A thermal overload relay is a protection device that stops an electric motor when it draws too much current for too long. It uses heat to do the job. The motor current warms a bimetallic strip, the strip bends, and the relay opens a contact that switches off the motor’s contactor.
Quick answers
- What it does: it trips the motor starter when current stays above the safe level for too long.
- What it does not do: it does not protect against short circuits. You still need a fuse, MCB or motor protection circuit breaker (MPCB).
- Setting: start from the full load current on the motor nameplate, then follow the relay’s manual.
- Trip class: Class 10 suits normal starts. Class 20 or 30 suits long, heavy starts.
- Why it trips: a real overload, a low setting, a trip class that is too fast, a supply fault, a hot panel or repeated starts.
Safety note: this article is general information. It is not installation, testing or repair guidance. Selection, setting, wiring and testing must follow the manufacturer’s manual and local rules (in the UK, BS 7671). Work must be done by competent people with the equipment isolated and locked off. Never bypass or jumper an overload relay.
What Is a Thermal Overload Relay?
Definition and main purpose
A thermal overload relay (also called a bimetallic overload relay, or “thermal relay” for short) senses motor current through heat. If the current stays above the set value for long enough, the relay trips. It opens a contact in the contactor’s coil circuit, the contactor drops out and the motor stops.
It handles overloads: currents a little above, up to several times above, the motor’s rated current, lasting seconds to minutes. Think of a jammed conveyor or a clogged pump. The relay reacts to current, not to the real winding temperature, so it works as a model of the motor’s heating.
Why motors need overload protection
A motor running above its rated current makes extra heat in its windings. Hotter insulation ages faster, and sustained overheating ends in winding failure. In the widely quoted EPRI survey of utility motors, stator winding faults caused 37% of failures, second only to bearings at 41%. Overload, a locked rotor and voltage imbalance are all known ways to overheat a winding. For a wider view, see the common causes of motor failure.
The law and wiring rules reflect this. BS 7671 expects motors rated above 0.37 kW to have control equipment with overload protection (Regulation 552.1.2). Check the current edition for the exact wording.
What a thermal overload relay does not do
The most common mistake is to treat an overload relay as complete protection. It is not. A short circuit produces a current many times larger than an overload, in milliseconds. IEC 60947-4-1 says starters and contactors are not normally designed to interrupt short-circuit currents, so a separate device must do that. To understand how those devices differ, read this guide to the difference between a fuse and a circuit breaker.
| Device | What it does | Example |
|---|---|---|
| Thermal overload relay | Senses sustained overcurrent through heat and opens the control circuit | Stops a motor on a jammed conveyor |
| Control relay | Switches control circuits on command. It does not measure motor load | Starts a pump when a float switch closes |
| Protection relay | Monitors a system for faults such as earth fault or overcurrent. See the guide to types of protection relays | Trips a feeder breaker in a switchboard |
| Fuse, MCB or MPCB | Interrupts very large fault currents quickly | Clears a short circuit in the motor cable |
Main applications
- Water pumps: a clogged impeller or seized bearing raises current.
- Fans and blowers: a damper left wide open or heavy dust on the impeller adds load.
- Compressors: high discharge pressure or worn parts raise current.
- Conveyors and crushers: jams and overfeeding cause overloads.
- Agricultural motors: irrigation pumps with silt, grain augers and choppers that jam.
How Does a Thermal Overload Relay Work?
Thermal overload relay working principle
The relay works on the heating effect of current. Heat rises with the square of the current, so a small overload heats slowly and a big overload heats fast. The steps are:
- Motor current flows through a heater element (or directly through the bimetal) in each phase.
- At normal current the heat is small and the strip stays almost straight.
- During an overload the strip heats up and bends.
- The bend moves a trip lever or slider.
- The trip mechanism opens the normally closed 95–96 contact in the contactor coil circuit.
- The contactor drops out and the motor stops. The relay is reset after it cools.
Role of the bimetallic strip
A bimetallic strip is two different metals bonded together. When heated, one metal expands more than the other, so the strip bends toward the lower-expansion side. One metal on its own would only get longer, which gives no useful movement. Two bonded metals turn a tiny length change into a bend that can push a lever.
The strip is also slow to heat. That suits motors: the short surge at start-up is ignored, but a long overload makes the strip bend far enough to trip.
What happens when the motor draws excessive current?
The higher the current, the faster the trip. This is called an inverse-time characteristic. The table shows typical IEC test points for a relay that starts cold.
| Motor current (× setting) | What the relay does |
|---|---|
| 1.05× or less | No trip within two hours |
| 1.2× | Trips within two hours |
| 1.5× | Class 10, 20 and 30 relays trip in under about 4, 8 and 12 minutes (warm relay) |
| 7.2× | Trips inside the class window: 4–10 s (Class 10), 6–20 s (Class 20), 9–30 s (Class 30) |
Construction and Main Parts of a Thermal Overload Relay
The parts are simple. Names vary slightly between makers.
| Part | What it does |
|---|---|
| Bimetallic strip | Bends when heated. One per phase. |
| Heater element | Carries the motor current and warms the strip (indirect heating). |
| Trip mechanism | Turns the strip’s movement into a snap action that changes the contacts. |
| Current setting dial | Sets the relay’s reference current in amps. |
| Reset button | Resets the relay after a trip. Works only after the strip has cooled. |
| Test (and stop) button | Lets a competent person check that the control contact operates, as the manual describes. |
| Auxiliary contacts | One normally closed (95–96) and one normally open (97–98) contact. |
| Differential mechanism | Makes the relay trip faster if one phase carries much less current than the others. |
Thermal Overload Relay Terminals and Diagram
Thermal overload relay symbol
On a schematic the relay appears twice: a heater symbol in the power circuit and a contact in the control circuit. Both carry the same label, usually F (IEC) or OL (US), for example F2.
Thermal overload relay terminals 95, 96, 97 and 98
| Terminals | Contact type | Normal use |
|---|---|---|
| 95–96 | Normally closed (NC) | In series with the contactor coil. Opens on a trip and stops the motor. |
| 97–98 | Normally open (NO) | Closes on a trip. Often feeds an alarm lamp or a PLC input. |
Thermal overload relay connection with a contactor
Most overload relays clip directly under a contactor, so the motor current passes through the relay on its way to the motor. The relay does not switch that current. The contactor does. If you are unsure how the two differ, read about the difference between a contactor and a relay. Together they form the heart of common starters, as covered in this guide to types of motor starters.
Basic motor starter circuit diagram
Pressing Start energises the KM1 coil through the stop button and the relay’s 95–96 contact. The KM1 auxiliary contact then holds the coil on. If F2 trips, 95–96 opens, the coil loses its supply and the motor stops.
Thermal Overload Relay Trip Classes Explained
What is a trip class?
A trip class tells you how long the relay takes to trip under a heavy overload. IEC 60947-4-1 defines it at 7.2 times the setting current, starting from a cold relay. A higher class gives the motor more time to start. Class 10 does not mean a 10 A relay. It relates to a trip time of 10 seconds or less.
IEC thermal overload relay trip classes
| Trip class | Tripping time at 7.2 × setting current | Typical interpretation |
|---|---|---|
| Class 10A | 2–10 seconds | Fast tripping for quick, light starts |
| Class 10 | 4–10 seconds | Normal starting duty |
| Class 20 | 6–20 seconds | Longer starting duty |
| Class 30 | 9–30 seconds | Long starting, heavier duty |
Class 10 vs Class 20 overload relay
Both are tested at 7.2 times setting current. A Class 10 relay must trip within 10 seconds at most. A Class 20 relay may take up to 20 seconds. If the motor needs 12 seconds to reach speed, a Class 10 relay will trip during the start. A Class 20 relay will let the start finish.
Class 20 vs Class 30 overload relay
Class 30 allows up to 30 seconds. It is for very long starts, such as high-inertia fans, centrifuges and large crushers. Do not choose it just to stop nuisance trips. A slower relay leaves the motor under stress for longer, so check that the motor and cable can take the longer start.
How to choose the right trip class
Pick the lowest class that lets the motor start without tripping. Two things decide this: the starting time and the load inertia. A heavy flywheel or large fan takes longer to accelerate. Compare the real starting time with the class window, then check the maker’s trip curve.
Illustrative example (not real product data): a motor takes 12 seconds to start at about 7.2 times its setting current. A Class 10 relay must trip within 10 seconds at that current, so it would trip before the motor reaches speed. A Class 20 relay (6–20 seconds) fits. A real start current is rarely exactly 7.2 times, so confirm with the datasheet curve.
Thermal Overload Relay Trip Curves
What is a trip curve?
A trip curve is a graph of trip time against current. The horizontal axis shows the current as a multiple of the setting current. The vertical axis shows how long the relay takes to trip. Both axes are usually logarithmic. The curve falls to the right: more current, shorter time.
Cold state vs hot state trip curves
Makers publish two curves. Cold state means the relay has carried no load and sits at ambient temperature. Hot state means it has already been carrying current, so the strip is warm and has less heat to gain before it trips. Schneider Electric describes its hot state as 75% of thermal capacity already used. WEG states that, for its RW range, the trip time at operating temperature can be about 25% of the cold value.
How current affects tripping time
| Current (× setting) | Cold relay | Hot relay |
|---|---|---|
| 1.2× | about 17 min | about 4 min |
| 1.5× | about 5 min | about 1 min 15 s |
| 2× | about 2 min | about 31 s |
| 3× | about 45 s | about 11 s |
| 5× | about 15 s | about 4 s |
| 7.2× | about 7 s | about 2 s |
Thermal memory and recovery time
The strip keeps its heat for a while, so the relay has a “thermal memory”. After a trip it must cool before it can be reset. If you restart straight away, the strip begins warm and trips sooner. Recovery time depends on the model and on how hot the strip became, so check the datasheet.
Why trip curves matter during motor starting
The relay’s curve must sit above the motor’s starting current and time, otherwise the relay trips during a normal start. It must also sit below the motor’s thermal limit, otherwise the motor is damaged before the relay acts. Frequent starts use up the thermal margin, so allow for them.
How to Set a Thermal Overload Relay
What is the current setting?
The dial is marked in amps. It sets the reference current the relay is built around. It is not the trip current. The relay carries its setting current without tripping and, from cold, trips within two hours at about 1.2 times that value.
Understanding motor full load current (FLC)
Full load current (FLC, also called FLA) is the current the motor draws at its rated output. You find it on the nameplate, in amps, for a stated voltage. Always use the current at your supply voltage, such as 400 V three-phase in the UK. Never set the dial from kilowatts or horsepower.
Thermal overload relay setting formula
No single formula suits every motor and relay. For an adjustable IEC relay on a direct-on-line starter, the usual starting point is:
Setting current ≈ motor nameplate full load current (at your supply voltage)
Two cases need care. In a star-delta starter, a relay wired inside the motor winding carries only about 58% (1 ÷ √3) of the line current, so its setting is lower. A relay placed in the supply line is set to the full line current. Check your starter diagram and the manual before you decide.
Role of motor service factor
Service factor (SF) shows how much extra load a motor can carry continuously under stated conditions. An SF of 1.15 means up to 115% of rated load. Some manufacturers and codes allow a higher setting when the SF is above 1.0. Others do not. Do not raise the dial just because the nameplate shows an SF. Follow the relay manual and local requirements.
Illustrative setting calculation
Illustrative example (not real product data): a 400 V motor with a nameplate current of 25 A and an SF of 1.15, started direct-on-line.
- Choose a relay whose adjustable range includes 25 A, ideally with 25 A away from the extreme end of the dial.
- Set the dial to 25 A as the starting point, unless the manual says otherwise.
- At 26.25 A (1.05×) the cold relay must not trip within two hours.
- At 30 A (1.2×) it must trip within two hours.
- At 180 A (7.2 × 25 A) a Class 10 relay trips in 4–10 s and a Class 20 relay in 6–20 s.
Common setting mistakes
- Setting the dial from kW or horsepower instead of amps.
- Turning the dial up to stop nuisance trips. This hides the real fault and puts the motor at risk.
- Choosing a relay whose range only just covers the motor current, so the setting sits at the extreme end of the dial.
- Ignoring the star-delta winding current.
- Forgetting that the relay and the motor may be in different ambient temperatures.
- Using the same setting on the output of a variable speed drive without the maker’s guidance.
How to Select the Right Thermal Overload Relay
Work down this checklist for every new motor starter.
| Check | What to confirm |
|---|---|
| Motor full load current | Read it from the nameplate at your supply voltage. |
| Relay current range | The motor current must sit inside the adjustable range, not at its extreme end. |
| Trip class | Match it to the starting time and load inertia (see the load table below). |
| Motor starting time | Longer starts need a slower class. Frequent starts need extra thought. |
| Contactor compatibility | Use a relay made for that contactor frame, or the maker’s mounting kit. |
| Ambient temperature | Check the temperature at the relay, and whether it is compensated. |
| Reset mode | Manual, automatic or remote. Choose manual unless restarting is safe. |
| Short-circuit protection | Pair with a fuse or breaker listed in the maker’s coordination table. |
| Standards and marking | IEC 60947-4-1 and the CE or UKCA marking for your market. |
Choose the correct trip class for the load
This is a starting framework, not a verdict. The real class depends on motor data, starter type and duty cycle.
| Load | Starting time | Class to consider | Why |
|---|---|---|---|
| Pump | Usually short | Often Class 10 | Verify against the real acceleration time |
| Fan | Can be long, especially high inertia | Often Class 20 or higher | A long run-up can look like an overload |
| Compressor | Depends on loaded or unloaded start | Depends | Starting torque and pressure matter |
| Conveyor | Moderate to long | Depends | Loaded starts and jam risk need checking |
| Crusher | Long, high inertia | Often Class 20 or higher | Long acceleration and stall risk |
Check short-circuit protection coordination
Manufacturers publish tables that list which fuse or breaker to fit with each contactor and relay. IEC 60947-4-1 describes two levels of coordination:
- Type 1: after a short circuit there is no danger to people or the installation, but the starter may need repair or replacement.
- Type 2: the starter must still be fit for use. Light contact welding is possible and must be easy to separate under the maker’s maintenance advice.
To see how these devices work together, read about protection coordination.
Ambient Temperature Compensation in Thermal Overload Relays
What is ambient temperature compensation?
A bimetal strip reacts to any heat, including heat from the surrounding air. A compensated relay has an extra bimetal that responds only to the air temperature and cancels its effect. The trip point then stays steady when the panel gets warmer or colder.
How high temperature affects relay operation
In a hot enclosure, such as a panel beside drives or in a boiler room, an uncompensated strip starts warm. It then trips at a lower motor current than the dial shows. A cold enclosure does the opposite, so the relay may trip late.
Compensated vs uncompensated relays and derating
- Compensated: keeps its trip point steady within the range stated by the maker.
- Uncompensated: needs a derating factor from the datasheet in hot or cold conditions.
Illustrative example: WEG lists a current correction factor of 0.87 at 70 °C for its RW range. For a 20 A motor, that method gives 20 ÷ 0.87 ≈ 23 A. This is one maker’s method for one range. It is not a rule for other relays.
Why manufacturer compensation limits matter
Compensation ranges differ by product, and the range where the relay is compensated is not the same as the full operating range. Also remember that the relay measures its own surroundings. It cannot sense a hot motor in a poorly ventilated room.
Phase Loss and Phase Unbalance Protection
What is phase failure?
Phase failure (also called single-phasing) happens when one of the three supply phases is lost, for example when one fuse blows or a terminal burns out. The motor may keep running on two phases, and the current in those two rises. It may also hum and fail to start.
How the differential trip mechanism works
In a normal overload all three strips bend by the same amount. With a lost phase, one strip stays cool while the other two bend. The differential mechanism turns that unequal movement into an earlier trip.
Phase loss vs phase unbalance
Phase loss means one phase carries no current. Phase unbalance means the three currents are unequal, for example because of a supply fault, a loose connection or uneven single-phase loads upstream.
Limitations of phase failure protection
Phase-failure sensitivity is a design feature, not something every thermal relay has. Its response is slower and less precise than an electronic relay. WEG, for example, quotes phase-loss protection in under 5 seconds and unbalance protection above 40% for its electronic range. For critical motors, a dedicated phase-failure relay may be a better choice.
Thermal Overload Relay Reset and Test Functions
| Reset mode | How it works | Main risk | Use when |
|---|---|---|---|
| Manual | A person presses reset after the relay cools | Slower return to service | Most cases. It forces someone to find the cause |
| Automatic | The relay resets itself once the strip cools | The motor can restart without warning if a start signal is still present | Only where an unexpected restart is safe |
| Remote | Reset by an electrical signal | Needs a safe control scheme | Remote or unattended sites with safeguards |
Manufacturers warn that automatic reset can cause unintended equipment operation, with a risk of serious injury or damage. Use it with care.
What is the test button?
The test (or stop) button lets a competent person check that the relay’s contact and trip mechanism operate. Use it only as the manual describes, and with the circuit made safe.
Why does a relay need cooling time before resetting?
The strip must cool before the trip mechanism can latch again. This is also protection: it stops anyone restarting a hot motor straight away.
Thermal Overload Relay vs Other Motor Protection Devices
| Comparison factor | Thermal relay | Electronic relay | MPCB | PTC relay |
|---|---|---|---|---|
| Operating principle | Bimetal heating | Electronic sensing | Thermal and magnetic | Winding temperature sensing |
| Overload protection | Yes | Yes | Yes | Winding-temperature based |
| Short-circuit protection | No | No | Yes | No |
| Ambient sensitivity | Depends on compensation | Generally lower | Product dependent | Sensor based |
| Advanced diagnostics | Limited | Available on some models | Model dependent | Model dependent |
Thermal overload relay vs electronic overload relay
An electronic relay measures current with sensors and models the motor’s heating in electronics. It often offers a wide setting range (WEG quotes 5:1 for one range), selectable trip classes and diagnostics. A thermal relay is simpler, rugged and lower in cost. Not every electronic relay suits single-phase or DC loads, so check the datasheet.
Thermal overload relay vs MPCB
An MPCB combines a manual switch, overload protection and short-circuit protection in one unit. A thermal relay does overload only and needs a separate short-circuit device. An MPCB has no remote switching of its own, so add a contactor if you need automatic control. For wider background, see these types of circuit breakers.
Thermal overload relay vs circuit breaker
A standard breaker protects the cable and clears faults. Its characteristic is not made to protect a motor winding through repeated starts. Read the comparison of an MCB, MCCB and ACB to see where each belongs.
Thermal overload relay vs fuse
Fuses clear short circuits well, but they are one-shot devices and give little precise overload protection. If one fuse blows, the motor can keep running on two phases. A relay with phase-failure sensitivity helps cover that.
Thermal overload relay vs contactor
They do different jobs. The contactor switches the motor current. The relay senses an overload and tells the contactor to open.
When should you use a thermistor (PTC) relay?
A PTC relay reads thermistors fitted in the motor windings, so it trips on real winding temperature whatever the current is. It suits motors with poor cooling, high ambient temperature, frequent starts or slow-speed drive operation. It complements a current relay rather than replacing it. It needs a motor with sensors fitted, and it cannot react fast enough to a locked rotor.
| Fault | Thermal relay | Electronic relay | MPCB | PTC relay |
|---|---|---|---|---|
| Locked rotor or stall | Depends on class and start time | Yes, within settings | Yes | Can detect the resulting heat |
| Phase loss | Only if the model has it | Often available | Product specific | Detects the heating, not the phase loss |
| Blocked ventilation, normal current | No | No | No | Yes |
| Ground fault | Not inherently | Some products | Product specific | No |
Single-Phase vs Three-Phase Thermal Overload Relays
| Point | Single-phase motor | Three-phase motor |
|---|---|---|
| Typical UK supply | 230 V | 400 V |
| Relay poles | Some makers offer two-pole versions or a published method for using a three-pole relay | Three poles, one per phase |
| Phase-loss sensitivity | Not relevant | Available on many models |
| Electronic relays | Some are not suitable | Widely available |
| Key check | Follow the maker’s connection method and current range | Check range, class and phase-failure feature |
Always use the manufacturer’s published method for single-phase use. Do not guess how to connect the poles.
Thermal Overload Relay with a VFD and Soft Starter
VFD: a drive normally has its own electronic motor protection, which you set to the motor’s rated current. A thermal relay on a drive output can trip early because the drive’s switching and harmonics add extra heat to the strip. WEG notes that, for one range, the setting may need to be higher than the motor’s rated current. At low speed the motor’s fan also cools less, which a current-based relay cannot see.
Soft starter: many soft starters include electronic overload protection with a selectable class. A separate relay is often used when the soft starter is bypassed after starting, or when it has no overload function.
Separate motor protection is needed when one drive feeds several motors, when a drive can be bypassed to run direct-on-line, or when the drive has no motor protection. Always follow both the drive and relay manufacturers. For help choosing between the two starters, read VFD vs soft starter.
Thermal Overload Relay Tripping Causes and Troubleshooting
This is a diagnostic guide only. Testing and repair must be done by qualified people with the equipment isolated and locked off.
| Problem | Possible cause |
|---|---|
| Trips immediately | Setting too low, wrong relay range, motor or wiring fault, locked rotor |
| Trips during start-up | Trip class too fast for the start, long acceleration, low supply voltage, mechanical binding |
| Trips during normal running | Sustained overload, process restriction, poor cooling or high ambient temperature |
| Trips now and then | Supply imbalance, intermittent overload, loose connections, repeated starts |
| Will not reset | Strip has not cooled, reset set to the wrong mode, mechanical fault |
| Does not trip on overload | Wrong setting or range, protection bypassed, or a failed relay |
What qualified personnel check first
- Nameplate current against the relay setting.
- Mechanical load: jams, bearings, belts and coupling.
- Supply voltage and phase balance.
- Enclosure temperature and ventilation.
- Loose or discoloured terminals.
- Motor winding condition. An insulation resistance test with a megger is one method.
For general approaches to checking protective devices, see relay testing.
What happens when a thermal overload relay fails?
The dangerous failure is silence. If the relay no longer trips, the motor runs unprotected until it burns out. A failed relay may also trip early or refuse to reset, which stops the motor for no reason. Replace a doubtful relay. Never adjust around it or bypass it.
Limitations of Thermal Overload Relays
| Limitation | What to do instead |
|---|---|
| No short-circuit protection | Fit a fuse, MCB, MCCB or MPCB |
| Blocked ventilation at normal current is not detected | Add PTC thermistor protection |
| Ambient temperature affects the trip point | Choose a compensated relay and check the range |
| Needs recovery time after a trip | Allow cooling. Do not force the reset |
| Limited diagnostics | Use an electronic relay if you need data |
| VFD use needs care | Rely on the drive’s motor protection unless both makers approve |
Standards and Certifications for Thermal Overload Relays
| Standard or mark | What it covers | Where it applies |
|---|---|---|
| IEC 60947-4-1:2023 (Edition 5.0, with Corrigendum 1 in March 2026) | Contactors and motor-starters, including overload relays | International |
| BS EN IEC 60947-4-1:2025 | UK adoption, identical to the IEC 2023 edition. BSI lists it as current | UK |
| BS 7671 | UK wiring regulations, including overload protection of motors | UK |
| CE and UKCA marking | Low voltage equipment. The UK government extended recognition of CE marking indefinitely in Great Britain, so either mark can be used | Great Britain |
| UL 508, UL 60947-4-1 and NEMA ICS 2 | North American product and class standards. NEMA classes use trip time at 600% of rating | USA and Canada |
| IS/IEC 60947-4-1 (BIS) | Indian adoption. Check the current BIS certification requirement for your product | India |
An overload relay is set from the motor nameplate, not the NEC table. Our guide to FLA and full load amps explains the difference between full load, running and starting current with a worked example.
Small DC motors need correctly sized cable as well as overload protection. Our 12V wire size calculator checks voltage drop, cable length and starting current.
HVAC and chiller nameplates use their own current ratings. Our guide to MCA meaning in electrical explains MCA, MOP, RLA and FLA with worked examples.
Setting an overload starts with the right motor current. Our NEC motor FLA table lists values up to 500 HP and shows how to handle larger motors.
Long motor runs need a voltage drop check as well as overload protection. See our guide to the NEC voltage drop code vs CEC Rule 8-102, with a motor feeder calculator.
Thermal overloads protect the motor, not the conveyor. For jam protection, see our guide to the mechanical overload switch and how to wire it fail-safe.
Frequently Asked Questions About Thermal Overload Relays
What is a thermal overload relay used for?
It protects an electric motor from sustained overload. If the motor draws too much current for too long, the relay trips and the contactor switches the motor off, which prevents overheating and winding damage.
How does a thermal overload relay work?
Motor current heats a bimetallic strip. Two bonded metals expand by different amounts, so the strip bends. After enough heat it moves a trip mechanism, which opens the 95–96 contact in the contactor coil circuit and stops the motor.
What is the working principle of a thermal overload relay?
It relies on the heating effect of electric current and the different thermal expansion of two metals. More current means more heat, a faster bend and a quicker trip, which gives the relay its inverse-time behaviour.
Does a thermal overload relay protect against short circuits?
No. A short circuit is a far larger current than an overload, and starters are not normally designed to interrupt it. You need a fuse, MCB, MCCB or MPCB upstream, matched to the manufacturer’s coordination table.
What are the main parts of a thermal overload relay?
Bimetallic strips, heater elements, a trip mechanism, a current setting dial, reset and test buttons, auxiliary contacts and, on many models, a differential mechanism for phase-loss sensitivity.
What do terminals 95, 96, 97 and 98 mean?
Terminals 95–96 are the normally closed contact, wired in series with the contactor coil so it opens on a trip. Terminals 97–98 are the normally open contact, which closes on a trip and is often used for an alarm. Always check the diagram on your relay.
What is the difference between Class 10 and Class 20?
Both are measured at 7.2 times setting current from cold. A Class 10 relay trips within 4–10 seconds. A Class 20 relay takes 6–20 seconds, so it suits motors that need longer to start.
How do you calculate thermal overload relay settings?
Start from the motor nameplate full load current in amps and set the dial to that value on a standard IEC relay. Then follow the manual for service factor, starter type and ambient temperature. There is no single formula for every case.
How do you select the correct overload relay?
Match the motor’s full load current to the relay’s range, pick a trip class that suits the starting time, then check contactor fit, ambient temperature, reset mode, auxiliary contacts and upstream short-circuit protection.
Why does a thermal overload relay keep tripping?
Common causes are a real overload, a setting that is too low, a trip class that is too fast for the start, supply imbalance or phase loss, high ambient temperature, repeated starts and loose connections. Find the cause before changing the setting.
What is the difference between manual and automatic reset?
Manual reset needs a person to press reset after the relay cools, so someone checks the fault. Automatic reset restores the relay by itself, which can restart the motor unexpectedly, so use it only where that is safe.
Can a thermal overload relay protect a single-phase motor?
Yes, if the relay is approved for it. Some relays are made for two-pole use and others publish a connection method for single-phase motors. Check the datasheet, because some electronic relays are not suitable for single-phase loads.
Can you use a thermal overload relay with a VFD?
Usually the drive’s own electronic motor protection does this job. A thermal relay on a drive output can trip early because of harmonic heating, so use one only if both the drive and relay manufacturers allow it.
What happens if an overload relay fails?
If it fails to trip, the motor has no overload protection, often unnoticed until the motor burns out. If it fails to reset or trips early, the motor stops unnecessarily. Replace a doubtful relay rather than adjusting around it.
How long does a thermal overload relay take to reset?
It depends on the model and how hot the strip became. Often it takes a few minutes for the bimetal to cool. Manufacturers publish recovery times, so check the datasheet rather than forcing the reset.
Conclusion
A thermal overload relay protects a motor from sustained overload by turning heat into a trip signal for the contactor. Choose the trip class to match the starting time, set the dial from the nameplate current and the manual, and make sure the contactor and relay are a matched pair. Remember that it never replaces short-circuit protection: a fuse, MCB or MPCB must sit upstream.
Safety reminder: isolate and lock off before any work, follow the manufacturer’s manual and BS 7671, and leave testing, setting and repair to competent people. Never bypass an overload relay.
Sources and further reading
- IEC 60947-4-1:2023, scope and edition and Corrigendum 1:2026
- BSI: BS EN IEC 60947-4-1:2025
- ABB: thermal overload relays technical document (trip classes, test points, coordination)
- WEG: thermal and electronic overload relays catalogue (ambient, phase loss, VFD)
- Schneider Electric: TeSys Giga thermal overload protection (cold and hot state, reset warning)