To select a PLC, first define your I/O: list every sensor and actuator, classify each signal, and add spare capacity. Then match the input and output types, check the power budget and choose the communication interfaces you need. Defining I/O first matters because the point count and signal types decide which controller family, modules and power supply will fit.
| Step | What to define | Result |
|---|---|---|
| 1. I/O | Digital, analog and specialty points | Channel count |
| 2. Signals | Voltage, sinking or sourcing, signal range | Module types |
| 3. Margin | Spare points for future changes | Final module count |
| 4. Power | Supply and backplane current | Power supply size |
| 5. Interfaces | HMI, drives, remote I/O, networks | Ports and protocols |
Define I/O: Count Every Input and Output
I/O means input and output. Inputs bring information into the PLC, and outputs let it act on the machine. If you need to define IO for a project, start with the electrical drawings or walk the machine and record each device.
| Type | Signal | Typical devices |
|---|---|---|
| Digital input | On or off | Push buttons, limit switches, proximity sensors |
| Digital output | On or off | Motor starters, solenoids, panel lamps |
| Analog input | Continuous value | Temperature, distance, level or pressure measurement |
| Analog output | Continuous value | Speed reference or signal to another controller |
| Specialty | Function-specific | High-speed counting or positioning |
For more on the devices themselves, see our guide to types of industrial sensors. If the term PLC is new to you, start with what a PLC is and how it works.
Add spare capacity
Projects change, so do not size the PLC to the exact count. DigiKey’s applications guidance suggests adding 25% to your initial I/O estimate. Use your own specification if it sets a different margin.
Match the Input and Output Types
A correct point count is not enough. Each module must also match the voltage and electrical behavior of the device connected to it.
Sinking and sourcing
A PNP transistor output sources current, while an NPN output sinks it. A sourcing device needs a sinking input, and a sinking device needs a sourcing input. Some modules accept both. Rockwell’s 1769-IQ16, for example, is a 24 V DC sinking or sourcing input module. Confirm the connection from the wiring diagram for your exact module.
Output types
| Output | Strength | Limit | Good for |
|---|---|---|---|
| Transistor (PNP or NPN) | Faster switching | Lower current, specific voltage | Small DC loads and fast signals |
| Relay | Isolated contacts, higher current, mixed voltages | Slower than transistor | Contactors and mixed loads |
| PWM or pulse | Variable or fixed pulse output | Needs a compatible device | Pulse-driven equipment |
| Analog | Continuous voltage or current | Usually a signal, not power | Drive speed reference |
Larger loads are normally switched through a contactor. Our comparison of contactors and relays explains which fits a given load. For drive speed signals, see potentiometer speed control.
Analog signal ranges
DigiKey lists typical analog output ranges as 1 to 5 V, 0 to 10 V, 0 to 20 mA and 4 to 20 mA. Match the range at both ends of the signal, and check the module’s accuracy against what the process needs.
Check the Power Budget
Some PLCs include a power supply and others need a separate module. Check the allowed supply voltage range, because voltage outside that range can damage the device. On a modular system, also add up the backplane current drawn by the modules.
Rockwell’s Compact I/O guide shows how this works. Its 1769-PA2 supply provides 2 A at 5 V DC and 0.8 A at 24 V DC, and the 5 V capacity is split as 1 A to each side of the supply.
| Supply | Input | 5 V DC bus | 24 V DC bus |
|---|---|---|---|
| 1769-PA2 | 120 or 240 V AC | 2 A | 0.8 A |
| 1769-PB2 | 24 V DC | 2 A | 0.8 A |
| 1769-PA4 | 120 or 240 V AC | 4 A | 2 A |
| 1769-PB4 | 24 V DC | 4 A | 2 A |
Worked Example: Sizing the I/O and Power
A small machine has 34 digital inputs and 20 digital outputs, all at 24 V DC. We will use 16-point Rockwell 1769 modules as the example.
| Item | Inputs | Outputs |
|---|---|---|
| Counted points | 34 | 20 |
| With 25% margin | 42.5, round up to 43 | 25 |
| 16-point modules | 3 × 1769-IQ16 | 2 × 1769-OB16 |
| Installed points | 48 | 32 |
| 5 V current per module | 115 mA | 200 mA |
| 5 V current total | 345 mA | 400 mA |
With all five modules on one side of a 1769-PA2, the 745 mA module load is within the 1 A limit for that side. The check is not finished yet. You must also include the controller and any other modules, and check the 24 V bus and the power supply distance rating. If demand is at or near the limit, add another I/O bank or a larger supply.
Choose the Communication Interfaces
List everything the PLC must talk to: the programming device, HMI, drives, remote I/O and plant systems. Check whether each port is built in or requires a separate module.
| Interface | Max devices | Max cable length |
|---|---|---|
| RS-232C | 1 | 15 m (50 ft) |
| RS-422 | 10 | 1,219 m (4,000 ft) |
| RS-485 | 32 | 1,219 m (4,000 ft) |
| DeviceNet | 63 | 500 m (1,640 ft) |
| EtherNet/IP | See vendor data | 100 m (328 ft) |
| EtherCAT | See vendor data | 100 m (328 ft) |
If you are wiring a serial link, our DB9 pinout guide covers RS-232 connections. To decide whether a PLC is the right platform at all, see PLC vs DCS vs SCADA. Programming language support is covered in our guide to IEC 61131-3.
Final PLC Selection Checklist
- Every device is listed and classified.
- Spare capacity has been added.
- Input and output voltage types match the field devices.
- Sinking and sourcing connections have been checked.
- Analog ranges match at both ends.
- Supply voltage and backplane current are within limits.
- All communication ports and protocols are available.
- Programming software and controller family are confirmed.
- Safety functions use suitably rated devices.
Before standardizing on any controller family, check its lifecycle status so you do not design in a product that is already Active Mature.
If you are choosing within the Siemens range, see our S7-1200 vs S7-1500 comparison.
Frequently Asked Questions
What does it mean to define I/O for a PLC?
It means listing every field device the PLC must read or control, then classifying each as a digital or analog input or output with its voltage and signal type.
How do I count I/O for a PLC?
Go through the machine or process device by device. Count inputs such as switches and sensors, and outputs such as motor starters, solenoids and lamps, then add a margin for future changes.
How much spare I/O should I allow?
DigiKey’s applications guidance suggests adding 25% to the initial estimate. Your project specification or company standard may set a different figure.
What is the difference between digital and analog I/O?
Digital I/O handles discrete on or off states. Analog I/O handles continuous values, such as 0 to 10 V or 4 to 20 mA signals.
Should I choose relay or transistor outputs?
Transistor outputs are faster but have lower current capability and a specific voltage. Relay outputs are isolated and can switch different voltages and higher currents, but they are slower.
What is a PLC power budget?
It is a check that the power supply can deliver the current drawn by the controller and modules. On modular systems, this includes the backplane current at each voltage.
Which communication interface does a PLC need?
Choose it from what must connect to the PLC, such as HMIs, drives, remote I/O and plant networks. Check whether the port is built in or needs a separate module.
Can a standard PLC handle an emergency stop?
No. A general-purpose PLC is not safety rated. Emergency stop and other safety functions should use a device rated for the hazard level.
Sources and Further Reading
- DigiKey: How to Choose the Correct PLC: I/O counting, 25% margin and safety.
- DigiKey: Choosing a PLC: input and output types, analog ranges and communication limits.
- DigiKey: Controllers, PLC Modules: module parameters and supply voltage.
- Rockwell Automation: Compact I/O Selection Guide, 1769-SG002C: module, backplane and power supply data.