There are three main surge protection device (SPD) types under the IEC/BS EN standards: Type 1, Type 2 and Type 3. Type 1 handles partial lightning current at the incoming supply. Type 2 protects distribution boards from switching and induced surges. Type 3 gives final protection close to sensitive equipment. Combined Type 1+2 and Type 2+3 devices also exist. North America uses a different system (UL 1449 Types 1 to 5), so the same word “Type” does not always mean the same thing.
This guide explains each type in plain English, shows where it is installed, and helps you choose the right one. It is written with UK practice in mind, with short notes for India and the USA.
Quick answer: SPD types at a glance
- Type 1 (Class I): tested with a 10/350 µs lightning current. Installed at the origin of the installation.
- Type 2 (Class II): tested with an 8/20 µs current. Installed in main and sub-distribution boards.
- Type 3 (Class III): tested with a combination wave. Installed near sensitive equipment.
- Type 1+2 and Type 2+3: one device tested to both classes.
- UL 1449 Types 1–5: North American types based on where the device may be installed and how it is built.
What is a surge protection device and how does it work?
A surge protection device (also called a surge protective device) limits short, sharp overvoltages called transients. It then diverts the surge current to earth. The aim is to stop the voltage reaching equipment at a level that damages insulation or electronics.
In normal use an SPD has a very high impedance, so it does almost nothing. When the voltage rises above its threshold, it conducts and clamps the voltage. When the surge has passed, it returns to its high-impedance state.
What causes electrical surges?
- Lightning: direct strikes, nearby strikes and induced voltages on cables.
- Switching: utility switching, motors, transformers and capacitor banks.
- Internal loads: welders, variable speed drives and inverters.
An SPD only deals with short transients. It does not fix power cuts, long-term undervoltage or sustained overvoltage, and it does not replace good earthing. If you are unsure how the earth path works, read our guide to types of earthing systems.
Types of surge protection devices by test class (IEC / BS EN 61643-11)
This is the main classification used in the UK, Europe and India. The type tells you the test the device passed and where it normally belongs. The waveform names describe the shape of the test pulse. In an 8/20 µs wave, the current reaches its peak in 8 µs and falls to half its peak in 20 µs.
Type 1 SPD (Class I)
A Type 1 SPD is tested with the 10/350 µs impulse current (rated as Iimp). This waveform imitates the long, energetic current from part of a direct lightning strike. Type 1 devices sit at the origin of the installation, such as the main incoming board. They suit buildings with an external lightning protection system or an overhead supply line. Most Type 1 devices use spark gaps, often combined with varistors.
Type 2 SPD (Class II)
A Type 2 SPD is tested with the 8/20 µs current (rated as In and Imax). It deals with switching surges and the smaller surges induced by nearby lightning. Type 2 is the most common SPD and is fitted in main and sub-distribution boards. Most are built around metal oxide varistors (MOVs). On a typical 230/400 V system this is the type most homes and small commercial buildings need.
Type 3 SPD (Class III)
A Type 3 SPD is tested with a combination wave: a 1.2/50 µs voltage pulse and an 8/20 µs current pulse (rated as Uoc). It has low surge capacity and is meant as the last stage, fitted near sensitive loads such as IT racks, control panels or socket outlets. It should never be the only protection, because it relies on upstream Type 1 or Type 2 devices to take the bulk of the surge.
Type 1+2 and Type 2+3 combined SPDs
A Type 1+2 device has passed both the Class I and Class II tests. It is useful when one device must cover both lightning current and switching surges, for example at a main board with limited space. A Type 2+3 device combines distribution-level and point-of-use duties. Always read the datasheet: combined devices still need correct coordination with other stages.
Type 1 vs Type 2 vs Type 3 vs Type 1+2
| Feature | Type 1 | Type 2 | Type 3 | Type 1+2 |
|---|---|---|---|---|
| IEC class | Class I | Class II | Class III | Class I + II |
| Test waveform | 10/350 µs current | 8/20 µs current | 1.2/50 µs voltage + 8/20 µs current | Both Type 1 and Type 2 tests |
| Key rating | Iimp | In, Imax | Uoc | Iimp and In |
| Main job | Divert partial lightning current | Limit surges in the distribution system | Fine protection at the equipment | Cover both jobs in one device |
| Typical location | Origin of installation, main incoming board | Main and sub-distribution boards | Near sensitive loads, sockets | Main board or origin |
| Stage | First | Second | Final | First and second |
Why use more than one stage? A single device cannot give both high energy capacity and a very low protection level. The upstream device takes the heavy energy, and the downstream device trims what is left. This is called coordination (see below).
Where should each SPD type be installed?
Installers follow the lightning protection zone (LPZ) idea from IEC 62305-4. LPZ 0 is outside the building, exposed to lightning. Each zone further inside is better protected, and SPDs sit at the boundaries. A typical power chain looks like this:
| Location | Typical SPD | Why |
|---|---|---|
| Main distribution board or origin | Type 1, Type 1+2 or Type 2 | First line of defence. Type 1 where a lightning protection system or overhead line is present. |
| Sub-distribution board | Type 2 | Limits surges that pass the first stage or are generated inside the building. |
| Socket outlet or equipment | Type 3 | Fine protection for electronics, IT and control equipment. |
SPDs are mounted in boards, so it helps to know what a board contains. See our guides on types of switchgear panels and what a busbar is for the equipment the SPD connects to.
UL 1449 surge protective device types (Type 1 to Type 5)
UL 1449 is the North American safety standard. Its types describe where the device may be installed and how it is built. They are not the same as the IEC test classes, so do not treat IEC Type 1 and UL Type 1 as equal.
| UL 1449 type | What it means | Typical use |
|---|---|---|
| Type 1 | Permanently connected. May be installed on the line side or load side of the service overcurrent device. Intended to work without external overcurrent protection. | Service entrance, meter socket |
| Type 2 | Permanently connected. Installed on the load side of the service overcurrent device. | Main panel, branch panels |
| Type 3 | Point-of-use device. Installed at least 10 m (30 ft) of conductor from the service panel. | Plug-in, cord-connected and receptacle devices |
| Type 4 | Component assembly: one or more Type 5 components with a disconnect. | Built into SPD products |
| Type 5 | Discrete component, such as a single varistor. | Circuit boards, assemblies |
IEC type vs UL type: what is the difference?
| Point | IEC / BS EN 61643-11 | UL 1449 |
|---|---|---|
| Classified by | Surge test class (waveform) | Installation position and construction |
| Types | 1, 2, 3 (plus 1+2, 2+3) | 1, 2, 3, 4, 5 |
| Protection rating | Up (voltage protection level) | VPR (voltage protection rating) |
| Fault current | Short-circuit withstand and backup protection stated by maker | SCCR (short-circuit current rating) |
| Main regions | UK, Europe, India, many other countries | USA and Canada |
As a loose guide, each system has a service-entrance type, a distribution type and a point-of-use type. But the tests, ratings and legal meaning differ. Always check which standard is printed on the product.
Types of SPD by technology
The parts inside an SPD decide how fast it reacts, how much surge it can carry and how it ages.
- Metal oxide varistor (MOV): its resistance drops as voltage rises. It is compact, fast and carries high surge current, so it is the standard choice in Type 2 and Type 3 power SPDs. It wears with repeated surges, so it needs a thermal disconnector.
- Gas discharge tube (GDT) and spark gap: a gas or air gap that breaks down and conducts when the voltage is high enough. They handle very high currents with almost no leakage, which suits Type 1 and telecom use. They are slower to switch and need care so that mains “follow current” does not keep flowing.
- TVS diode (silicon avalanche diode): a semiconductor that clamps voltage very quickly and precisely. It handles only small energy, so it is used for data lines and electronics.
- Hybrid: combines parts, for example a spark gap with a varistor, to get high energy capacity and a low protection level together.
| Technology | Behaviour | Surge capacity | Ageing | Typical use |
|---|---|---|---|---|
| MOV | Voltage-limiting | High | Degrades with repeated surges | AC power, Type 2 and 3 |
| GDT / spark gap | Voltage-switching | Very high | Tolerant of large impulses | Type 1, telecom |
| TVS diode | Voltage-limiting, very fast | Low to medium | Limited surge exposure | Data and signal lines |
| Hybrid | Switching plus limiting | Depends on design | Depends on parts | Type 1+2, mixed use |
Response times and energy values vary by product, so use the datasheet rather than a general figure.
Voltage-switching, voltage-limiting and combination SPDs
| Mode | How it behaves | Typical parts |
|---|---|---|
| Voltage-switching | High impedance until a threshold, then conducts suddenly | Spark gap, GDT |
| Voltage-limiting | Impedance falls steadily as voltage rises | MOV, TVS diode |
| Combination | Shows both behaviours | GDT with MOV or TVS |
Types of SPD by construction
- One-port (parallel): connected across the supply. It does not carry the load current. This is the usual choice for power distribution boards.
- Two-port (series): has input and output terminals and carries the load current, so its current rating must suit the circuit. Used for some equipment-level and signal applications.
- Fixed: the protection element cannot be swapped, so the whole unit is replaced at end of life.
- Pluggable: has replaceable cartridges, so you can swap a worn module and keep the base.
Common forms include DIN-rail modules for boards, panel-mount units, and plug-in or socket-outlet devices for point-of-use protection.
Types of SPD by application
| Application | Main standard | Key points |
|---|---|---|
| AC power | IEC / BS EN 61643-11 | Single-phase and three-phase boards. Match to the earthing system. |
| Solar PV (DC side) | IEC 61643-31 (up to 1,500 V DC) | Must be rated for DC voltage, polarity and DC arc interruption. |
| Other DC circuits | IEC 61643-41 (up to 1,500 V DC) | Battery storage and DC power equipment. |
| Data and telecom | IEC 61643-21 | Ethernet, PoE, telephone, coax and CCTV. Must not harm signal quality. |
Solar PV and battery storage SPDs
Direct current does not pass through zero like alternating current, so an arc is harder to put out. This is why you cannot use an ordinary AC SPD on a PV array. A PV SPD must be rated for the maximum DC system voltage and connected with the correct polarity. Battery storage systems follow the same logic on their DC side, with extra protection at the inverter.
EV charging, data and LED lighting
EV chargers are electronics on long outdoor cable runs, so they need SPD protection at the supply and, where required, at the charger. Data SPDs protect Ethernet, PoE, telephone and coaxial lines for CCTV and networks, and are chosen by line voltage and data rate. Outdoor LED lighting and street lights are also surge-sensitive, because LED drivers are electronic and the cable runs are long.
SPD ratings explained in simple terms
| Rating | Plain-English meaning | Matters most for |
|---|---|---|
| Uc | Highest voltage the SPD can sit across continuously | All SPDs |
| Up | Voltage left across the SPD during a surge. Lower is better when the SPD is correctly selected. | All SPDs |
| Iimp | Lightning impulse current (10/350 µs) | Type 1 |
| In | Nominal discharge current (8/20 µs), which the SPD can take repeatedly | Type 2 |
| Imax | Maximum single discharge current (8/20 µs) | Type 2 |
| Uoc | Open-circuit voltage of the combination wave | Type 3 |
| VPR | UL’s measured voltage protection rating. Not identical to Up. | UL 1449 devices |
| SCCR | Fault current the SPD can safely withstand | UL 1449 devices |
| TOV | Temporary overvoltage the SPD can survive for a set time | All SPDs |
Two points catch people out. First, Uc is not the same as nominal voltage: it must suit the earthing arrangement and temporary overvoltages. On 230/400 V systems, Uc values of 255 V and above are common, and many products are rated 275 V, 320 V or 385 V (check the datasheet). Second, a higher kA figure is not automatically better. The rating must match the test class, location and coordination.
Coordination, backup protection and lead length
Coordination means the stages share the surge energy properly, so the upstream device takes the heavy load and the downstream device does not get overloaded. Makers publish rules, such as minimum cable length between stages. Our guide to protection coordination explains the same principle for protective devices in general.
Backup protection. Many SPDs need a fuse or breaker upstream so that a failed device cannot cause a sustained short circuit. Follow the maker’s instructions. To understand the difference between the two devices, see fuse vs circuit breaker and our overview of the types of circuit breakers.
Thermal disconnector. A worn MOV can overheat. The thermal disconnector removes it from the circuit and normally triggers the status indicator.
Earthing. The SPD diverts the surge, but the earthing system carries it away. Poor earthing and bonding spoil the protection. If the terminology is confusing, read earthing vs grounding.
Why lead length matters: a worked example
Connection leads act as inductance, and a fast surge produces an extra voltage across them. The equipment sees roughly the SPD’s Up plus this extra voltage:
Vequipment ≈ Up + L × (di/dt)
Illustrative example, not real project data. Assume Up = 1.5 kV, a lead inductance of about 1 µH per metre, and a 10 kA 8/20 µs surge, which rises at about 1.25 kA per µs.
| Total lead length | Extra voltage | Approx. voltage at equipment |
|---|---|---|
| 0.5 m | about 0.6 kV | about 2.1 kV |
| 1.0 m | about 1.25 kV | about 2.75 kV |
In this example the longer lead pushes the voltage above the 2.5 kV impulse withstand level of category II equipment on a 230 V supply. The simple sum is a conservative estimate (the peaks do not always coincide), but the message holds: keep leads as short and straight as possible, ideally 0.5 m or less in total, and follow the maker’s instructions.
How to choose the right SPD
- Identify the system: AC or DC, single-phase or three-phase, voltage, and earthing arrangement (TN, TT or IT).
- Assess surge risk: overhead supply, external lightning protection, exposed location, or heavy switching loads.
- Pick the type and location: Type 1 or 1+2 at the origin where lightning current is likely, Type 2 at boards, Type 3 near sensitive equipment.
- Check ratings: Uc, Up, Iimp, In, Imax, and short-circuit withstand.
- Check installation needs: backup protection, connection arrangement, earthing and the maker’s instructions.
| Application | Typical SPD arrangement (concept only) |
|---|---|
| Home | Type 2 at the consumer unit, or Type 1+2 if there is an external lightning system. Optional Type 3 for sensitive equipment. |
| Commercial building | Type 1 or 1+2 at origin, Type 2 at sub-boards, Type 3 for IT and terminals. |
| Industrial plant | Coordinated Type 1/2 at incomers and sub-boards. Type 3 for PLCs and instruments. |
| Solar PV | DC SPD on the PV side (IEC 61643-31) plus AC SPD at the inverter output. |
| EV charging | SPD at the supply board and at the charger where required. |
| Data centre | Coordinated AC SPDs, plus data-line SPDs on external cables. |
These are general guides, not design advice. Selection and installation should be done by a competent person following local regulations.
SPD standards and regulations (UK, USA, India)
| Standard | What it covers |
|---|---|
| IEC / BS EN 61643-11 | Low-voltage AC SPDs: requirements and tests |
| IEC 61643-12 | Selection and application principles |
| IEC 61643-21 | Telecom and signalling SPDs (2025 edition) |
| IEC 61643-31 | SPDs for the DC side of solar PV, up to 1,500 V DC (2018) |
| IEC 61643-41 | SPDs for DC power circuits, up to 1,500 V DC (2025) |
| IEC 60364-5-53 | Selection and erection of protective devices, including overvoltage protection |
| IEC 62305-4 | Lightning protection of electrical and electronic systems in structures |
| UL 1449 | North American SPD safety standard (Types 1 to 5) |
UK: BS 7671 covers protection against transient overvoltage in Section 443 (when it is needed) and Section 534 (selection and installation). In general you must either fit protection or show through a risk assessment that it is not needed, depending on the consequences of failure.
USA: the National Electrical Code requires SPD protection at dwelling-unit services under 230.67. The 2023 edition sets a minimum nominal discharge current of 10 kA for the SPDs it requires. Check the edition adopted in your state.
India: installations generally follow IEC-based standards adopted through BIS, along with CEA regulations and utility rules. Confirm the current requirement for your project, as it varies by building type and supply authority.
Always check the current edition and amendments of each standard before relying on this table.
How to inspect and maintain an SPD
Most SPDs show their health at a glance. A green window normally means healthy and a red window means the module has reached end of life, although colours vary by maker. Some have a mechanical flag instead. Many also have a remote signalling contact, a dry contact that switches when the device fails. It can send an alarm to a building management system or PLC.
- Check the status indicator during routine inspections.
- Replace the module or unit when the indicator shows end of life.
- Check after a severe storm or a known surge event, even if the indicator looks fine.
- Check that the backup fuse or breaker, earth connection and lead lengths are unchanged.
- Follow the maker’s instructions, and use a competent person for any work on live boards.
Protection relays and SPDs do different jobs, but both are part of a well-maintained system. See relay testing for how inspection routines work on the protection side.
SPD vs other protective devices
| Device | What it does | What it does not do |
|---|---|---|
| SPD | Limits transient overvoltage and diverts surge current | Does not give backup power or fix sustained voltage problems |
| Surge arrester | Broader term. In higher-voltage networks it protects lines and transformers (IEC 60099-4). | Not automatically the same as a low-voltage SPD |
| Lightning rod | Intercepts a strike and gives it a path to earth | Does not protect electronics from induced surges |
| UPS | Provides backup power and some conditioning | Not a substitute for SPDs at the board |
| AVR | Corrects long-term voltage sags and swells | Cannot divert high-energy surges |
| Circuit breaker | Interrupts overload and fault current | Does not clamp surge voltage |
For the arrester terminology in more detail, read lightning arrester vs surge arrester. For the wider picture of board equipment, see what switchgear is.
Common SPD mistakes and misconceptions
- “A power strip protects the whole house.” A power strip is a low-capacity point-of-use device, and not every strip contains real surge protection. Check the marking.
- “IEC Type 1 equals UL Type 1.” They are different systems.
- “Type 1 is always better.” It is built for a different job. It does not replace Type 2.
- Long connection leads. They raise the voltage the equipment sees.
- Wrong Uc for the earthing system. It can cause early failure.
- Using an AC SPD on a solar DC array. It cannot interrupt a DC arc safely.
- Ignoring the end-of-life indicator. A tripped indicator means protection has been lost.
- No coordination between stages. The downstream device can be overloaded.
Frequently asked questions
What are the three main types of surge protection devices?
Type 1, Type 2 and Type 3. Type 1 handles partial lightning current at the origin, Type 2 protects distribution boards, and Type 3 protects equipment at the point of use.
What is the difference between Type 1 and Type 2 SPDs?
Type 1 is tested with a 10/350 µs lightning current and suits the main incoming supply. Type 2 is tested with an 8/20 µs current and suits distribution boards.
Which SPD type is best for a home?
Most homes use a Type 2 SPD at the consumer unit. A Type 1 or Type 1+2 device is more likely where there is an external lightning protection system or an overhead supply. A competent electrician should confirm the choice.
What is a Type 1+2 SPD?
One device that has passed both the Type 1 and Type 2 tests. It is used at a main board where one unit must do both jobs.
What is the difference between IEC and UL SPD types?
IEC types are based on surge test class. UL 1449 types are based on where the device may be installed and how it is built. The numbers look alike but are not equivalent.
What are UL 1449 Type 4 and Type 5?
Type 4 is a component assembly, made of Type 5 components plus a disconnect. Type 5 is a discrete component such as a varistor.
What does Uc mean on an SPD?
It is the maximum continuous operating voltage: the highest voltage the SPD can have across it all the time without conducting or being damaged.
What is the difference between In and Imax?
In is the current the SPD can discharge many times. Imax is the highest current it can discharge once.
Can an SPD protect against a direct lightning strike?
A Type 1 SPD can carry part of the lightning current that enters the installation, but no SPD guarantees protection against a direct strike. An external lightning protection system deals with the strike itself.
Can a power strip give complete surge protection?
No. It is a low-capacity Type 3 style device and cannot replace protection at the main board.
Do solar panels need DC surge protection?
Usually yes. DC-side SPDs rated to IEC 61643-31 are used on the PV side, and the AC side is protected separately. Check the inverter maker’s instructions and local rules.
Can I use an AC SPD on a DC system?
No. DC arcs do not extinguish naturally, so DC systems need an SPD designed and rated for DC.
How long does an SPD last, and when should it be replaced?
Life depends on how many surges it takes. Replace it when the indicator shows end of life, or after a major surge event.
Does an SPD replace earthing?
No. An SPD depends on a good earthing and bonding system to carry the surge away.
Conclusion: which SPD type should you choose?
Start with the location. Use Type 1 (or 1+2) where lightning current may enter, Type 2 at distribution boards, and Type 3 at sensitive equipment. Add the right technology, ratings and DC or data variants for your application. Then get the installation details right: short leads, proper earthing, backup protection and coordination.
Remember that IEC and UL types are different systems. SPD selection, installation and testing must be carried out by competent people following BS 7671, other local regulations and the manufacturer’s instructions. The worked example above is illustrative only.