500 MCM (500 kcmil) Wire: Diameter, mm² and kcmil Meaning

By editor 5 min read
Large conductor sizes from 4/0 AWG to 1000 kcmil drawn to scale

500 MCM is the same as 500 kcmil: a conductor with a cross-sectional area of 500,000 circular mils, about 253 mm². MCM and kcmil both mean “thousand circular mils”, and a circular mil is the area of a circle 0.001 in across. Per NEC Chapter 9, Table 8, stranded 500 kcmil has 37 strands and an overall diameter of 0.813 in (20.65 mm). A solid conductor of the same area would be 0.707 in. kcmil sizes start at 250 kcmil, the next size above 4/0 AWG.

500,000
circular mils
≈ 253 mm²
metric area
0.813 in
stranded diameter
37
strands

What kcmil and MCM Mean

A circular mil is a unit of area equal to a circle one mil (0.001 in, 0.0254 mm) in diameter: π/4 square mils, or about 5.067 × 10⁻⁴ mm². Because the definition contains π, the area of a round wire in circular mils is simply its diameter in mils squared. The US NEC and Canadian CEC use circular mils for wire sizes larger than 0000 AWG, written as kcmil or MCM. A 0.5 in diameter conductor is 500² = 250,000 cmil = 250 kcmil, the first size above 4/0 in the NEC (Wikipedia).

Area (cmil) = d² (d in mils)     1 kcmil = 1,000 cmil ≈ 0.5067 mm²     2 kcmil ≈ 1 mm²

kcmil Converter

kcmil Converter: Area, Diameter and mm²
IndustrialBasics converter. 1 cmil = area of a 1 mil circle; area in cmil = (diameter in mils)²; 1 kcmil ≈ 0.5067 mm² (Wikipedia, circular mil). AWG diameter = 0.005 in × 92(36−n)/39, with n = −1, −2, −3 for 2/0, 3/0, 4/0 (Wikipedia, AWG). Stranded diameter and resistance shown for sizes listed in NEC Chapter 9, Table 8.

500 kcmil Specifications

Property500 kcmilSource
Area500,000 cmil (253 mm²)NEC Ch. 9, Table 8
Stranding37 strands of 0.116 in (2.95 mm)NEC Table 8
Overall diameter, stranded0.813 in (20.65 mm)NEC Table 8
Diameter if solid0.707 in (√500,000 mils)Calculated
Overall area (for conduit fill)0.519 in² (336 mm²)NEC Table 8
DC resistance, copper (75 °C)0.0258 Ω/kft (0.0845 Ω/km)NEC Table 8
DC resistance, aluminum (75 °C)0.0424 Ω/kft (0.1391 Ω/km)NEC Table 8
From a transcription of NEC 2014 Chapter 9, Table 8 (conductor properties); check the edition you are working to.
4/0 to 1000 kcmil conductor sizes to scaleCircles drawn to scale for stranded copper conductors: 4/0 AWG 0.528 inch, 250 kcmil 0.575, 350 kcmil 0.681, 500 kcmil 0.813 (highlighted), 750 kcmil 0.998 and 1000 kcmil 1.152 inch overall diameter.Large conductor sizes to scale: overall diameter of stranded copper4/0 AWG0.528 in250 kcmil0.575 in350 kcmil0.681 in500 kcmil0.813 in750 kcmil0.998 in1000 kcmil1.152 in500 kcmil: 37 strands, 0.813 in (20.65 mm) overall; a solid 500,000 cmil conductor would be √500,000 = 707 mils (0.707 in).IndustrialBasicsindustrialbasics.com
Figure 1: Overall diameters of stranded bare conductors from NEC Chapter 9, Table 8 (2014 edition transcription). Insulated cable is larger.

kcmil Wire Size Chart (250 to 1000 kcmil)

Sizemm²StrandsOverall dia. (in)Overall dia. (mm)Area (in²)Cu Ω/kftAl Ω/kft
4/0 AWG107.2190.52813.410.2190.06080.1000
250 kcmil127370.57514.610.2600.05150.0847
300 kcmil152370.63016.000.3120.04290.0707
350 kcmil177370.68117.300.3640.03670.0605
400 kcmil203370.72818.490.4160.03210.0529
500 kcmil253370.81320.650.5190.02580.0424
600 kcmil304610.89322.680.6260.02140.0353
700 kcmil355610.96424.490.7300.01840.0303
750 kcmil380610.99825.350.7820.01710.0282
800 kcmil405611.03026.160.8340.01610.0265
900 kcmil456611.09427.790.9400.01430.0235
1000 kcmil507611.15229.261.0420.01290.0212
Stranded conductor properties and DC resistance at 75 °C, NEC Chapter 9, Table 8 (2014 transcription).

The bare-conductor area is what Table 8 lists. Conduit fill uses the insulated-conductor area from Chapter 9, Table 5 for the insulation type, so see the conduit fill chart. For grounding electrode and equipment grounding conductor sizes related to large feeders, see NEC 250.66 and the ground wire size chart.

Specifying tip: Specify kcmil cable by material, size, strand class and insulation, for example “500 kcmil Cu THHN/THWN-2”. Insulated outside diameter varies by type and manufacturer, so use the cable data sheet for lugs, bending space and pulling calculations.

Ampacity and Voltage Drop

Ampacity is not a property of the size alone. It depends on copper or aluminum, the insulation temperature rating, the terminal rating, the number of current-carrying conductors and ambient temperature. Use NEC Table 310.16 with its correction and adjustment factors (see our AWG wire ampacity chart). Very large feeders are often built from conductor sets in parallel rather than one huge conductor. For voltage drop, use the Table 8 resistance above, or see NEC voltage drop rules.

Installation note: Large conductors carry very high fault energy. Terminate with listed compression or mechanical lugs rated for the conductor size and material, torque to the manufacturer’s value, and use anti-oxidant compound on aluminum where required.

Frequently Asked Questions

What does MCM mean in wire size?

Thousand circular mils. MCM and kcmil mean the same thing: 500 MCM = 500 kcmil = 500,000 circular mils (Wikipedia).

What does kcmil stand for?

Kilo-circular mils: thousands of circular mils. A circular mil is the area of a circle one mil (0.001 in) in diameter.

What is the diameter of 500 MCM wire?

For stranded copper or aluminum, 0.813 in (20.65 mm) overall, with 37 strands of 0.116 in, per NEC Chapter 9, Table 8. A solid conductor of the same area would be 0.707 in. Insulated cable is larger; check the cable data sheet.

How many mm² is 500 kcmil?

About 253 mm² (500 × 0.5067). The rule of thumb 2 kcmil ≈ 1 mm² is within about 1.3% (Wikipedia).

What size comes after 4/0 AWG?

250 kcmil is the first size larger than 4/0 AWG used in the NEC (Wikipedia). 4/0 AWG is 211,600 cmil.

How do you calculate circular mils?

Area in circular mils = (diameter in mils)². A 0.5 in (500 mil) solid conductor has 500² = 250,000 cmil = 250 kcmil.

What is the resistance of 500 kcmil copper?

0.0258 Ω per 1,000 ft (0.0845 Ω/km) uncoated copper at 75 °C; aluminum is 0.0424 Ω/kft (NEC Chapter 9, Table 8).

How many strands are in 500 MCM?

37 strands in NEC Table 8; sizes from 600 to 1000 kcmil use 61 strands.

What is the ampacity of 500 kcmil?

It depends on conductor material, insulation temperature rating, number of conductors and ambient temperature; use NEC Table 310.16 with correction and adjustment factors. See our AWG wire ampacity chart.

Why are big wires in kcmil instead of AWG?

AWG stops at 4/0 (0000). Beyond that, the NEC and CEC define sizes by area in circular mils (Wikipedia).

Sources and Further Reading