Motor Feeder Voltage Drop: NEC vs CEC Code Rules and Calculations

By editor 7 min read
Long motor feeder from a panel to a motor with a voltmeter showing the voltage falling, labelled NEC 3 and 5 percent and CEC Rule 8-102

The NEC does not generally make voltage drop mandatory. Informational notes in 210.19(A) and 215.2(A) suggest no more than 3% on a feeder or branch circuit and 5% in total, but they are explanatory only. The Canadian Electrical Code is different: Rule 8-102 sets mandatory voltage drop limits. For motor feeders, check running drop against these figures and the motor’s voltage tolerance, then check the larger drop during starting.

Code edition: Code-based content. NEC informational note numbers have changed between editions, and CEC limits and provincial amendments vary. Confirm the edition adopted where you work and have the design reviewed by a qualified person.
PointNEC (US)CEC (Canada)
Status of the limitInformational notes, not enforceable (90.5(C))Mandatory, Rule 8-102
Typical figures3% feeder or branch, 5% total (suggested)Set in Rule 8-102 of the adopted edition
Load usedCalculated loadConnected load, or 80% of the protective device rating (per Ontario ESA)
Where it is mandatorye.g. 647.4(D), 695.7, and maker instructions via 110.3(B)All installations within the rule’s scope
From IAEI Magazine, PacifiCorp Engineering Handbook 1C.2.1 and Ontario ESA Bulletin 8-6-5 (May 2025).
3%
NEC suggestion for a feeder or branch
5%
NEC suggestion in total
12.9
K for copper at 75°C (IAEI)
±10%
motor voltage tolerance (DOE)

What the NEC Says

NEC suggested voltage drop percentagesFrom the service panel, a feeder runs to an MCC or sub-panel and a branch circuit runs to the motor. The NEC informational notes suggest up to 3 percent on each and 5 percent in total.Where the NEC’s suggested percentages applyServicepanelFeederMCC orsub-panelBranch circuitMotorup to 3% suggestedup to 3%Feeder + branch: 5% total suggestedIndustrialBasicsindustrialbasics.com
Figure 1: Suggestions only in the NEC. Your engineer or the equipment maker may set a tighter limit.

IAEI explains that voltage drop is “only mentioned in some sections of the NEC as informational notes, and is required to be calculated in other sections”. It lists 210.19(A), 215.2(A)(1), 310.15(A)(1), 647.4(D), 310.60(B), 455.6(A) and 695.7, and says permitted or required amounts “may range from 1.5 to 15 percent”, with 5% maximum generally suggested on a circuit.

The key point is 90.5(C): informational notes are explanatory material, not requirements. An inspector cannot fail an installation solely for exceeding the 3% or 5% suggestion. But IAEI stresses a second rule that does apply. Section 110.3(B) requires listed equipment to be installed according to its instructions, and those instructions often set a minimum operating voltage. Its example is a 240 V luminaire that needs at least 228 V, which is exactly a 5% drop.

What the CEC Says

NEC and CEC voltage drop comparedIn the NEC, voltage drop percentages are informational notes, with 3 percent suggested for a feeder or branch circuit and 5 percent in total. In the CEC, Rule 8-102 sets mandatory limits, calculated on the connected load or 80 percent of the protective device rating.NEC vs CEC: how voltage drop is treatedNEC (United States)Informational notes, not mandatory3% suggested for a feeder or branch5% suggested in total to the outletMandatory in a few articlesManufacturer limits via 110.3(B)CEC (Canada)Rule 8-102: mandatory limitsRead the limits in youradopted edition and provinceCalculated on connected load or80% of the protective device rating** As described in Ontario ESA Bulletin 8-6-5 for the Ontario Electrical Safety Code.IndustrialBasicsindustrialbasics.com
Figure 2: Summary from IAEI Magazine, the PacifiCorp handbook and the Ontario ESA bulletin.

In Canada, Rule 8-102 of the Canadian Electrical Code, Part I, is a mandatory rule. Ontario’s Electrical Safety Authority describes Rule 8-102 of the Ontario code as setting “the maximum voltage drop limits on all types of electrical installations including residential”. Its May 2025 bulletin also says Subrule 8-102 1) was amended to base the calculation on the connected load, if known, or 80% of the rating of the overcurrent device.

Provinces adopt the CEC with their own amendments. Manitoba’s Regulation 30/2026 adopts the 26th edition (CSA C22.1:24) and amends Subrule 8-102 1) to apply to “the branch circuit” rather than “the feeder or branch circuit”. That shows why you must read the rule in the edition and province that apply to your job. This guide does not quote the CEC percentages because we could not verify them from a readable copy of the code.

Why Motor Feeders Need Extra Care

The DOE’s motor tip sheet says motors are designed to operate within ±10% of nameplate voltage, and that reduced voltage lowers torque by the square of the voltage ratio. It also notes that low voltage caused by high system impedance is worse during starting, when current is four to eight times the full-load value. A feeder that drops 3% while running can drop well over 10% while a large motor starts.

Estimate starting current from the nameplate code letter with our locked rotor amps calculator, and running current from the NEC motor FLA table. Reduced voltage starting, covered in our FVNR and DOL guide, is one way to cut the starting dip.

The Calculation

IAEI uses the K-factor method, based on DC resistance from NEC Chapter 9, Table 8 at 75°C. K is 12.9 for copper and 21.2 for aluminum.

Single phase: VD = 2 × K × I × L ÷ CM
Three phase: VD = 1.732 × K × I × L ÷ CM

L is the one-way length in feet, I is the current, and CM is the conductor area in circular mils. Percent drop is VD ÷ system voltage × 100. IAEI notes that Table 8 DC values are close to the AC values in Table 9 for these purposes. For large conductors or low power factor loads, an AC impedance method is more accurate.

Voltage Drop Calculator

Motor Feeder Voltage Drop Calculator (three-phase)
IndustrialBasics estimate using the IAEI K-factor method (DC resistance at 75°C). Large conductors and low power factor loads can drop more on AC. Ampacity must be checked separately.

Worked Example: 50 HP Motor Feeder

ItemValue
System480 V, three phase
Running current65 A (example)
Starting current390 A, about 6 times running (example)
Length400 ft one way, copper
4 AWG (41,740 cmil) running drop1.732 × 12.9 × 65 × 400 ÷ 41,740 = 13.9 V (2.90%)
4 AWG starting drop83.5 V (17.4%)
2 AWG (66,360 cmil) running drop8.8 V (1.82%)
Illustrative values. Size for ampacity first, then check voltage drop. Starting drop here is the feeder share only.

On 4 AWG the running drop of 2.9% sits just inside the NEC’s 3% suggestion for a feeder, but it leaves only about 2% for the branch circuit within the 5% total, and the starting drop of 17.4% is large before the branch circuit and supply add their share. Going up to 2 AWG brings running drop to 1.8% and starting drop to 10.9%. Remember that increasing the phase conductors for voltage drop also affects the equipment grounding conductor size, which must be increased in proportion.

For the basics of current and power in three-phase systems, see 3 phase calculations.

Frequently Asked Questions

Is voltage drop a code requirement in the NEC?

Generally no. IAEI explains that the 3% and 5% figures are informational notes, which are explanatory and not mandatory under 90.5(C). A few articles do require it, such as 647.4(D) and 695.7.

The informational notes suggest no more than 3% on a feeder or branch circuit and no more than 5% in total from the service to the farthest outlet.

Is voltage drop mandatory in the Canadian Electrical Code?

Yes. Rule 8-102 sets maximum voltage drop limits. Ontario’s ESA describes it as setting “the maximum voltage drop limits on all types of electrical installations”. Read the limits in your adopted edition.

What current is used for CEC voltage drop?

Ontario’s ESA bulletin says the calculation is based on the connected load if known, or 80% of the rating of the overcurrent device protecting the circuit.

Can a manufacturer make voltage drop mandatory in the US?

In effect, yes. NEC 110.3(B) requires listed equipment to be installed per its instructions, and IAEI notes these often set a minimum operating voltage.

How do I calculate voltage drop on a 3-phase motor feeder?

IAEI gives VD = 1.732 × K × I × L ÷ CM, where K is 12.9 for copper or 21.2 for aluminum, L is the one-way length in feet and CM is the conductor area in circular mils.

Why does voltage drop matter more for motors?

Motors draw several times running current while starting, so the drop is much larger then. The DOE notes reduced voltage cuts torque by the square of the voltage ratio.

What voltage should a motor see?

The DOE says motors are designed to operate within ±10% of nameplate voltage. Feeder and branch drop eat into that margin.

Sources and Further Reading

About the author

editor

Leave a Comment