Quick answer: A transformer is an electrical device that changes AC voltage from one level to another using electromagnetic induction. There is no single official count of transformer types, because transformers are grouped in several different ways. The most useful way is by function: power, distribution, instrument, isolation, autotransformer and special-purpose transformers. They can then be grouped further by voltage change, number of phases, core shape, winding arrangement, cooling and insulation, and installation.
Transformers sit at every stage of the electricity supply chain. A generator produces power at a moderate voltage, a transformer raises it for long-distance transmission, and more transformers bring it down in steps until it is safe to use in a home or factory. Because the jobs differ so much, so do the designs.
Many online lists mix up different ways of sorting transformers. A “step-up” transformer and an “oil-immersed” transformer are not alternatives, because one describes what the transformer does and the other describes how it is cooled. This guide keeps each classification separate, so you can see where every type fits. It is written for students, apprentices, electricians and plant engineers, with notes for India, the UK and the US where the rules differ.
What Is a Transformer?
A transformer is a static (non-moving) device that transfers electrical energy between two or more circuits by electromagnetic induction. It normally changes voltage and current levels while keeping the frequency the same. It does not create power. It passes power from one circuit to another, with small losses.
Transformers need alternating current (AC). Steady direct current (DC) produces a steady magnetic field, so no voltage is induced in the secondary winding once the current settles. This is why the national grid uses AC.
How Does a Transformer Work?
Working Principle
An alternating current in the primary winding creates a changing magnetic flux in the iron core. This flux links with the secondary winding and induces a voltage in it. This follows Faraday’s law of electromagnetic induction. Lenz’s law explains why the induced voltage opposes the change that produces it. No electrical connection is needed between the two windings; the core carries the energy as magnetic flux.
Main Parts of a Transformer
- Core: thin steel laminations that guide the magnetic flux.
- Windings: the primary (input) and secondary (output) coils.
- Insulation: paper, pressboard, resin or liquid that keeps windings apart.
- Tank, bushings and tap changer: the enclosure, the insulated terminals, and the device that adjusts the voltage ratio.
- Cooling system, conservator and breather: radiators or fans for heat removal, plus an oil-expansion tank and air dryer on larger liquid-filled units.
Turns Ratio Formula
For an ideal transformer (ignoring losses), voltage, turns and current are related like this:
V₁ / V₂ = N₁ / N₂ = I₂ / I₁
Here V is voltage, N is the number of turns, and I is current. Subscript 1 is the primary and 2 is the secondary. More turns on the secondary gives a higher voltage and a lower current, and fewer turns does the opposite.
Worked example (illustrative figures): A transformer steps 11,000 V down to 433 V. The primary draws 10 A.
- Turns ratio = 11,000 ÷ 433 ≈ 25.4
- Secondary current = 10 × 25.4 ≈ 254 A
The voltage falls by about 25 times and the current rises by about the same factor, so the power stays almost the same.
How Are Transformers Classified?
Each classification answers a different question. Function tells you the job. Voltage tells you whether it raises or lowers voltage. The others describe how the transformer is built and installed. Indian standards material takes the same multi-way approach, classifying by usage, voltage transformation, phase, installation, core design, core material, insulant and number of windings.
Types of Transformers Based on Function
This is the most practical way to sort transformers, because it matches where each one sits in the power system. The figure below shows the path of electricity from generator to consumer.
Power Transformers
A power transformer moves bulk power through the transmission network and large industrial plants. IEC 60076-1, the main international standard, defines a power transformer as a static apparatus with two or more windings that transforms AC voltage and current, usually to different values at the same frequency, for transmitting power. Instrument transformers and a few special types are outside its scope.
Power transformers are usually rated in MVA, are normally oil-immersed, and are designed to run efficiently near their rated load for long periods. You will find them at power stations and transmission substations, often inside a switchgear-equipped yard that connects them to the grid.
Distribution Transformers
A distribution transformer does the final voltage reduction, from a distribution circuit (for example 11 kV or 33 kV in India) to the voltage consumers use. Loads on these units rise and fall through the day, and they are energised around the clock, so low no-load loss matters more than at a power transformer. Pole-mounted units serve overhead rural lines, and pad-mounted or ground-mounted units serve underground and urban networks.
Where is the boundary? There is no single kVA limit that separates power from distribution transformers worldwide. India’s IS 1180 covers three-phase distribution transformers up to 2,500 kVA for systems up to 33 kV. US federal efficiency rules define a distribution transformer by voltage (input 34.5 kV or less, output 600 V or less), 60 Hz, and a kVA range. Always check which definition applies in your country.
| Feature | Power transformer | Distribution transformer | Instrument transformer |
|---|---|---|---|
| System role | Bulk transfer in generation and transmission | Final step-down to consumers | Measurement and protection signals |
| Typical rating | MVA scale (no universal limit) | kVA scale (definitions vary by country) | Defined by secondary current or voltage and burden |
| Load pattern | Often steady and high | Varies through the day | Very small, constant burden |
| Design focus | Load loss and no-load loss at expected duty | Low no-load loss and all-day efficiency | Accuracy class and protection performance |
| Main standards | IEC 60076, IEEE C57, IS 2026 | IEC 60076, IEEE C57, IS 1180 | IEC 61869, IEEE C57.13 |
Instrument Transformers (CT, VT and CVT)
Instrument transformers scale high currents and voltages down to small, standard values that meters and protection relays can handle safely. This keeps people and delicate equipment away from high voltage. The signals feed protection relays, and the settings must be coordinated, as explained in our guide to protection coordination.
| Type | Connection | What it does | Typical secondary | Key caution |
|---|---|---|---|---|
| Current transformer (CT) | In series with the line | Reduces high current to a measurable value | 1 A or 5 A | Never open-circuit the secondary while energised |
| Voltage / potential transformer (VT or PT) | In parallel across the line | Reduces high voltage to a measurable value | Commonly 100–120 V | Do not short-circuit the secondary |
| Capacitor voltage transformer (CVT) | Capacitor divider plus a small transformer | Measures high transmission voltages; can support carrier signalling | Standard low voltage | Needs correct divider and ferroresonance-aware design |
CT safety warning: Do not leave the secondary of an energised current transformer open-circuited. With no secondary current to balance the primary, the core saturates and a dangerously high voltage can appear across the open terminals. Short the secondary terminals before disconnecting any meter or relay, and follow your site procedure.
Isolation Transformers
An isolation transformer has two completely separate windings, so there is no direct electrical connection between input and output. The ratio is often 1:1, but the main purpose is separation, not a change in voltage. It limits shock risk, reduces electrical noise and keeps sensitive circuits separate from the supply. You will see it in workshops, test benches, laboratories and some medical-adjacent equipment. An ordinary two-winding transformer also isolates, so “isolation transformer” mostly describes the intended purpose.
Autotransformers
An autotransformer uses one winding, with part of it shared by the input and output. Because it needs less copper and iron for a modest voltage change, it is smaller and cheaper than a two-winding transformer of the same rating. The trade-off is that it gives no galvanic isolation, so a fault on the high-voltage side can reach the low-voltage side directly.
| Feature | Two-winding transformer | Autotransformer |
|---|---|---|
| Windings | Separate primary and secondary | One winding with a shared section |
| Isolation | Full electrical isolation | None |
| Material use | Higher for the same rating | Lower, especially when the ratio is close to 1:1 |
| Typical use | General power, distribution, isolation | Interconnecting transmission levels, motor starting, variable-voltage supplies |
A Variac is a variable autotransformer. A sliding contact moves along the winding to give an adjustable output voltage, and it is common in laboratories.
Special-Purpose Transformers
Some transformers are built for one particular duty. They are still power transformers, but their design is shaped by the load.
| Type | Purpose | Where it is used |
|---|---|---|
| Generator step-up (GSU) | Raises generator voltage to transmission voltage | Power stations |
| Furnace | Supplies very high current at low voltage | Arc and induction furnaces |
| Rectifier | Feeds rectifier systems | Electrolysis and industrial DC loads |
| Converter | Connects AC systems to converters | HVDC links, large drives |
| Traction | Supplies railway power | Rail substations and rolling stock |
| Phase-shifting | Controls real-power flow by shifting phase angle | Interconnected transmission networks |
| Earthing / zig-zag | Creates a neutral or earth-fault path | Systems with no neutral; see types of earthing systems |
| Scott-T | Converts three-phase to two-phase, or the reverse | Older industrial and railway loads |
| Welding | Delivers high current at low voltage | Welding equipment |
| Solar and wind step-up | Steps inverter or turbine output up to collection voltage | Solar plants, wind farms (IEC/IEEE 60076-16 covers wind-turbine units of 100–10,000 kVA) |
| EV charging and data centre | Feeds charging hubs or critical IT load | Charging sites, data centres |
Types of Transformers Based on Voltage Transformation
This classification simply asks whether the transformer raises voltage, lowers it, or keeps it the same.
| Type | Winding turns | Output voltage | Isolation | Typical use |
|---|---|---|---|---|
| Step-up | Secondary turns greater than primary | Higher than input | Yes, if two-winding | Generator output, solar and wind plants |
| Step-down | Secondary turns fewer than primary | Lower than input | Yes, if two-winding | Substations, distribution, building supplies |
| Isolation | Often equal (1:1) | Same as input | Yes | Safety separation, noise reduction |
Raising voltage lowers current for the same power, which cuts I²R loss in transmission lines. That is why power is stepped up for transmission and stepped back down near the user.
Types of Transformers Based on Phase
| Type | Description | Typical use | Points to note |
|---|---|---|---|
| Single-phase | One primary and one secondary winding | Homes, small loads, rural lines, control circuits | Simple and cheap, but limited capacity |
| Three-phase unit | Three phase windings on one core in one tank | Utilities and industry | More compact and usually cheaper than three single-phase units of the same total rating |
| Three-phase bank | Three single-phase transformers connected together | Large units, difficult transport, where a spare is needed | If one unit fails, only that single-phase unit needs replacing |
Types of Transformers Based on Core Construction
The core shape decides how the magnetic flux travels and how the windings are supported.
| Core type | Layout | Strengths | Typical use |
|---|---|---|---|
| Core type | Windings around the core limbs | Simple insulation arrangement; common in large units | Power and distribution transformers |
| Shell type | Core surrounds the windings | Good mechanical support for the windings | Smaller and some special transformers |
| Berry type | Multi-limbed, shell-like layout | Compact magnetic circuit | Specific designs; the term is used inconsistently, so check the manufacturer |
| Toroidal | Ring-shaped core with windings around the ring | Compact, low stray magnetic field | Control, audio and variable autotransformers |
| Amorphous-metal core | Core made from amorphous alloy instead of conventional CRGO steel | Lower no-load loss | Energy-efficient distribution transformers |
CRGO means cold-rolled grain-oriented electrical steel, the standard core material. Amorphous cores cost more and are harder to handle, but they cut no-load loss, which matters most in distribution transformers that stay energised all year.
Types of Transformers Based on Winding Arrangement
- Two-winding: separate primary and secondary windings, giving full isolation.
- Three-winding: adds a tertiary winding, used for an auxiliary supply, reactive compensation or a path for harmonic currents.
- Autotransformer: a shared winding, covered above.
Three-phase windings can be connected in star (wye), delta or zig-zag. A vector group such as Dyn11 describes the connection on each side and the phase shift between them. In Dyn11, the high-voltage side is delta (D), the low-voltage side is star (y) with an accessible neutral (n), and the low-voltage side leads by 30° (the “11” refers to the clock position). Vector groups matter when running two transformers in parallel, because units with different groups must not be paralleled.
Types of Transformers Based on Cooling and Insulation
Windings heat up under load, so every transformer needs a way to remove heat and keep the insulation intact. The medium used is one of the most important choices in selecting a transformer.
| Type | How it works | Fire and environment notes | Typical use |
|---|---|---|---|
| Mineral-oil-immersed | Oil insulates and carries heat to radiators | Oil is combustible, so containment and fire precautions are needed | Outdoor utility, substations, heavy industry |
| Natural ester-filled | Plant-based liquid replaces mineral oil | Higher fire point and more biodegradable; check fluid-specific data | Fire-conscious or environmentally sensitive sites |
| Synthetic ester-filled | Man-made ester liquid | Similar fire-safety reasoning; different fluid properties | Industrial, renewable and special applications |
| Silicone-filled | Silicone liquid | High fire point; specialist fluid | Selected industrial and indoor sites |
| Gas-filled | Gas provides insulation and cooling | No liquid spills; gas must be managed (IEC 60076-15) | Where liquid is unwanted |
| VPI dry-type | Air-cooled; windings impregnated under vacuum and pressure | No liquid; low fire load | Commercial and industrial buildings |
| Cast-resin dry-type | Air-cooled; windings encased in epoxy resin | No liquid; robust insulation | Hospitals, high-rises, data centres, marine |
IEC 60076-11 covers dry-type power transformers with a highest voltage up to 72.5 kV and at least one winding above 1.1 kV.
Oil-Immersed vs Dry-Type: Which Is Better?
Neither is better everywhere. The right choice depends on where the transformer will be installed.
| Factor | Oil-immersed | Dry-type |
|---|---|---|
| Cooling and insulation | Liquid | Air and solid insulation |
| Fire risk | Higher; needs fire barriers or bunding | Lower |
| Best location | Outdoors | Indoors and populated buildings |
| Maintenance | Oil sampling and tests | Visual checks, cleaning, electrical tests |
| Size at high ratings | Generally more compact | Generally larger |
Market-research estimates give a sense of how common each is. One 2025 estimate puts oil-immersed units at about 58% of the global distribution-transformer market and dry-type at about 42%.
Transformer Cooling Codes: ONAN, ONAF, OFAF and ODAF
The cooling code on a nameplate tells you how heat is removed. Under IEC 60076-2, liquid-immersed transformers use a four-letter code, read in this order: internal liquid, how it circulates inside, the outside cooling medium, and how that circulates.
| Code | Meaning | Used on |
|---|---|---|
| ONAN | Oil natural, air natural | Small and medium oil-immersed units |
| ONAF | Oil natural, air forced (fans) | Oil-immersed units needing extra capacity |
| OFAF | Oil forced (pumps), air forced | Larger oil-immersed units |
| ODAF | Oil directed through the windings, air forced | Large power transformers |
| KNAN | As ONAN, but with a high fire-point fluid such as ester (K) | Ester-filled units |
| AN / AF | Dry-type, air natural or air forced | Dry-type units |
Check the exact wording against IEC 60076-2 or IEEE C57.12.00 if you need it for a specification.
Types of Transformers Based on Installation
| Installation | Description | Typical use |
|---|---|---|
| Indoor | Usually dry-type, inside a building | Commercial buildings, factories, data centres |
| Outdoor | Weather-protected tank or enclosure | Substations and industrial sites |
| Pole-mounted | Mounted on an overhead-line pole | Rural and overhead distribution |
| Pad-mounted | Tamper-resistant enclosure at ground level | Underground networks, campuses, commercial areas |
| Underground / vault | In a vault or chamber below ground | Dense urban networks |
| Hermetically sealed | Sealed tank with no conservator | Lower-maintenance liquid-filled units |
| Conservator type | Oil-expansion tank and breather | Larger liquid-filled transformers |
Electronic and Signal Transformers
Audio, pulse, radio-frequency (RF), flyback and switched-mode power supply (SMPS) transformers use the same induction principle, but they are a different family. They work at much higher frequencies and far lower power, often with ferrite cores, and they follow electronics standards rather than grid standards. A flyback transformer in a phone charger and a 315 kVA distribution transformer have little in common in design or safety, so this article covers grid-connected equipment.
Modern and Emerging Transformer Technologies
- Smart transformers: usually a conventional transformer fitted with sensors, communications and monitoring. The meaning varies by supplier.
- Solid-state transformers: use power electronics to convert and control power. They are still developing and are not a mainstream replacement for conventional units.
- Amorphous-core transformers: lower no-load loss, and recognised as a core-material category in Indian standards.
- Ester-filled transformers: use natural or synthetic ester liquid. IS 1180 Part 2 covers ester-immersed distribution transformers.
Transformer Losses and Efficiency
A transformer has no moving parts, so its efficiency is high, but it is never perfect. Two kinds of loss occur:
- No-load (core) loss: caused by hysteresis and eddy currents in the core. It is present whenever the transformer is energised, whatever the load.
- Load (copper) loss: the I²R heating in the windings. It rises with the square of the load current.
Efficiency (η) = Pout ÷ (Pout + no-load loss + load loss) × 100
Worked example (illustrative figures): A 100 kVA transformer at unity power factor has a no-load loss of 0.3 kW and a full-load copper loss of 1.2 kW. At 75% load:
- Output = 100 × 0.75 = 75 kW
- Copper loss = 1.2 × 0.75² = 0.675 kW
- Efficiency = 75 ÷ (75 + 0.3 + 0.675) ≈ 98.7%
Efficiency peaks when copper loss equals core loss. In this example that happens at 50% load, because 1.2 × 0.5² = 0.3 kW.
Why Are Transformers Rated in kVA, Not kW?
The heat a transformer produces depends on its voltage and current, not on the power factor of the load. kVA (apparent power) is voltage times current, so it measures the transformer’s real limit. How many kW you get from it then depends on the power factor.
Transformer Standards and Efficiency Regulations
Standards describe how transformers must be designed and tested, and regulations set minimum efficiency. They overlap but differ by region.
| Standard or rule | Body | Scope | Region |
|---|---|---|---|
| IEC 60076 series (Part 1 is the 2011 edition; Part 11, dry-type, is 2018) | IEC | Power transformers | International |
| BS EN 60076-1 | BSI / CENELEC | UK and European adoption of IEC 60076-1 | UK, Europe |
| IEC 61869 series | IEC | Instrument transformers | International |
| IEEE C57 series (C57.13 for instrument transformers) | IEEE | Power, distribution and regulating transformers | US and others |
| IS 2026 | BIS | Power transformers | India |
| IS 1180 | BIS | Distribution transformers up to 2,500 kVA and 33 kV (Part 1 mineral oil, Part 2 ester) | India |
| BEE Schedule 4 star label | Bureau of Energy Efficiency | Oil-immersed, naturally air-cooled, three-phase, double-wound, non-sealed outdoor distribution transformers. Star 1 has the highest losses and Star 5 the lowest | India |
| Regulation (EU) 548/2014 as amended by 2019/1783 | European Commission | Power transformers of 1 kVA and above; Tier 2 applies from July 2021; instrument transformers excluded | EU |
| 10 CFR Part 431 and the 2024 DOE final rule | US Department of Energy | Distribution transformers; compliance with the amended standards from 23 April 2029 | US |
Editions and compliance dates change, so check the official source or standards body before relying on any figure.
How to Choose the Right Type of Transformer
This table is a starting framework, not a sizing method. A qualified engineer should specify the final selection.
| Application | Likely type | Key points to consider |
|---|---|---|
| Transmission substation | Oil-immersed power transformer | MVA rating, cooling, impedance, protection, transport |
| Local distribution | Pole-, pad-mounted or underground distribution transformer | kVA, losses, installation, public safety |
| Commercial building or hospital | Dry-type (cast resin or VPI) | Fire safety, noise, indoor space |
| Data centre | Dry-type or liquid-filled | Harmonics, load growth, cooling, footprint |
| Solar or wind plant | Step-up transformer for the plant | Inverter harmonics, outdoor duty, efficiency |
| Arc furnace | Furnace transformer | Very high current, thermal and mechanical stress |
Whatever the application, work through these questions:
- What kVA or MVA, voltage ratio, frequency and number of phases are needed?
- Is it going indoors or outdoors, and what are the ambient temperature, altitude and ventilation?
- Is fire safety or environmental protection a priority?
- What are the load profile, power factor, harmonics and expected growth?
- What are the purchase price, running losses, maintenance needs and expected life?
Judge cost over the whole life of the unit, not just the purchase price. A cheaper transformer with higher losses can cost more to run.
Transformer Protection, Testing and Maintenance
This is an overview only. Detailed procedures belong in dedicated guides and the manufacturer’s instructions.
- Protection devices: Buchholz relay (gas and oil surge detection in oil units), pressure-relief device, oil and winding temperature indicators, and differential protection. Relay settings should be verified through regular relay testing.
- Tests: insulation resistance (see our insulation resistance test with a megger guide), turns ratio, winding resistance, oil testing and dissolved gas analysis (DGA).
- Routine care: visual inspection, checking oil level and temperature, inspecting bushings, checking cooling equipment, and reviewing protection and test records.
A transformer is only one part of the electrical system. It connects to busbars, is switched and protected by the circuit breakers you choose, and is housed in switchgear panels. Surge damage is limited with the right surge protection devices.
Common Mistakes and Safety Precautions
- Expecting a transformer to work on DC.
- Treating power and distribution transformers as the same thing; duty, losses and standards differ.
- Assuming an autotransformer gives full isolation.
- Believing dry-type units need no maintenance.
- Ignoring harmonics from drives, rectifiers, EV chargers and data-centre loads.
- Choosing a cooling class that does not suit the ambient conditions.
- Comparing purchase price only and ignoring losses.
- Paralleling transformers with incompatible vector groups.
- Leaving an energised CT secondary open-circuited.
Transformer metal parts and tanks must also be properly earthed. See earthing vs grounding if the UK and US terms confuse you.
Many building transformers supply a 120/208 V wye. Our guide to 208 single phase explains how two legs make 208 V, how to wire it and how it compares with 240 V.
Comparing three-phase connections? Our guide to the wye wye transformer explains how it differs from delta-wye on harmonics, grounding and applications.
If a transformer keeps opening its protection, our guide to the transformer fuse explains why it can blow with no load and how to diagnose the cause.
Once you have chosen a transformer, plan its location carefully. Our guide to transformer clearances covers ventilation, combustible materials and NEC working space.
Designing or buying equipment for a US building? Our 208 vs 240 volt guide explains where each voltage comes from, the ANSI ranges and how 230/400 V European supplies compare.
Feeding heaters from a 480 V supply? Our guide to single phase 480 V heater wiring covers protection, contactor control and balancing loads across three phases.
If a CT-fed meter reads low after a generator transfer, see our troubleshooting guide: current transformer meter shows half current.
Transformers are rated in kVA, not kW; our kVA to kW conversion guide shows how power factor sets the real load a transformer or generator can carry.
Frequently Asked Questions About Types of Transformers
How many types of transformers are there?
There is no official number. Transformers are classified in several ways at once, including function, voltage, phase, core, cooling and installation. Depending on how you count, lists run from about 7 main types to more than 30.
What are the main types of transformers?
By function, the main types are power, distribution, instrument, isolation and autotransformers, plus special-purpose units such as generator step-up transformers. By voltage change, they are step-up, step-down and isolation transformers.
What is the most commonly used transformer?
Distribution transformers are the most widely installed in power networks, because every area needs them to supply consumers. Small single-phase and electronic transformers are more numerous overall, since they are built into countless appliances.
What is the difference between a power transformer and a distribution transformer?
A power transformer handles bulk power in transmission and large plants. A distribution transformer makes the final step down to the consumer. The exact boundary varies by country, so rely on the local standard.
What is the difference between a step-up and step-down transformer?
A step-up transformer has more secondary turns than primary turns and raises voltage. A step-down transformer has fewer secondary turns and lowers voltage. Current changes in the opposite direction to voltage.
What is an isolation transformer used for?
It separates two circuits electrically. This reduces shock risk, filters some electrical noise and protects sensitive equipment. The voltage ratio is often 1:1, though not always.
What is an autotransformer?
An autotransformer is a transformer whose primary and secondary share part of one winding. It uses less material than a two-winding unit but gives no electrical isolation between circuits.
What is the difference between CT and PT?
A current transformer (CT) is connected in series and scales current. A potential or voltage transformer (PT or VT) is connected in parallel and scales voltage. Both supply meters and protection relays.
What is the difference between oil-immersed and dry-type transformers?
Oil-immersed units are cooled and insulated by liquid and suit outdoor sites. Dry-type units use air and solid insulation, carry a lower fire risk and suit indoor and populated buildings.
What does ONAN mean in a transformer?
ONAN stands for Oil Natural, Air Natural. The oil circulates by natural convection and air passes over the radiators without fans. It is the simplest cooling method for oil-immersed transformers.
Why are transformers rated in kVA instead of kW?
Heating depends on voltage and current, not on power factor. kVA captures both, so it shows the true loading limit regardless of the type of load connected.
What is a transformer vector group?
A vector group is a code such as Dyn11 that shows how the windings are connected and the phase shift between primary and secondary. It must match for transformers to run in parallel.
Can a transformer work on DC?
No. A transformer needs a changing magnetic flux, which AC provides. Steady DC induces no output voltage and can overheat the primary winding.
What are the advantages of a three-phase transformer?
A three-phase unit is usually more compact and cheaper than three separate single-phase units of the same total rating, and it needs less space and wiring. A bank of single-phase units makes spare cover easier.
What is the difference between core-type and shell-type transformers?
In a core-type transformer the windings surround the core limbs. In a shell-type transformer the core surrounds the windings. Core type is more common in large units.
Which transformer is used in power stations?
The generator step-up (GSU) transformer raises the generator voltage to transmission voltage. Stations also use auxiliary transformers for their own supply, and instrument transformers for metering and protection.
What is a pole-mounted transformer?
It is a distribution transformer fixed on an overhead-line pole. It steps the line voltage down to the supply voltage for nearby consumers and is common in rural and overhead networks.
What is an amorphous core transformer?
It has a core made from amorphous metal rather than conventional CRGO steel. This reduces no-load loss, so it suits distribution transformers that are energised all the time.
What is the difference between a two-winding transformer and an autotransformer?
A two-winding transformer has separate windings and full isolation. An autotransformer shares part of one winding, uses less material and gives no isolation.
What is a generator step-up transformer?
A GSU transformer connects a generator to the transmission grid. It raises the generator’s moderate output voltage to a much higher level so power can travel long distances with less loss.
Conclusion: Understanding the Different Types of Transformers
The simplest way to understand the types of transformers is to ask one question at a time. What job does it do (function)? Does it raise or lower voltage? How many phases does it have? How is the core built, and how is it cooled? Where will it be installed? Answering these in turn removes most of the confusion found in long, mixed lists.
Power, distribution, instrument, isolation and autotransformers cover almost every case, and the remaining classifications describe how each one is built and installed. Match the type to the application, the location, the fire and environmental needs, and the running cost, and check local standards before specifying anything.
Disclaimer: This article is for general education. Transformer selection, installation, operation, testing and maintenance must be carried out by qualified engineers in line with local regulations, codes and the manufacturer’s instructions. Worked examples use illustrative figures and are not for design use. Market figures are paid-report estimates and standard editions change, so verify them against official sources.
Sources
- IEC 60076-1 and IEC 60076-11 (IEC Webstore): IEC 60076-11:2018
- Bureau of Indian Standards, transformer educational material: BIS Transformers
- Bureau of Energy Efficiency: Schedule 4, Distribution Transformers
- European Commission: Power transformers Ecodesign
- US Federal Register: DOE distribution transformer standards, 2024
- Market estimates: Fortune Business Insights and Mordor Intelligence
