To control a drive with an analog potentiometer, connect its two outer terminals to the drive’s +10 V reference and analog common, and connect the wiper to the analog speed input. The pot then sends a 0 to 10 V command, which the drive scales to speed. If the response feels slow or unstable, adjust the ramp time, analog filter and scaling, in that order, and check for electrical noise.
| Pot terminal | Connects to | Typical drive label |
|---|---|---|
| One outer end | 10 V reference | +10V, AVR or REF |
| Wiper (center) | Analog voltage input | AI, AVI or V_REF |
| Other outer end | Analog common | ACM, GND or COM |
| Cable shield | Drive shield or ground terminal | E(G), SH or as shown in the manual |
How to Wire a Speed Potentiometer
- Isolate the drive and wait for the stored energy to discharge as the manual instructs.
- Identify the reference, analog input and common from the control terminal diagram.
- Connect the pot with its outer ends on +10 V and common and its wiper on the input.
- Terminate the shield where the drive manual specifies.
- Set the input type to voltage if the drive uses a jumper, switch or parameter.
- Select the analog input as the frequency or speed source.
- Provide a run command. On most drives, the pot sets the speed but does not start the motor.
- Test with the motor uncoupled where practical, and confirm direction and maximum speed.
Choosing the potentiometer value
The drive’s reference supply has a current limit, so the pot value matters. Current through the pot is 10 V divided by its resistance. Delta’s VFD-EL reference is rated at only 3 mA, while its VFD-B reference is rated at 20 mA. Both manuals specify a 5 kΩ, 0.5 W potentiometer.
| Pot value | Reference current | Within 3 mA (VFD-EL)? | Within 20 mA (VFD-B)? | Wiper at mid-travel, 47 kΩ input |
|---|---|---|---|---|
| 1 kΩ | 10 mA | No | Yes | 4.97 V |
| 2 kΩ | 5 mA | No | Yes | 4.95 V |
| 5 kΩ | 2 mA | Yes | Yes | 4.87 V |
| 10 kΩ | 1 mA | Yes | Yes | 4.75 V |
A larger pot draws less current, but the drive’s input resistance loads it slightly more. At mid-travel, a 5 kΩ pot feeding a 47 kΩ input gives about 4.87 V instead of 5 V. That is why the speed may not be perfectly proportional to the knob marking, and why scaling can be trimmed at commissioning.
How to Scale the Speed Command
With no offset, the commanded speed is proportional to the analog voltage. Most drives let you choose which frequency or speed corresponds to the maximum input.
| Pot voltage | 60 Hz VFD | Servo scaled to 3000 rpm at 10 V |
|---|---|---|
| 0 V | 0 Hz | 0 rpm |
| 2.5 V | 15 Hz | 750 rpm |
| 5 V | 30 Hz | 1500 rpm |
| 7.5 V | 45 Hz | 2250 rpm |
| 10 V | 60 Hz | 3000 rpm |
If the motor should never run below a set speed, use the drive’s minimum frequency or bias setting, not a resistor in series with the pot. If you are selecting the drive itself, our comparison of VFDs and soft starters explains which one offers real speed control.
Potentiometer to Servo Response Speed: What Sets It
When you turn the knob, the signal passes through several stages before the shaft changes speed. The slowest stage sets the response you notice. On a VFD, that is usually the acceleration ramp. On a servo, the command filter and S-curve settings are often the first place to look.
| Stage | What it does | If set too slow | If set too fast |
|---|---|---|---|
| Analog input filter | Smooths noise on the signal | Knob feels laggy | Speed jitters |
| Accel / decel ramp | Limits rate of speed change | Motor is slow to follow | Overcurrent or overvoltage trips |
| S-curve | Softens the start and end of ramps | Longer speed changes | More jerk on the machine |
| Speed loop gain | Corrects speed error | Soft, sluggish response | Vibration or oscillation |
Worked example: VFD ramp time
Acceleration time is commonly defined as the time from zero to maximum frequency. With a 60 Hz maximum and a 5 s ramp, a knob change from 20 Hz to 40 Hz takes:
A typical analog filter is far shorter. Delta’s VFD-B, for example, has an AVI input delay adjustable from 0.00 to 10.00 s with a factory setting of 0.05 s. Reducing that filter would barely change this response, so the ramp is the setting to adjust. Check how your own drive defines its ramp, because some models differ.
Servo drives
A servo in analog speed mode works on the same principle. In AutomationDirect’s SureServo2, for example, P1.040 sets the maximum speed for the analog command, and P1.034 to P1.036 shape the S-curve used by the analog speed command filter. A low-pass filter removes unwanted noise, but too much filtering reduces bandwidth. The same trade-off appears in PID tuning: more smoothing means less speed of response.
Fixing Noise and Unstable Speed
Analog signals are low level and sit close to high-power drive wiring, so noise is the most common problem. Delta advises using shielded wiring and keeping it as short as possible, under 20 m on the VFD-EL. Yaskawa’s GA500 manual calls for shielded twisted-pair cable with the shield connected to terminal E(G) when using an external potentiometer.
| Symptom | Likely cause | Fix |
|---|---|---|
| Speed hunts at a steady setting | Noise or worn pot track | Measure the wiper voltage, reroute the cable, replace the pot |
| Speed jumps when turning the knob | Dirty or worn wiper | Replace the pot |
| Works backward | Outer terminals swapped | Swap +10 V and common at the pot |
| No speed change | Wrong source or input mode | Check source parameter and voltage/current setting |
| Never reaches full speed | Scaling, gain or low reference | Measure 10 V, then check maximum frequency |
| Motor creeps at zero | Offset or noise | Adjust offset or use a deadband, if available |
| Trips when the knob is turned fast | Ramp too short | Increase accel or decel time |
Keep the signal cable away from motor leads and connect shields as the manufacturer directs. Our guides to earthing and grounding and power quality problems explain the wider causes of electrical noise. Where the signal comes from a controller instead of a knob, see what a PLC is and how its analog outputs are used.
Frequently Asked Questions
How do you wire a potentiometer to a VFD?
Connect one outer pot terminal to the drive’s +10 V reference, the other outer terminal to analog common, and the wiper to the analog voltage input. Then set the drive’s frequency source to that input.
What size potentiometer is used for a VFD?
Use the value in the drive manual. Delta’s VFD-EL and VFD-B specifications list 5 kΩ, 0.5 W, which is a common choice. Do not assume another value is safe for the reference supply.
Why does my speed pot work backward?
The two outer connections are reversed. With the drive powered down, swap the +10 V and common wires at the pot. Leave the wiper where it is.
Why is the motor speed unstable with a potentiometer?
Common causes are electrical noise, a worn pot, a poor common connection, or too little analog filtering. Check the signal with a meter, then check the cable routing and shield.
How do I make the drive respond faster to the pot?
Shorten the acceleration and deceleration times first, then reduce the analog filter if needed. Confirm the motor and load can accept the faster change without tripping.
Can a potentiometer control a servo drive?
Yes, if the drive has an analog speed command input and is set to speed mode. The drive’s scaling parameter sets how many rpm correspond to the analog voltage.
Does turning the pot to zero stop the motor safely?
No. It only reduces the speed command. Use the drive’s stop function for normal stopping, and a properly designed safety circuit for protection of people.
Should a speed potentiometer be linear or logarithmic?
Use a linear taper, so that knob position is proportional to voltage and speed. A logarithmic taper makes most of the speed change happen over a small part of the rotation.
Sources and Further Reading
- Delta: VFD-EL Series User Manual: reference rating, input impedance, pot value and analog wiring.
- Delta: VFD-B User Manual: reference rating and analog input delay.
- Yaskawa: GA500 Installation and Primary Operation Manual: shielded wiring for an external potentiometer.
- AutomationDirect: SureServo2 User Manual, Chapter 6: analog speed scaling, S-curve and filters.