An electrical hazard in industry is any condition where contact with, or failure of, electrical equipment can cause injury, fire or an explosion. The common electrical hazards in industry are electric shock and electrocution, arc flash and arc blast, electrical burns, electrical fires, explosions in hazardous areas, and falls caused by a shock. You control them in a set order: isolate the equipment and prove it dead, add engineering safeguards, follow strict procedures, and use PPE only as the last line of defence.
This guide is for maintenance teams, supervisors, safety managers and students dealing with electrical hazards in the workplace. It starts with UK law and HSE guidance, and shows where US and international rules differ. Last verified: 15 November 2026.
The short answer
- Main hazards: shock and electrocution, arc flash, arc blast, burns, fire, explosion, and falls or other secondary injuries.
- The “3 types”: most often shock, arc flash and arc blast. HSE groups them as shock and burns, arcing, fire and explosion. Both are correct; they group the hazards differently.
- Where they sit: switchgear, motor control centres, motors and drives, temporary power, wet areas, hazardous areas and overhead lines.
- Why accidents happen: damaged insulation, poor earthing, overloaded circuits, weak maintenance, bypassed isolation and untrained people.
- Best protection: work dead. Isolate, lock off and prove dead before touching anything. PPE comes last.
1. Why electrical safety matters in industrial plants
Industrial plants run heavy electrical loads around the clock. The equipment is powerful, often high voltage, and surrounded by heat, dust, moisture and moving machinery. One mistake near live equipment can cause electric shock, burns, a fire or an explosion. Beyond the human cost, a single event can wreck equipment and stop production.
The US Bureau of Labor Statistics (BLS) recorded 142 deaths from exposure to electricity in 2023 and 130 in 2024. The 2024 figure is about 2.6% of all 5,070 fatal work injuries that year. Nearly half were direct contact with electricity, and almost as many were indirect, for example through equipment or lines. These are US figures. HSE publishes Great Britain’s numbers each year under the accident kind “contact with electricity or electrical discharge”.
2. What is an electrical hazard in an industrial plant?
An electrical hazard is a condition where electrical energy can hurt people or damage property. HSE describes the harm as electric shock, electric burns, fires of electrical origin, electric arcing and explosions started by electricity.
A hazard is the source of possible harm, such as a live busbar behind an open panel door. An accident is what happens when someone is actually harmed, for example when a dropped spanner touches that busbar. Hazards are always present. Controls stop them turning into accidents.
Common electrical hazards in industrial workplaces include:
- exposed live parts and damaged cables or insulation
- poor earthing or bonding
- overloaded circuits and loose connections
- wet, dusty or corrosive conditions
- faulty or unsuitable equipment, including in hazardous areas
- overhead lines and buried cables
3. Why are electrical hazards more common in industrial environments?
Homes and offices have electrical risks too. Industry has more of them, and they are more severe. These factors drive electrical hazards in manufacturing and process plants:
- Heavy loads and high fault levels. A large supply can release far more energy in a fault than a domestic circuit.
- High-voltage equipment. Switchgear and distribution boards sit at the centre of the plant and carry large currents.
- Motors and drives. Motor control centres (MCCs) and variable frequency drives (VFDs, see VFD vs soft starter) run hot and vibrate, which loosens terminals and ages insulation. See also the common causes of motor failure.
- Harsh conditions. Heat, moisture, dust and corrosive chemicals break down insulation and enclosures.
- Continuous operation. Shutdowns are hard to get, which tempts people to work live.
- Temporary installations and maintenance. Temporary cables, extension leads and short-term supplies are less well protected than fixed wiring.
Electrical safety in industrial plants therefore has to cover more than the electrical room. Figure 2 shows where hazards tend to cluster.
4. What are the main types of electrical hazards in industry?
The three types most often given are electric shock, arc flash and arc blast. This is a common grouping by the energy involved. It is not a universal definition, and other bodies group the hazards differently.
4.1 Electric shock
Electric shock happens when the body becomes part of an electrical circuit and current flows through it. Touching an energised terminal in a panel is a typical plant example.
4.2 Arc flash
An arc flash is a sudden release of heat and light when current jumps through air between conductors, or from a conductor to earth. A short circuit inside switchgear can cause one.
4.3 Arc blast
An arc blast is the pressure wave and debris that come with the arc. The air and metal around the arc heat so fast that they expand violently, which can throw people and damage nearby equipment.
Different sources use different groupings, so the answer to “what are the 3 types of electrical hazards” depends on who you ask.
| Source or view | How it groups the hazards | Focus |
|---|---|---|
| Common safety training view | Electric shock, arc flash, arc blast | Energy released |
| HSE (UK) | Shock and burns from live parts, arcing, fire, explosion, plus indirect injuries such as falls | Hazard and outcome |
| OSHA construction workbook (US) | Electrocution, electrical shock, burns from arc blast, falls | Injury outcome |
| NPTEL course notes (India) | Electrical shock, arc burns, blast effects | Academic framing |
5. Common electrical hazards in industrial plants, with examples
Table 2 gives the overview. The sections after it explain how each hazard works, where it shows up in a plant, and the main control. Section 7 covers controls in full.
| Hazard | How it happens | Typical plant source | What decides severity |
|---|---|---|---|
| Shock and electrocution | Current passes through the body | Exposed live parts, damaged cables, poor earthing | Current, path through the body, time, wet conditions |
| Arc flash | Current jumps through air, releasing intense heat and light | Switchgear, MCCs, panels, busbars | Fault level, time to clear the fault, distance, enclosure |
| Arc blast | Rapid heating creates a pressure wave and molten metal | Faulted switchgear, cable and joint faults | Same factors as arc flash |
| Electrical burns | Current through tissue, or heat from an arc | Live-part contact, panel faults | Contact time, current, distance |
| Electrical fire | Overheating from overloads, loose joints or damaged insulation | Overloaded circuits, ageing wiring, dusty equipment | Load, nearby fuel, protection settings, maintenance |
| Explosion | A spark, arc, hot surface or static discharge ignites gas, vapour or dust | Chemical, paint-spray and powder areas | Atmosphere, ignition energy, equipment suitability |
| Falls and secondary injuries | A shock causes loss of control | Ladders, platforms, work near machinery | Height, nearby machinery, response time |
| Line and cable strikes | Plant or tools touch or come near lines or cables | Cranes, scaffolds, excavations | Voltage, distance, contact time |
5.1 Electric shock and electrocution
Electric shock is the effect of current passing through the body. Electrocution is a shock that kills. Voltage is the push that drives current, but current does the harm. How serious a shock is depends on the size of the current, its path through the body, how long it lasts and the person. HSE says contact above about 50 V AC can affect breathing and the heart, and that no one is immune to injury from electricity.
A shock from hand to foot sends current across the chest, which is the most dangerous path. Damp conditions and large amounts of metalwork, both common in plants, make shocks worse. Figure 3 shows the approximate effects.
Typical plant examples:
- touching live terminals in an MCC with the door open
- a damaged flexible cable on a portable tool or hoist
- an unearthed metal enclosure that becomes live after a fault
- working close to energised busbars with no barrier in place
Main control: work dead, and keep a good earth path so the protective device trips fast. UK engineers say earthing and US sources say grounding; the two mean the same thing in practice (see earthing vs grounding).
5.2 Arc flash and arc blast hazards
Both hazards come from the same event, an electrical arc. The flash is the heat and light. The blast is the pressure wave, molten metal and debris. The arc temperature is often quoted at around 19,000°C, several times hotter than the surface of the Sun. Treat that as an illustration, since each fault is different.
In plants, arcs usually start in these ways:
- a fault between conductors in ageing or faulty switchgear or a distribution panel
- a metal tool slipping into a live panel
- dust and moisture building up on insulation until it breaks down
- operating or racking out a breaker that is faulty or already under fault
- working on equipment that was not proven dead
The injuries are thermal burns, eye damage, hearing damage, being thrown by the blast, and wounds from flying metal. Severity depends on the available fault current, how long the fault lasts before protection clears it, how far away the worker is and how the equipment is enclosed. That is why correct settings and protection coordination matter. For boundaries, labels and PPE ratings, see the full guide to arc flash.
Main control: de-energise before work. If live work is truly unavoidable, assess the arc risk first and use arc-rated PPE.
5.3 Electrical burns
There are three kinds of burn from electricity:
- Contact burns come from current passing through the body, and HSE guidance notes current can cause deep burns.
- Arc flash burns come from intense radiant heat.
- Thermal burns come from hot gases, molten metal, hot surfaces and ignited clothing.
Common workplace examples are a hand on a live busbar, an arc at a panel and molten copper thrown out by a fault. Because current can burn deep inside the body, every electrical burn needs a medical check, even if the skin looks fine.
Main control: isolation, insulation and guarding, with arc-rated clothing for any task that carries arc risk.
5.4 Electrical fires
Electricity starts fires by heating something until it ignites. The usual causes are overloaded circuits, loose connections that heat up, damaged insulation, faulty equipment and poor maintenance. Dust around motors, drives and panels adds fuel.
In plants this looks like overloaded distribution boards, a loose terminal overheating inside an MCC, or a motor running above its rating. Overcurrent devices such as fuses and circuit breakers and motor thermal overload relays should disconnect the circuit before cable insulation burns.
Main control: correct sizing and protection, plus regular inspection, testing and thermal imaging surveys to find hot joints early.
5.5 Electrical explosions
Where flammable gas, vapour or combustible dust is present, a spark, arc, hot surface or static discharge can set off an explosion. HSE points to explosions caused by unsuitable electrical apparatus and to static igniting vapours or dusts, for example in a spray-paint booth. Even a single torch battery can produce a spark strong enough to ignite an explosive atmosphere.
Examples are non-certified lighting in a solvent store, a standard motor in a flour-handling area, and a junction box that has lost its seal. Section 9 explains the zone system.
Main control: use equipment certified for the zone, and control every ignition source.
5.6 Falls and other secondary injuries
A shock too small to injure on its own can still cause a serious fall. HSE notes that shocks can make people fall from ladders or scaffolds, and can cause loss of control that leads to contact with moving machinery.
Typical cases are technicians on platforms or cable trays near live gear, and people working at height on lighting circuits. Equipment that starts unexpectedly while someone is working on it is a related risk, which is why isolation matters.
Main control: avoid live work at height, use proper fall protection, and isolate machinery before anyone works on it.
5.7 Overhead and underground electrical hazards
HSE advises that you do not work within 6 metres of an overhead line, where equipment could come that close, without getting advice, and that you speak to the line owner first. It also warns that electricity can flash over from a line even when plant does not touch it. Cranes, tipper lorries, scaffolds and excavators are the usual culprits in plant yards.
Underground cables are just as dangerous. HSE says to assume buried cables are present when digging in streets, pavements or near buildings. Records are only a guide, so confirm positions with a locator and dig safely. Temporary connections add their own risk and need the same care as fixed supplies.
Main control: identify lines and cables before work starts, keep clear, and get lines made dead where possible.
6. Common causes of electrical hazards in industrial facilities
US OSHA groups the causes of electrical accidents into three: unsafe equipment or installation, an unsafe environment, and unsafe work practices. In industrial plants these show up in ten ways.
6.1 Poor electrical installation
Wrong cable sizes, poor terminations, unsuitable equipment and missing barriers create hazards from day one. Installations in the UK should follow BS 7671 and be designed for the conditions they work in.
6.2 Damaged wires and insulation
Heat, vibration, chemicals and physical damage wear insulation away until live conductors are exposed. Insulation resistance testing finds deterioration before it causes a fault.
6.3 Improper earthing and bonding
Without a reliable earth path, a fault can leave metalwork live and the protective device may not trip. The earthing arrangement matters; see types of earthing systems.
6.4 Overloaded electrical circuits
Too much load for the cable or equipment rating causes overheating, which ages insulation and can start a fire.
6.5 Lack of regular inspection and maintenance
Loose joints, worn insulation and out-of-date protection settings go unnoticed until something fails. HSE says testing frequency should be based on risk, written down, and adjusted according to the faults found. Protective devices also need checking, for example through relay testing.
6.6 Wet, dusty and corrosive working conditions
Moisture lowers the resistance of both equipment and people. Dust and corrosion cause tracking and poor connections.
6.7 Improper use of electrical tools
Damaged leads, wrong equipment for the environment and tools used outside their rating are common triggers, particularly with portable equipment.
6.8 Poor training and lack of safety awareness
People who cannot recognise a hazard cannot avoid it. The Electricity at Work Regulations require anyone doing work where danger could arise to be competent, or supervised by someone who is.
6.9 Bypassing lockout/tagout procedures
Skipped locks, missing proving tests and assumed isolation lead to unexpected energisation, one of the most serious ways people get hurt during maintenance.
6.10 Unsafe temporary electrical connections
Temporary supplies often lack proper protection, earthing and mechanical protection, and they stay in place longer than planned.
| Main cause | Possible electrical risk |
|---|---|
| Damaged insulation | Electric shock |
| Poor earthing | Electric shock and equipment faults |
| Overloaded circuits | Electrical fire |
| Loose connections | Overheating and fire |
| Poor maintenance | Electrical failure and arc flash |
| Wet conditions | Higher shock risk |
| Bypassed LOTO | Unexpected energisation |
7. How to control electrical hazards in industry: the hierarchy of controls
The hierarchy of controls ranks protection from most to least effective. The idea is simple: removing the hazard is far more reliable than relying on people to behave perfectly or on PPE to work when something goes wrong. OSHA’s own guidance places PPE last for the same reason.
7.1 Elimination
- De-energise equipment before maintenance.
- Remove hazards that are not needed.
- Avoid live work wherever possible.
In the UK, working dead is the default under the Electricity at Work Regulations 1989. Regulations 12 and 13 cover isolation and the precautions for equipment made dead. Regulation 14 allows live work only when all three conditions are met: it is unreasonable for the equipment to be dead, it is reasonable to work live, and suitable precautions are in place. HSE puts it plainly: it is never absolutely safe to work on live equipment.
7.2 Substitution
- Replace outdated or unsafe equipment, for example old open switches with enclosed ones.
- Use lower-voltage systems where they are suitable, such as low-voltage control circuits.
7.3 Engineering controls
- Provide reliable earthing and bonding.
- Fit RCDs. HSE recommends a rating of 30 mA or less, especially in wet places. They do not stop every type of shock, so isolation is still essential. Test them regularly.
- Use insulation, enclosures and barriers so live parts cannot be touched.
- Fit interlocks on doors and covers that give access to live parts.
- Install suitable protective devices; see types of circuit breakers.
- Where available, use arc-resistant switchgear and remote operation so workers stay away from the equipment.
7.4 Administrative controls
- Carry out electrical risk assessments.
- Use written safe systems of work and permits for higher-risk tasks.
- Train people and check they are competent before authorising them.
- Restrict access to switch rooms and live areas, and use clear signs.
- Follow risk-based inspection and maintenance schedules.
7.5 Personal protective equipment (PPE)
- Voltage-rated insulating gloves.
- Arc-rated clothing.
- Safety helmets and face shields.
- Insulating mats and protective footwear.
- Inspection and care of all PPE before each use.
PPE reduces injury if something goes wrong, but it does not remove the hazard. Our guide to electrical safety PPE covers types, ratings and inspection.
8. Lockout/tagout (LOTO): preventing electrical accidents during maintenance
8.1 What is lockout/tagout?
Lockout/tagout is a method of making equipment safe to work on. Energy sources are isolated, each isolation point is locked and tagged, stored energy is released, and the absence of energy is proved. In the UK the same idea is usually called safe isolation or lock-off. For the full step-by-step method, see our lockout/tagout procedure guide.
8.2 Why is LOTO important in industrial facilities?
Many electrical injuries during maintenance happen because equipment was live, or became live, when the worker thought it was off. LOTO protects against unexpected energisation and unexpected machine start-up. HSE says each isolation device should be locked, the keys kept by the person doing the work, and warning notices placed at isolation points.
8.3 How does the LOTO process work?
- Identify all energy sources, including electrical, mechanical, pneumatic and hydraulic.
- Shut the equipment down.
- Isolate the electrical supply at the correct isolation point.
- Apply locks and warning tags.
- Release or control any stored energy.
- Prove the equipment dead using a suitable, tested voltage indicator, checking all conductors.
- Complete the work, then restore supply only through the authorised process.
8.4 Common LOTO mistakes to avoid
- Missing an energy source.
- Using an incomplete isolation procedure.
- Not proving that the equipment is dead.
- Removing someone else’s lock without an authorised procedure.
- Restarting equipment before everyone is clear.
US note
In the US, OSHA’s LOTO standard (29 CFR 1910.147) does not cover electrical hazards from work on or near conductors in electric-utilisation installations. Those are covered by Subpart S.
9. Electrical hazards in hazardous areas
In some areas flammable gas, vapour or combustible dust can collect in explosive amounts. Ordinary electrical equipment can ignite them. These places need classified areas and specially certified equipment.
9.1 Chemical and petrochemical plants
Process vessels, pumps and solvent handling release flammable vapour. Motors, lighting and junction boxes in these zones must be certified for them.
9.2 Oil and gas facilities
Wellheads, compressors and pipework can release gas, so sites rely on hazardous area classification drawings to show where each zone starts and ends.
9.3 Grain and food processing plants
Flour, sugar and grain dust can form explosive clouds, and dust layers on hot motors can ignite. Housekeeping is an electrical safety control here.
9.4 Mining and heavy manufacturing
Mining has its own equipment group, because coal dust and methane may be present, and some mining equipment must be de-energised if an explosive atmosphere forms. Heavy manufacturing adds metal dust alongside high fault levels.
9.5 Wet and corrosive processing areas
These areas are not explosive, but water and corrosion raise shock risk and damage equipment. Use suitably rated enclosures and RCD protection.
In Great Britain, the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR) require hazardous places to be classified into zones based on how often and how long an explosive atmosphere is present. Gas and vapour zones are 0, 1 and 2. Dust zones are 20, 21 and 22. Equipment categories 1, 2 and 3 match them, as Figure 5 shows.
- Flammable gases and vapours: classified by how often they are present.
- Combustible dust: includes layers and clouds, so cleaning matters.
- Suitable equipment: choose the category and protection type for the zone.
- Ignition-source control: cover sparks, hot surfaces and static, not only electrical equipment.
Zones and Divisions
Zone systems are used in the UK and under IEC standards. North America has traditionally used Class and Division classification. The rules depend on the country, so always follow the standard that applies to your site.
10. Electrical safety standards and regulations for industrial facilities
No single rulebook applies everywhere. Table 4 labels each rule by region, with the UK first.
| Region | Regulation or standard | Main focus |
|---|---|---|
| UK | Electricity at Work Regulations 1989 | Legal duty to prevent danger from electrical systems at work |
| UK | HSE guidance: HSG85, HSR25, INDG231 | Safe working practices and guidance on the Regulations |
| UK | BS 7671 (IET Wiring Regulations) | Design, installation and verification of low-voltage installations |
| UK | DSEAR 2002 | Risks from flammable and explosive atmospheres, including zoning |
| UK | RIDDOR 2013 | Reporting deaths, specified injuries and dangerous occurrences |
| International | IEC 60364 | Low-voltage electrical installations |
| International | IEC 60479 | Effects of current on the human body |
| International | IEC 60079 series | Equipment and classification for explosive atmospheres |
| United States | OSHA 29 CFR 1910 Subpart S | General industry electrical safety |
| United States | OSHA 29 CFR 1910.147 | Control of hazardous energy (LOTO) |
| United States | NFPA 70E | Workplace electrical safety practices |
| Canada | CSA Z462 | Workplace electrical safety |
The Electricity at Work Regulations apply to almost all workplaces in Great Britain. Their general rule is that every work activity on or near an electrical system must be carried out so that it does not give rise to danger, so far as is reasonably practicable. Deaths, specified injuries, plant touching overhead lines, and electrical incidents that cause a fire or explosion can all be reportable under RIDDOR.
Important note
NFPA 70E is an industry consensus standard, not itself an OSHA regulation, and OSHA says it generally does not enforce it. Countries such as India, Australia and the Gulf states have their own rules, so check your local requirements and the current edition of any standard.
11. Industrial electrical safety checklist
Use this electrical hazard control measures checklist for routine inspections and audits. It suits safety managers, maintenance teams and employers.
11.1 Electrical equipment inspection
- ☐ Cables and wires are free from damage.
- ☐ Panels and switchgear are in good condition.
- ☐ Earthing and bonding are intact.
- ☐ No loose connections or signs of overheating.
- ☐ Protective devices are present and working.
11.2 Workplace safety inspection
- ☐ Electrical panels are accessible and clear of storage.
- ☐ Working areas are clear.
- ☐ Water and moisture are kept away from equipment.
- ☐ Warning signs and barriers are in place.
- ☐ Temporary power installations are checked.
11.3 Worker safety and PPE
- ☐ Workers have the required training.
- ☐ Insulating gloves and protective clothing are inspected.
- ☐ Only qualified or competent people carry out authorised electrical tasks.
- ☐ Emergency procedures have been reviewed.
11.4 LOTO and maintenance verification
- ☐ All energy sources are identified.
- ☐ Isolation points are checked.
- ☐ Absence of voltage is proved.
- ☐ Lock and tag procedures are confirmed.
- ☐ Inspection and maintenance are recorded.
Free download: Industrial Electrical Safety and LOTO Audit Checklist (PDF)
A printable two-page audit sheet with equipment details, hazard identification, isolation verification, PPE inspection, emergency contacts and approval signatures.
Download the PDF checklist12. What should you do if someone gets an electric shock?
Follow your site emergency procedure. The standard first aid steps from St John Ambulance are:
- Do not touch the casualty while they may still be in contact with the electricity.
- Switch off the supply, if it is safe to do so.
- If you cannot switch it off, stand on dry insulating material and use a dry wooden pole, such as a broom handle, to push their limb away. This is for low-voltage situations only.
- If that fails, loop rope around their arms or ankles and pull them clear without touching them.
- Once contact is broken, check them and treat any injuries. Trained people should give CPR if needed.
- Call 999 or 112.
Do not approach high-voltage equipment or fallen overhead lines. Keep others back and wait for the authorised person or network operator to make it safe. Everyone who has had a shock should be medically assessed, even if they feel well, and the incident should be reported and, where required, notified to HSE under RIDDOR.
Flammable gases and vapors add an ignition risk. Our guide to Class 1 Division 1 electrical requirements explains zones, protection methods and conduit seals.
For the full breakdown of hazardous locations, including Groups A–G, temperature codes and protection methods, read our guide to Class 1 Div 1 vs Div 2.
13. Frequently asked questions about electrical hazards in industry
1. What are the common electrical hazards in industry?
Electric shock and electrocution, arc flash and arc blast, electrical burns, electrical fires, explosions in hazardous areas, and falls or other secondary injuries. Contact with overhead lines and buried cables is also a major hazard.
2. What are the three main types of electrical hazards?
The common answer is electric shock, arc flash and arc blast. HSE groups them as shock and burns, arcing, fire and explosion, and OSHA’s construction material lists electrocution, shock, burns from arc blast and falls. The grouping differs, but the hazards are the same.
3. What is an electrical hazard in the workplace?
It is any condition where electrical energy can cause injury or damage, such as exposed live parts, damaged insulation, poor earthing, overloaded circuits or wet conditions.
4. What causes electrical accidents in industrial plants?
Damaged insulation, poor earthing, overloads, weak maintenance, wet or dusty conditions, untrained people, unsafe temporary supplies and bypassed lockout/tagout. See section 6.
5. How can electrical hazards be prevented in manufacturing plants?
Work dead wherever possible, then add engineering controls, administrative controls such as permits and training, and PPE last. Regular inspection and maintenance keep the controls working.
6. What is the difference between arc flash and arc blast?
Arc flash is the intense heat and light from an electrical arc. Arc blast is the pressure wave, molten metal and debris that come with it. They happen together but cause different injuries.
7. How does lockout/tagout prevent electrical accidents?
It isolates the equipment, locks and tags each isolation point, releases stored energy and proves the equipment dead. That prevents it from being energised while someone is working on it.
8. Can PPE alone protect workers from electrical hazards?
No. PPE reduces the severity of injury but does not remove the hazard. It is the last line of defence after isolation, engineering controls and safe procedures.
9. Why is earthing important in industrial electrical systems?
A good earth gives fault current an easy path back to the source, so the protective device trips quickly instead of leaving exposed metalwork live. “Earthing” is the UK term and “grounding” the US term.
10. What are the risks of working with live electrical equipment?
Shock, burns, arc flash and arc blast, and falls caused by the shock. In the UK, live work is allowed only if all three conditions in Regulation 14 are met.
11. What electrical safety standards apply to industrial facilities?
In the UK, the Electricity at Work Regulations 1989, BS 7671 and DSEAR 2002 apply, with HSE guidance. Elsewhere, OSHA and NFPA 70E (US), CSA Z462 (Canada) and IEC standards are used. See section 10.
12. What should you do if someone receives an electric shock?
Do not touch them until the supply is off or you have safely broken contact, then call 999 and give first aid. See section 12.
13. Are electrical hazards present outside electrical rooms?
Yes. Portable tools, temporary power, wet areas, overhead lines and hazardous atmospheres all create risk. ESFI’s analysis of US data for 2011 to 2023 found about 74% of workplace electrical deaths were in non-electrical occupations.
14. Conclusion: making industrial electrical safety a priority
Electrical hazards in industry include shock, arc flash, arc blast, burns, fire, explosion and falls. They come from damaged equipment, harsh conditions and unsafe work, and each can be controlled. Regular inspection and maintenance keep equipment in a safe condition.
Build your electrical safety programme on the hierarchy of controls: de-energise first, use lockout/tagout every time, add engineering and procedural controls, and treat PPE as the final layer. Use the checklist above to find gaps before they cause harm.
Disclaimer
This article is general information, not legal or engineering advice. Only competent, authorised people should work on electrical equipment, and you should always follow the law, standards and procedures that apply to your site.
Sources
- HSE: Introduction to electrical safety
- HSE: Electricity at work FAQs
- HSE: The Electricity at Work Regulations 1989, guidance on Regulations (HSR25)
- HSE: Electrical safety and you (INDG231)
- The Electricity at Work Regulations 1989 (legislation.gov.uk)
- HSE: Hazardous area classification and control of ignition sources
- HSE: ATEX and DSEAR definitions
- St John Ambulance: Electric shock first aid
- US BLS: Fatal occupational injuries by event or exposure, 2024
- US BLS: Fatal occupational injuries for selected events or exposures, 2023 to 2024
- OSHA: Controlling electrical hazards (publication 3075)
- OSHA: Control of hazardous energy
- OSHA: Letter of interpretation on NFPA 70E
- Cornell University EHS: Electrical safety, effects of current
- ESFI: Workplace electrical injury and fatality statistics