A 4-20 mA flow control valve changes its opening in proportion to a current signal, usually with 4 mA at 0%, 12 mA at 50% and 20 mA at 100% travel. The controller connects to the valve’s positioner or modulating actuator through a two-wire loop. To commission one, wire the polarity correctly, confirm the loop can drive the device’s load, calibrate zero and span, and verify what the valve does when the signal is lost.
| Signal | Fail closed position | Fail open position |
|---|---|---|
| 4 mA | 0% | 100% |
| 8 mA | 25% | 75% |
| 12 mA | 50% | 50% |
| 16 mA | 75% | 25% |
| 20 mA | 100% | 0% |
4-20 mA Valve Signal Calculator
Enter the loop current, valve action and total loop resistance to see the commanded position and loop voltage.
How a 4-20 mA Valve Works
The controller, often a PLC or DCS, sends a current that represents the desired valve position. A positioner or modulating actuator compares that command with the measured valve position and moves the valve until they match. In a flow loop, the controller’s output usually comes from a PID loop acting on a flow measurement.
For example, 10 mA commands (10 − 4) ÷ 16 × 100 = 37.5%. To go the other way, use mA = 4 + (16 × position ÷ 100).
Starting at 4 mA is known as a live zero. A healthy signal does not fall to 0 mA, so a broken wire can be detected. Indelac’s modulating board, for example, offers its loss-of-signal functions in the 1-5 V and 4-20 mA ranges.
How to Wire a 4-20 mA Valve
- Isolate the control circuit and confirm the device’s signal type.
- Connect the controller output to the positioner’s (+) and (−) loop terminals.
- Use the cable and shield arrangement in the manual.
- If the valve has position feedback, wire it as a separate loop. AVID’s analog transmitter, for example, needs an external 24 V DC supply.
- Check polarity, then apply a known signal from a loop calibrator before connecting to live control.
For help choosing analog channels, see how to select a PLC. If the valve uses air, our guide to the pneumatic relay explains how a small signal controls a larger air flow.
Check the loop can drive the load
Every device in the loop drops voltage. At 20 mA, the voltage needed is the current multiplied by total loop resistance.
Valmet’s ND9000H positioner has a load voltage of up to 9.7 V at 20 mA, equivalent to 485 Ω. With an assumed 20 Ω of cable resistance, the total is 505 Ω, so the output must be able to drive 10.1 V at 20 mA. Compare that figure with the rated load of your analog output.
Calibrating Zero and Span
- Make the process safe and get any required approval.
- Connect a calibrated mA source.
- Check air supply or actuator power, if used.
- Set the correct action, such as fail closed or fail open.
- Run auto-calibration, or set zero and span as described in the manual.
- Check the valve at 4, 8, 12, 16 and 20 mA, moving in both directions.
- Confirm the position feedback matches, then record the results.
| Product | Calibration detail |
|---|---|
| AVID SmartCal | Automatic calibration requires a 12 mA input and also tunes PID gains |
| Westlock K20 | Factory calibrated with 4 mA at the fail position and 20 mA at the span position |
| Indelac modulating board | Non-interactive zero and span adjustments |
Technical Specifications to Check
Specifications vary by product, so compare the data for your exact valve. These real examples show how much they can differ:
| Specification | Example | Why it matters |
|---|---|---|
| Input load | Azbil ACTIVAL: 100 Ω; Valmet ND9000H: up to 9.7 V at 20 mA | Sets the output drive needed |
| Minimum operating signal | Valmet ND9000H: 3.7 mA | Loop-powered device must stay alive |
| Maximum loop voltage | Valmet ND9000H: 30 V DC | Protects the electronics |
| Deadband | AVID SmartCal: nominal ±0.3% of full scale | Affects small movements |
| Position feedback | Azbil ACTIVAL: 4-20 mA DC output | Confirms actual position |
| Rangeability | Azbil ACTIVAL: 100:1 | Usable control range |
| Valve capacity | Azbil DN25 water valve: Cv 10 or 16 | Must suit the required flow |
For water service, also check body and seal materials, pressure and temperature ratings, leakage class, close-off pressure and the enclosure rating for the site.
Fail Position and Signal Loss
Do not assume what a valve will do on a fault. Signal loss, power loss and air loss can each cause a different response. Indelac’s board can be configured to stop in its last position, fail open or fail closed when the command signal is lost. On Azbil’s ACTIVAL, a selector switch makes the valve close or open if no control signal is input.
Choose the safe state from the process hazard, then test it during commissioning by actually removing the signal under controlled conditions.
Troubleshooting
| Symptom | Possible cause | Check |
|---|---|---|
| 0 mA at the valve | Open loop or no output | Wiring, fuse and controller output |
| Valve works backward | Wrong action setting | Direct/reverse or fail mode |
| Cannot reach 20 mA | Too much loop resistance | Output rating and total load |
| Valve hunts | Tuning, deadband or friction | Positioner and PID settings |
| Display and feedback disagree | Feedback not calibrated | Feedback transmitter |
| Noisy signal | Poor shielding or routing | Shield and separation from power cables |
If the fault could be in the measurement rather than the valve, review our guide to industrial sensors. For control architecture, see PLC vs DCS vs SCADA.
Choosing the valve itself starts with its flow capacity; our guide to the valve flow coefficient Cv covers the Cv formula for liquids and gases, Kv conversion and a sizing calculator.
Frequently Asked Questions
What is a 4-20 mA flow control valve?
It is a modulating valve whose position follows a 4 to 20 mA control signal. On a typical fail closed setup, 4 mA is closed, 12 mA is half open and 20 mA is fully open.
Why does the signal start at 4 mA instead of 0?
A live zero makes a broken loop detectable because a healthy signal never falls to 0 mA. Some actuator boards use this to trigger a loss-of-signal response.
What happens if the 4-20 mA signal is lost?
It depends on the device. Indelac’s modulating board can be set to stay in its last position, fail open or fail closed.
What is the input impedance of a 4-20 mA valve?
It varies by product. Azbil’s ACTIVAL lists 100 Ω, while Valmet’s ND9000H loads the loop by up to 9.7 V at 20 mA, equivalent to 485 Ω.
How do you calibrate a 4-20 mA valve positioner?
Isolate the process as required, connect a calibrated mA source, run the auto-calibration or set zero and span, then check the position at several signal points.
Is 12 mA always 50 percent open?
For a standard linear signal range, 12 mA commands 50 percent travel. Actual flow may not be 50 percent because valve characteristics and pressure drop affect flow.
Can a PLC drive a loop-powered positioner directly?
Yes, if the analog output can supply the current through the total loop resistance. Compare the positioner load voltage and wiring with the output’s rated load.
What is the difference between fail closed and fail open?
They describe the valve’s safe position. Fail closed goes closed and fail open goes open on the defined failure, so choose based on the process hazard.
Sources and Further Reading
- AVID SmartCal Valve Positioner IOM: wiring, calibration, action and deadband.
- Westlock K20 Smart Positioner Operating Manual: calibration and fail mode.
- Azbil ACTIVAL Motorized Two-Way Valve Specifications: water valve input, feedback, Cv and rangeability.
- Indelac Modulating Actuator IOM: loss-of-signal options and calibration.
- Valmet ND9000 Intelligent Valve Controller Manual: load voltage and minimum signal.