C.

Frequently Asked Questions

What is the difference between Class 1 Div 1 and Class 1 Div 2?

In a Class I, Division 1 location, ignitable concentrations of flammable gas or vapor can exist under normal operating conditions. In Division 2 they exist only under abnormal conditions, such as a leak or equipment failure. Division 1 is the more hazardous and has stricter equipment rules.

What does C1D1 mean?

Class I, Division 1: a location where flammable gases or vapors are, or may be, present in ignitable concentrations during normal operation. C1D2 is Class I, Division 2.

Can Class 1 Div 1 equipment be used in Div 2?

Yes, if it matches the class, group and temperature class. Equipment approved for Division 1 may be used in Division 2, but Division 2 equipment cannot be used in Division 1.

What are Class II and Class III locations?

Class II covers combustible dust (Groups E, F, G) and Class III covers ignitable fibers and flyings, such as cotton lint. Each also has Division 1 and Division 2.

What are Groups A, B, C and D?

Gas groups in Class I based on how easily the material ignites and how violent the explosion is: A is acetylene, B hydrogen, C ethylene, D propane and methane. Equipment must be listed for the group present.

What is a temperature code (T-code)?

The maximum surface temperature the equipment can reach, from T1 (450 °C) down to T6 (85 °C). It must be below the autoignition temperature of the gas or vapor present.

Is a Class 1 Div 2 enclosure explosion-proof?

Not necessarily. Division 2 allows several protection methods, including nonincendive circuits and hermetically sealed contacts; EC&M notes that Division 2 boxes and fittings need only be explosion-proof where the rules call for it, while Division 1 boxes must be identified for Division 1.

What is the difference between explosion-proof and intrinsically safe?

Explosion-proof equipment contains any internal explosion and stops it igniting the surrounding atmosphere. Intrinsically safe equipment limits electrical and thermal energy so it cannot cause ignition in the first place.

How do Divisions relate to Zones?

Class I, Division 1 corresponds to Zones 0 and 1; Division 2 corresponds to Zone 2. Zone 0 is where gas is present continuously or for long periods, such as the vapor space of a tank.

Who decides whether an area is Division 1 or 2?

An area classification study by qualified people from operations, process, safety and electrical disciplines, documented on area classification drawings. The authority having jurisdiction enforces the NEC requirements for the result.

Sources and Further Reading

About the author

editor

Leave a Comment