Quick answer: what are the types of motor starters?
A motor starter connects a motor to the supply, limits the high current it draws at start-up, and protects it from overload. The main types are:
- Full-voltage: direct-on-line (DOL) starter, also called across-the-line, and the reversing DOL starter.
- Reduced-voltage: star-delta, autotransformer, primary resistance or reactance, and part-winding starters.
- Electronic: soft starter and variable frequency drive (VFD).
- Slip-ring (wound-rotor) motors: rotor resistance starter.
The right one depends on the motor size, the load and how much starting current your supply can take.
Every induction motor takes a large surge of current for a few seconds when it starts. A motor starter manages that surge so the motor, the supply and the machine it drives are not damaged. This guide explains each type in plain language, shows how they compare, and helps you choose the right one. It focuses on three-phase squirrel-cage induction motors, which are the most common in industry, and covers other motor types briefly.
What Is a Motor Starter?
A motor starter is a switching assembly that safely starts, runs and stops an electric motor. Most starters also include overload protection, and many include undervoltage and phase-failure protection. In the IEC system, electromechanical starters are covered by IEC 60947-4-1 and electronic ones by IEC 60947-4-2.
A few terms are often mixed up:
- Contactor: an electrically operated switch that makes and breaks the motor circuit. On its own it gives no overload protection.
- Magnetic starter: a contactor plus an overload relay. This is the usual meaning of “starter” in most workshops.
- Motor controller: a broader term that also covers electronic devices such as soft starters and drives.
Why Do Electric Motors Need a Starter?
When an induction motor is at standstill, it behaves much like a transformer with a shorted secondary. If you apply full voltage, it draws its locked-rotor current. This is commonly around 6 to 8 times the full-load current, though the exact figure depends on the motor design. Starters exist to deal with three problems this causes.
- Supply voltage dip: the heavy current pulls the supply voltage down, which can make lights flicker, trip other equipment or breach the utility’s limits. A weak supply, such as a long feeder or a small substation transformer, makes this worse.
- Mechanical shock: a sudden torque jump stresses shafts, couplings, belts and gearboxes.
- Heating: repeated high-current starts overheat the motor windings.
How Voltage Affects Starting Current and Torque
Most reduced-voltage starters work on one simple rule. If you lower the voltage at the motor terminals:
- Starting current falls roughly in proportion to the voltage: Istart ∝ V
- Starting torque falls with the square of the voltage: Tstart ∝ V²
This is why reducing the voltage also reduces the pulling power of the motor. At 50% voltage you get about half the current but only a quarter of the torque. The chart below shows the pattern.
Motors matter at a large scale too. The US Department of Energy estimates that motor-driven systems use over 70% of the electricity in many industrial plants, so how motors are started and controlled has a real effect on plant demand.
Classification of Motor Starters
Starters are grouped by the voltage they apply during starting and by how they control it. The diagram shows the full picture.
Full-Voltage Starters
Direct-On-Line (DOL) Starter
A DOL starter connects the motor straight to the full supply voltage. It is the simplest, cheapest and most common starter. In North America the same method is called an across-the-line starter, so the two names mean the same thing.
How a DOL starter works
- You press the START button. Current flows through the contactor coil.
- The contactor closes and connects all three phases to the motor.
- An auxiliary contact on the contactor closes in parallel with the START button. This “hold-in” contact keeps the coil energised after you release the button.
- Pressing STOP, or an overload trip, breaks the coil circuit and the contactor opens.
| Advantages | Disadvantages |
|---|---|
| Lowest cost and simplest wiring | Highest starting current |
| Highest starting torque for that motor | Can cause a supply voltage dip |
| Easy to maintain and fault-find | Sudden torque can shock the drive train |
| Compact and reliable | No speed control |
Where it is used: small pumps, compressors, fans and conveyors, where the supply is strong enough to take the starting current. There is no universal kW limit for DOL starting. The limit depends on your supply capacity and the utility’s rules, so always check locally.
Reversing DOL (Forward-Reverse) Starter
A reversing starter uses two contactors, one for forward and one for reverse. The reverse contactor swaps two of the three supply phases, which makes the motor turn the other way. The two contactors must never close together, as that would short two phases. To prevent this, the starter uses electrical interlocking (normally-closed auxiliary contacts) and often mechanical interlocking as well. It suits hoists, gates, lifts, machine tools and conveyors.
Reduced-Voltage Starters
These starters feed the motor with less than full voltage during the first few seconds, then switch to full voltage. They cut the starting current but, because of the V² rule, they also cut the starting torque. They only work well when the load is easy to accelerate.
Star-Delta (Wye-Delta) Starter
A star-delta starter starts the motor with its windings connected in star, then reconnects them in delta once the motor has speeded up. In star, each winding receives only 1/√3 (about 58%) of the line voltage. This cuts the line current to about one-third of the DOL value. The torque also drops to about one-third.
Motor requirements: the motor must be designed to run in delta at the supply voltage (for example 415 V delta), and all six winding terminals must be brought out to the terminal box.
How star-delta starting works
| Advantages | Disadvantages |
|---|---|
| Starting current cut to about one-third | Starting torque also cut to about one-third |
| Cheaper than an autotransformer starter or soft starter at medium sizes | Needs a six-terminal, delta-rated motor |
| Simple and proven | Open-transition changeover causes a current spike |
| No harmonics | Not suitable for hard-to-start loads |
Where it is used: centrifugal fans, centrifugal pumps, light conveyors and other loads that need little torque at start-up.
Open-Transition vs Closed-Transition Star-Delta
The moment of changeover from star to delta matters. During a standard (open-transition) changeover, the motor is disconnected from the supply for a fraction of a second. When it reconnects in delta, its residual voltage may be out of phase with the supply, which causes a short current and torque spike. On a high-inertia load this can stress gearboxes and trip upstream protection.
| Feature | Open transition | Closed transition |
|---|---|---|
| Motor during changeover | Briefly disconnected | Stays connected through resistors |
| Changeover spike | Can be significant | Much smaller |
| Parts needed | Three contactors and a timer | Extra contactor and transition resistors |
| Cost | Lower | Higher |
| Best for | Low-inertia loads, strong supplies | High-inertia loads, sensitive supplies |
Autotransformer Starter
An autotransformer starter feeds the motor through an autotransformer with voltage taps, commonly 50%, 65% and 80%. After the motor has accelerated, the transformer is bypassed and the motor runs on full voltage. In North America, this is also called a compensator starter.
With a tap of k (for example 0.65):
- Motor current = k × DOL current
- Supply (line) current = k² × DOL current, because the transformer also steps current up on the motor side
- Starting torque = k² × DOL torque
The lower line current for the same torque is the main advantage over star-delta and resistance starters. The disadvantages are higher cost and larger size. It suits large motors with high-inertia loads such as big compressors, crushers and fans.
Korndorfer Starter
A Korndorfer starter is a closed-transition autotransformer arrangement. When it switches from the reduced tap to full voltage, part of the transformer winding stays in series with the motor for a moment. The motor is never disconnected, so the changeover spike is avoided. It costs more than a simple open-transition autotransformer starter and is used where a smooth changeover matters, usually on large motors.
Primary Resistance and Primary Reactance Starters
These starters put resistors (or reactors) in series with the stator winding. The voltage drop across them lowers the voltage at the motor. As the motor speeds up, it draws less current, so the voltage drop falls and the motor voltage rises on its own. At the end, the resistors or reactors are shorted out.
- Resistance type: gives a smooth, step-free start but wastes energy as heat in the resistors.
- Reactance type: wastes less energy as heat but is bulkier and gives a lower power factor during start.
- Use today: uncommon. You will mostly meet them on older installations or special applications.
Part-Winding Starter
A part-winding starter works with a special motor that has two identical parallel windings. At start, only the first winding is connected, which gives lower current and torque. After a short delay, the second winding is added and the motor runs on both. It is simple and cheap, but the reduction in current is fixed by the winding design and the motor must be built for this method, so it is a niche choice.
Electronic Motor Starters
Soft Starter
A soft starter uses pairs of back-to-back thyristors (SCRs) in each phase to raise the motor voltage smoothly from a low value to full voltage. This is called phase-angle control. You can usually set the ramp time and a current limit, and many models also provide a soft stop. IEC 60947-4-2 covers these devices.
| Advantages | Disadvantages |
|---|---|
| Smooth, shock-free acceleration | No continuous speed control |
| Adjustable ramp time and current limit | Costs more than DOL or star-delta |
| Soft stop reduces water hammer in pumps | Can produce harmonics and heat during starting |
| No changeover spike | Torque is reduced during the ramp |
Where it is used: centrifugal pumps, fans, conveyors and compressors, particularly where mechanical shock or supply dip must be reduced. Power electronics are sensitive to voltage spikes, so many installers add surge protection devices upstream.
Variable Frequency Drive (VFD) as a Starter
A VFD converts the supply to DC and then creates a new AC output with adjustable voltage and frequency. It starts the motor at low frequency and raises it gradually. This allows high torque at low speed with low starting current, and speed control while running.
- Advantages: lowest starting current, controlled torque, full speed control, soft stop, and energy savings on variable-torque loads such as fans and pumps.
- Disadvantages: highest cost, harmonics, extra cable and EMC (interference) requirements, and more complex commissioning.
- Where it is used: variable-flow pumps and fans, conveyors, cranes, mixers and any process that needs speed control.
Soft Starter vs VFD vs Star-Delta
| Feature | Star-delta | Soft starter | VFD |
|---|---|---|---|
| How it works | Changes winding connection | Ramps voltage with thyristors | Changes voltage and frequency |
| Starting current | About 33% of DOL | Adjustable (for example 3 × full-load current) | Adjustable, can be close to full-load current |
| Starting torque | About 33% of DOL | Reduced, set by ramp | Can be high, controllable |
| Speed control | No | No | Yes |
| Changeover spike | Yes (open transition) | No | No |
| Relative cost | Low to moderate | Moderate to high | Highest |
| Best for | Light-start fans and pumps | Smooth start and stop of pumps and conveyors | Variable-speed processes |
In short: use a soft starter if you only need a gentle start and stop, and a VFD if you also need to change the motor speed.
Slip-Ring (Rotor Resistance) Motor Starters
A slip-ring (wound-rotor) induction motor has a rotor winding connected to slip rings, so you can add external resistance to the rotor circuit. This is not possible with a squirrel-cage motor.
- All the external resistance is connected in the rotor circuit at start.
- The extra resistance raises the starting torque and keeps the starting current low.
- As the motor speeds up, the resistance is cut out in steps by contactors (or a rheostat).
- At full speed, the slip rings are shorted and the resistance is fully removed.
This gives the best starting torque for the lowest current of any conventional method. The cost is extra maintenance, because the brushes and slip rings wear, plus the size and heat of the resistors. It suits cranes, hoists, crushers, mills and other heavy-duty loads. Many new installations now use a squirrel-cage motor with a VFD instead.
Starting Other Types of Motors
| Motor type | How it is started |
|---|---|
| Single-phase induction | It has no rotating field at standstill, so it needs a starting aid: a second winding (split-phase) or a capacitor in series with it (capacitor-start). A centrifugal switch or electronic relay removes the starting winding near full speed. Capacitor-run and permanent-split-capacitor motors keep the capacitor connected while running. |
| Synchronous | Usually started as an induction motor using damper (amortisseur) windings. DC excitation is applied near full speed, and the motor locks into synchronism with the supply. |
| DC | At standstill there is no back-EMF, so current would be very high. A series resistance, or a controlled DC supply, limits the current while the motor speeds up. |
Main Components of a Motor Starter and Protection
| Component | What it does | What it does not do |
|---|---|---|
| Contactor | Switches the motor current on and off | Protect against overload or short circuit |
| Overload relay (thermal or electronic) | Trips on sustained overcurrent | Clear a short circuit |
| Fuse or circuit breaker | Clears short circuits | Give accurate overload protection |
| MPCB | Combines short-circuit and overload protection in one device | Remove the need to check coordination |
| Timer | Sets the star-delta or part-winding changeover time | Protect the motor |
| Phase-failure or undervoltage relay | Detects lost phases or low voltage | Limit starting current |
The most common mix-up is between overload and short-circuit protection. An overload relay reacts slowly to a modest, sustained overcurrent. A short circuit needs a fast device, so this is the job of a fuse or breaker. If you are unsure which to use, read our guide on fuse vs circuit breaker.
An MPCB is similar to an MCB but has an adjustable thermal setting and a magnetic trip tuned to motor starting current. A standard MCB can trip on the start-up surge. For the wider breaker family, see MCB vs MCCB vs ACB and the overview of types of circuit breakers. For larger motors, a dedicated motor protection relay adds functions such as phase unbalance, stall and earth-fault protection. These devices need periodic relay testing to make sure they trip when needed.
Contactor Utilisation Categories: AC-3 and AC-4
- AC-3: starting squirrel-cage motors and switching them off while running. This covers most normal duty.
- AC-4: starting, plugging (reversing while running) and inching. It is a much tougher duty because the contactor breaks high current, so a contactor used for AC-4 must be rated higher or derated.
Overload Relay Trip Classes
The trip class tells you how quickly an overload relay trips under a heavy overload. The class number is the maximum time, in seconds, for a relay to trip from cold at 7.2 times its setting current. Class 10 is the standard choice for normal starts. Class 20 or 30 gives the motor longer to accelerate high-inertia loads such as large fans or centrifuges, without nuisance trips. Always check the exact trip-time limits in the current edition of IEC 60947-4-1 or the relay datasheet.
Type 1 vs Type 2 Coordination
Coordination describes how the starter and its short-circuit protective device behave together during a short circuit. IEC 60947-4-1 defines two types:
| Type | After a short circuit | When to choose it |
|---|---|---|
| Type 1 | The starter may be damaged and may need repair or replacement. There must be no danger to people. | Where downtime is acceptable and cost is the priority |
| Type 2 | The starter is still fit for use. Only light contact welding is allowed, and it must be easy to separate. | Where quick restart and continuity of production matter |
Coordination only holds if you use the exact combination of devices the manufacturer has tested. For the bigger picture, read our guide to protection coordination.
In most plants, starters are grouped in motor control centres or panels. See types of switchgear panels and what is switchgear for how they are housed.
Comparison of Motor Starters
The figures below are typical values for a standard squirrel-cage motor on a stiff supply. Actual values depend on the motor design, the load and the starter settings.
| Starter | Starting current | Starting torque | Speed control | Cost and complexity | Typical use |
|---|---|---|---|---|---|
| DOL | Highest (about 100% of DOL) | Highest (100%) | No | Lowest | Small pumps, fans, compressors |
| Star-delta | About 33% | About 33% | No | Low to moderate | Fans and pumps with light starting load |
| Autotransformer | Line current = tap² (42% at 65% tap) | Tap² (42% at 65% tap) | No | High | Large, high-inertia loads |
| Primary resistance or reactance | Reduced | Reduced (about V²) | No | Moderate | Older plant, special cases |
| Part-winding | Reduced (fixed) | Reduced (fixed) | No | Low to moderate | Part-winding motors only |
| Soft starter | Adjustable | Adjustable by ramp | No continuous control | Moderate to high | Pumps, conveyors, compressors |
| VFD | Adjustable, can be near full-load current | Controlled, can be high | Yes | Highest | Variable-speed processes |
| Slip-ring rotor resistance | Low | High | Limited (stepped) | High, plus brush maintenance | Cranes, hoists, crushers, mills |
How to Choose the Right Motor Starter
Work through these questions in order:
- What is the motor? Check its rating, voltage, full-load current, and whether it has six terminals (needed for star-delta). Slip-ring motors need a rotor starter.
- What does the load need to start? Fans and centrifugal pumps need little torque at standstill. Conveyors, crushers and loaded compressors need much more. Check that the starter’s reduced torque is still above the load torque, or the motor will not accelerate.
- How strong is the supply? A weak supply allows only a small voltage dip, which pushes you towards a reduced-voltage or electronic starter. Follow the local utility’s rules.
- Do you need speed control? If yes, use a VFD. No other starter on this page controls speed while running.
- How often does it start, and does it reverse? Frequent starts need correctly sized contactors and overload settings. Reversing needs a reversing starter or a drive.
- What are the cost and maintenance limits? Compare purchase cost, space, and long-term upkeep.
- Which standards apply? Check the relevant IEC or IS standard, your local wiring rules and the manufacturer’s data.
| Application | Starter to consider | Main reason |
|---|---|---|
| Small pumps | DOL | Simple and cheap |
| Centrifugal pumps | Soft starter or VFD | Controlled acceleration, less water hammer |
| Industrial fans | Star-delta or VFD | Light starting torque, or speed control |
| Conveyors | Soft starter or VFD | Smooth start protects the belt and load |
| Cranes and hoists | VFD or rotor resistance | High starting torque and control |
| Heavy crushers and mills | VFD or slip-ring starter | High starting torque |
| Variable-speed processes | VFD | Continuous speed control |
This table is a starting point. The final choice depends on the actual motor and load.
Worked Examples
These examples are illustrative and for learning only. Use real motor and starter data for actual designs.
Assumed motor: 30 kW, 415 V, three-phase, full-load current (FLC) = 55 A, locked-rotor current = 6 × FLC, DOL starting torque = 1.5 × rated torque.
Starting current
| Method | Calculation | Line current |
|---|---|---|
| DOL | 6 × 55 | 330 A |
| Star-delta | 330 ÷ 3 | 110 A |
| Autotransformer, 65% tap | 330 × 0.65² (0.65² = 0.4225) | about 139 A (motor current 330 × 0.65 = 214.5 A) |
| Autotransformer, 80% tap | 330 × 0.80² (0.80² = 0.64) | about 211 A |
| Soft starter, limit 3 × FLC | 3 × 55 | 165 A |
Starting torque
| Method | Calculation | Starting torque |
|---|---|---|
| DOL | Given | 1.50 × rated |
| Star-delta | 1.5 ÷ 3 | 0.50 × rated |
| Autotransformer, 65% tap | 1.5 × 0.4225 | about 0.63 × rated |
| Autotransformer, 80% tap | 1.5 × 0.64 | 0.96 × rated |
What this means: suppose the load needs 0.6 × rated torque to get moving. Star-delta (0.50) would leave the motor stalled. The 65% tap (0.63) only just clears it, with almost no margin to accelerate, so the 80% tap (0.96) is the safer choice. Check the full motor torque-speed curve before you decide, because torque must stay above the load torque all the way up to speed.
Standards and Regulations
| Standard | What it covers |
|---|---|
| IEC 60947-4-1 | Electromechanical contactors and motor starters, including coordination types |
| IEC 60947-4-2 | Semiconductor motor controllers and starters, including soft starters |
| IEC 60034-12 | Starting performance of single-speed three-phase cage induction motors |
| IS/IEC 60947-4-1 | Indian adoption of IEC 60947-4-1 |
| NEMA ICS 2 | US standard for industrial controllers, contactors and overload relays |
| NEC Article 430 | US rules for motors, motor circuits and controllers |
| BS 7671 | UK wiring regulations for electrical installations |
Standards are revised from time to time, so check the current edition before you design or install. Local utility rules on starting current and voltage dip also vary, so confirm them with your supplier. Safe motor circuits also rely on good earthing.
Energy Efficiency and Modern Starters
- Soft starters do not save running energy. Once the motor is at speed, the bypass contactor takes over and the motor runs as it would on DOL. The benefit is a gentle start, not lower running cost.
- VFDs can save energy on variable-torque loads. For fans and centrifugal pumps, power falls steeply as speed falls, so running slower when full flow is not needed saves a lot. Savings depend on the duty cycle and are not guaranteed.
- High-efficiency motors (IE3, IE4, IE5) are defined in IEC 60034-30-1. Because they are more efficient, their starting characteristics can differ, so always check the datasheet when replacing an old motor.
- Smart starters now offer remote monitoring and communication over protocols such as Modbus and IO-Link, which helps with maintenance planning.
Common Problems and Mistakes
| Problem | Possible causes to check |
|---|---|
| Motor will not start | No supply or control voltage, a tripped protective device, a stuck load, or an open control-circuit contact |
| Overload relay trips often | Overloaded machine, wrong relay setting or class, phase imbalance, poor cooling, or too many starts per hour |
| Contactor chatters | Low or unstable control voltage, a faulty coil, or a dirty or damaged magnet face |
| Star-delta changeover trips | Timer set too short or too long, wrong contactor sequence, or a wrong motor terminal connection |
| Soft starter faults | Supply problems, stalled load, bypass contactor not closing, or a fault shown on the display (see the manual) |
Regular insulation checks help catch winding problems early. Our guide to the insulation resistance test with a megger explains how. Fault-finding on live equipment should only be done by qualified people following the manufacturer’s instructions.
Mistakes to avoid
- Using star-delta on a motor that is not delta-rated at the supply voltage, or that has only three terminals.
- Using a reduced-voltage starter on a load that needs high torque at start.
- Treating an overload relay as short-circuit protection.
- Choosing a starter on kW alone, without checking load torque, supply and duty.
- Ignoring the changeover spike on open-transition star-delta.
- Expecting a soft starter to control speed or to save running energy.
- Ignoring Type 1 and Type 2 coordination.
Very small motors often need no starter at all. Our guide to the shaded pole motor explains how these simple fan motors start, how to identify them and how far their speed can be controlled.
When a motor keeps tripping or a starter checks out fine, the windings may be the cause. Our guide to motor phase angle testing shows how to compare phases and find developing winding faults.
A reliable starter still depends on sound connections at the motor. Our guide to the motor peckerhead shows how to protect the terminal box from water, dust, condensation and vibration.
Working with a smaller 230 V machine? Our guide on how to wire a single phase electric motor covers UK terminal markings, capacitors, reversing and overload rules.
To work out the speed your starter or drive will deliver, use our direct coupled shaft RPM calculator.
Small single-phase fan and blower drives often use a different motor design. Our guide to PSC motors covers their wiring, capacitors and rotation control.
Not sure what FVNR, DOL or ATL mean on a schedule? Our FVNR starter terminology reference shows they are the same full-voltage method and explains FVR reversing starters.
To estimate how much current a motor draws at the instant of a full-voltage start, use our locked rotor amps calculator, which works from the nameplate code letter.
Motor nameplates in the US are rated in horsepower and imported motors in kilowatts; our kW to hp conversion guide has the formula, charts, a calculator and the NEMA vs IEC size match-up.
Before choosing a starter, size the motor from the load; our guide to brake horsepower shows how to calculate pump BHP and pick the next standard motor size.
Frequently Asked Questions
What are the different types of motor starters?
The main types are DOL (and reversing DOL), star-delta, autotransformer, primary resistance or reactance, part-winding, soft starter, VFD and, for slip-ring motors, the rotor resistance starter.
Which motor starter is most commonly used?
The DOL starter is the most common because it is simple and cheap. Star-delta and soft starters are the usual choices for larger motors.
Why does an electric motor need a starter?
A starter switches the motor, protects it from overload and, where needed, limits the large starting current that would otherwise cause voltage dips and mechanical shock.
What is the difference between a DOL and a star-delta starter?
A DOL starter applies full voltage at once, giving high current and high torque. A star-delta starter starts the motor in star, which cuts both current and torque to about one-third, and then switches to delta.
Why does a star-delta starter reduce current to one-third?
In star, each winding gets 1/√3 of the line voltage, so winding current falls by a factor of √3. In delta, line current is √3 times winding current, but in star it equals winding current. Combining the two factors gives 1/√3 × 1/√3 = 1/3 of the delta line current.
Can all three-phase motors use star-delta starters?
No. The motor must be rated to run in delta at the supply voltage and have all six winding terminals available.
What is the working principle of a soft starter?
It uses thyristors to raise the voltage applied to the motor gradually, so current and torque rise smoothly. A bypass contactor then takes over at full speed.
What is the difference between a soft starter and a VFD?
A soft starter only changes the voltage during starting and stopping. A VFD changes both voltage and frequency, so it also controls the motor speed while running.
Does a soft starter save electricity?
Not while the motor is running. Its benefit is a gentle start and stop. Energy savings come mainly from VFDs on variable-torque loads.
Which starter is best for a centrifugal pump?
A soft starter is a common choice because its soft stop reduces water hammer. A VFD is better if you also need flow control. Small pumps on a strong supply may use DOL.
Which starter suits heavy-load motors?
Heavy loads need high starting torque, so use a VFD, a rotor resistance starter on a slip-ring motor, or a high-tap autotransformer starter. Star-delta is usually unsuitable.
What is a slip-ring motor starter?
It connects external resistance to the rotor of a wound-rotor motor to give high starting torque with low current, then removes the resistance in steps as the motor speeds up.
What is the difference between a contactor and a motor starter?
A contactor only switches the circuit. A motor starter combines a contactor with overload protection and control, and may include other protection and a starting method.
What are AC-3 and AC-4 contactor categories?
AC-3 covers normal starting and stopping of squirrel-cage motors. AC-4 covers harsh duty such as plugging and inching, where the contactor breaks high current.
What is Type 1 and Type 2 coordination?
Type 1 allows damage to the starter after a short circuit, provided there is no danger to people. Type 2 requires the starter to remain usable, with only light contact welding that is easy to separate.
What is the function of an overload relay?
It protects the motor from sustained overcurrent that would overheat the windings. It does not protect against short circuits.
Conclusion
Motor starters fall into four groups: full-voltage (DOL), reduced-voltage (star-delta, autotransformer, resistance, part-winding), electronic (soft starter, VFD) and rotor resistance for slip-ring motors. DOL is the simplest, star-delta and autotransformer starters reduce current at the cost of torque, a soft starter gives a smooth ramp, and a VFD adds full speed control.
To choose well, match the starter to the motor rating, the torque the load needs, the strength of your supply, and whether you need speed control. Design, installation, settings and testing must be carried out by qualified people, following local regulations, utility rules and the manufacturer’s instructions, because motor circuits are hazardous.
Sources and references: IEC 60947-4-1, IEC 60947-4-2 and IEC 60034-12 (IEC Webstore); IS/IEC 60947-4-1 (Bureau of Indian Standards); US Department of Energy, motor-driven systems guidance; ABB and Rockwell Automation motor-starting application guides; AuCom motor starting solutions white paper.