Locked Rotor Amps: NEMA Code Letters and Motor Sizing Calculator

By editor 6 min read
Motor nameplate with code letter G highlighted, feeding a calculation that ends in a locked rotor amps reading on a meter

Locked rotor amps (LRA) are the current a motor draws at rated voltage before the rotor starts turning. To estimate it, take the kVA/hp band for the nameplate code letter from NEC Table 430.7(B), multiply by horsepower, and divide by 1.732 × voltage. A 30 hp, 460 V, Code G motor draws about 211 to 237 A at the moment of a full-voltage start.

LRA = (kVA/hp × hp × 1000) ÷ (1.732 × V)

Locked Rotor Amps Calculator

Locked Rotor Amps Calculator (three-phase)
IndustrialBasics estimate from NEC Table 430.7(B) code letter bands. The motor maker’s data sheet value takes priority.

The calculator covers three-phase motors. Where the motor’s data sheet gives a locked rotor current, use that figure. The code letter only tells you the band it falls in.

How to calculate locked rotor amps from the code letterRead the code letter, look up the kVA per horsepower band, multiply by horsepower, then divide by 1.732 times the line voltage. A 30 hp, 460 V, Code G motor gives 211 to 237 A.From nameplate code letter to locked rotor amps1. Read code lettere.g. Code G2. Look up kVA/hpG = 5.6 to 6.293. Multiply by hp× 30 hp = 168 to 188.7 kVA4. Divide by √3 × V÷ (1.732 × 460 V)Result: 211 A to 237 Alocked rotor current at 460 VIndustrialBasicsindustrialbasics.com
Figure 1: The 30 hp, 460 V, Code G example worked step by step.

NEC Table 430.7(B) Code Letters

The code letter on the nameplate is the locked rotor indicating code. Each letter covers a range of locked rotor kilovolt-amperes per horsepower. The right-hand column shows what each band means for a 10 hp, 460 V motor.

Code letterkVA per hp (locked rotor)LRA for 10 hp at 460 V
A0.00 to 3.140 to 39 A
B3.15 to 3.5440 to 44 A
C3.55 to 3.9945 to 50 A
D4.00 to 4.4950 to 56 A
E4.50 to 4.9956 to 63 A
F5.00 to 5.5963 to 70 A
G5.60 to 6.2970 to 79 A
H6.30 to 7.0979 to 89 A
J7.10 to 7.9989 to 100 A
K8.00 to 8.99100 to 113 A
L9.00 to 9.99113 to 125 A
M10.00 to 11.19126 to 140 A
N11.20 to 12.49141 to 157 A
P12.50 to 13.99157 to 176 A
R14.00 to 15.99176 to 201 A
S16.00 to 17.99201 to 226 A
T18.00 to 19.99226 to 251 A
U20.00 to 22.39251 to 281 A
V22.4 and up281 A and up
A to P from NEC Table 430.7(B) as reproduced in the 2020 NEC training slides of the Electrical Association of Minnesota. R to V from Engineering ToolBox and SIU, which agree.
Watch out: Some copies of this table online list an “I” band and shift every letter after it. NEMA skips I and O. If a table shows an I, do not use it.

Engineering ToolBox notes that small motors generally need more starting kVA per hp than large ones. Its typical values for standard three-phase motors run from Code L below 1 hp down to Code G above 15 hp. Always read the actual nameplate.

Code Letter vs NEMA Design Letter

These are two different markings, and mixing them up is the most common mistake. The DOE motor tip sheet states that the locked rotor code “is not the same as the motor design letter code”.

NEMA designCharacteristicTypical use
Design AHigh pullout torque; no locked rotor current limit (DOE)Specialist uses, such as injection molding
Design BReasonable starting torque, moderate starting currentStandard industrial duty
Design CHigh starting torqueHard-to-start loads
Design DHigh torque, poor full load efficiencyPunch presses, hoists, elevators
From the Electrical Association of Minnesota 2020 NEC slides and the DOE tip sheet.

DOE notes that many premium efficiency Design A motors meet Design B torque requirements but exceed Design B locked rotor current limits. That matters when a replacement motor starts tripping a breaker that never tripped before.

Locked Rotor Current vs Peak Inrush

Peak inrush, locked rotor current and full load currentCurrent spikes to a peak inrush in the first half cycle, settles at the locked rotor current during acceleration, then falls to full load current as the motor nears speed.Starting current over time (illustrative shape)TimeCurrentFull load currentLocked rotor current (RMS)Peak inrush, first half cycleStays near LRC while acceleratingIndustrialBasicsindustrialbasics.com
Figure 2: Not to scale. DOE notes peak inrush can reach 2.8 times the RMS locked rotor current.

NEMA recognises two parts of starting current, according to DOE. Peak inrush is a transient within half a cycle of contact closure. Locked rotor current is the RMS current that follows and stays near that value during acceleration. DOE says peak inrush can reach 2.8 times the RMS locked rotor current, and it can trip instantaneous magnetic-only circuit protectors even when the LRA itself is within limits.

Worked Examples

30 hp, 460 V, Code G

StepValue
kVA/hp band5.6 to 6.29
Locked rotor kVA5.6 × 30 = 168 to 6.29 × 30 = 188.7 kVA
Divide by 1.732 × 460210.9 A to 236.8 A
Matches the maximum of 236.8 A in the Electrical Association of Minnesota slides.

100 hp, 460 V, Code C

Code C is 3.55 to 3.99 kVA/hp. The maximum is 3.99 × 100 × 1000 ÷ (1.732 × 460) = 501 A. The DOE tip sheet works the same motor with a rounded 4.0 kVA/hp and gets 502 A.

What LRA Is Used For

Code note: NEC 430 also contains tables of locked rotor current used for selecting disconnects and controllers. Use the edition your jurisdiction has adopted, and the manufacturer’s data where it exists.

For an overview of starting methods, see types of motor starters and VFD vs soft starter.

Frequently Asked Questions

What are locked rotor amps?

Locked rotor amps (LRA) are the current a motor draws from the supply when energized at rated voltage with the rotor not turning. It is the current at the instant of a full-voltage start.

How do you calculate locked rotor amps?

Multiply the code letter’s kVA per hp by the horsepower and by 1,000, then divide by 1.732 times the line voltage for a three-phase motor.

What does the code letter on a motor nameplate mean?

It is the locked rotor indicating code from NEC Table 430.7(B). Each letter covers a band of locked rotor kVA per horsepower. Letters I and O are not used.

Is the code letter the same as the NEMA design letter?

No. The DOE tip sheet stresses that the locked rotor code is not the design letter. Design (A, B, C, D) describes the torque and current characteristics.

What is the locked rotor current of a 30 hp, 460 V Code G motor?

About 211 A to 237 A, using 5.6 to 6.29 kVA/hp.

Why do premium efficiency motors draw more starting current?

DOE says they have slightly higher locked rotor current and code letters. Most are still Design B and must meet the same maximum allowable locked rotor current.

Is peak inrush the same as locked rotor current?

No. Peak inrush is a transient in the first half cycle. DOE says it can be as high as 2.8 times the RMS locked rotor current, and no standard limits it.

Do IEC motors have code letters?

No. The DOE tip sheet notes IEC or metric motors do not use NEMA-defined code letters. Use the manufacturer’s locked rotor current ratio instead.

Sources and Further Reading

About the author

editor

Leave a Comment