Ground Wire Size Chart: NEC Table 250.122 and Multiconductor Cable

By editor Updated 7 min read
Green insulated copper ground conductors increasing in size beside an earth symbol and breaker ratings

Under NEC Table 250.122, the ground wire is sized from the breaker or fuse rating, not the wire ampacity. Common copper sizes are 14 AWG for 15 A, 12 AWG for 20 A, 10 AWG for 30 to 60 A, 8 AWG for 100 A and 6 AWG for 200 A. If a rating falls between two rows, use the next higher row. This chart covers equipment grounding conductors (EGCs), the ground wires run with a circuit.

Breaker or fuse (not exceeding)Copper EGCAluminum or copper-clad aluminum EGC
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1000 A2/0 AWG4/0 AWG
1200 A3/0 AWG250 kcmil
1600 A4/0 AWG350 kcmil
2000 A250 kcmil400 kcmil
Equipment grounding conductor sizes from NEC Table 250.122. Check the edition adopted locally.
Reader tip: There is no 30 A, 40 A or 50 A row. Those circuits use the 60 A row, so the minimum copper EGC is 10 AWG.
10 AWG
Copper EGC for 30 to 60 A
8 AWG
Copper EGC for 100 A
6 AWG
Copper EGC for 200 A
1/0
Copper EGC for 800 A

How to Read the Ground Wire Size Chart

Copper equipment grounding conductor size by breaker rangeUp to 15 amps uses 14 AWG, up to 20 amps 12 AWG, up to 60 amps 10 AWG, up to 100 amps 8 AWG, up to 200 amps 6 AWG and up to 300 amps 4 AWG copper.Copper ground wire by breaker range14 AWGUp to 15 A12 AWG16 to 20 A10 AWG21 to 60 A8 AWG61 to 100 A6 AWG101 to 200 A4 AWG201 to 300 AIndustrialBasicsindustrialbasics.com
Figure 1: Each size applies up to its row rating in NEC Table 250.122. Drawing is illustrative, not to scale.
  1. Find the overcurrent device rating protecting the circuit.
  2. Go to the first row that equals or exceeds that rating.
  3. Read the size in the column for your conductor material.
  4. Check whether the hots were upsized for voltage drop.
  5. Check parallel runs, because each raceway or cable needs its own EGC.
  6. Confirm the EGC need not exceed the size of the circuit conductors.

The EGC’s main job is to carry fault current back to the source so the breaker or fuse opens quickly. That is why its size follows the protective device. To choose the circuit conductors themselves, use our AWG wire ampacity chart.

Material note: Aluminum EGCs have installation limits. NEC 250.120(B) restricts their use within 18 inches of earth and in direct contact with masonry.

EGC vs GEC: Use the Right Table

“Ground wire” can mean two different conductors. Confusing them is one of the most common sizing mistakes.

Equipment grounding conductor and grounding electrode conductorThe equipment grounding conductor runs from the panel to equipment and is sized from the overcurrent device. The grounding electrode conductor runs to the earth electrode and is sized from the service conductors.EGC vs GEC: two different conductorsService panelMain bonding pointEquipmentMetal enclosureEGCTable 250.122GECTable 250.66EarthGrounding electrodeEGC sized from thebreaker or fuse ratingGEC sized from theservice conductor sizeIndustrialBasicsindustrialbasics.com
Figure 2: Use the correct table for the conductor you are sizing.
PointEGCGEC
Full nameEquipment grounding conductorGrounding electrode conductor
ConnectsEquipment to the panelSystem to the grounding electrode
NEC tableTable 250.122Table 250.66
Sized fromOvercurrent device ratingLargest ungrounded service conductor
200 A example6 AWG copper4 AWG copper with 2/0 or 3/0 copper service conductors
The two ground conductors compared.

Table 250.66 for grounding electrode conductors

Largest copper service conductorCopper GECAluminum GEC
2 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4 AWG2 AWG
Over 3/0 through 350 kcmil2 AWG1/0 AWG
Over 350 through 600 kcmil1/0 AWG3/0 AWG
Over 600 through 1100 kcmil2/0 AWG4/0 AWG
Over 1100 kcmil3/0 AWG250 kcmil
Grounding electrode conductor sizes for copper service conductors, from NEC Table 250.66.

The GEC can be smaller for some electrodes. A sole connection to a rod, pipe or plate electrode is not required to be larger than 6 AWG copper or 4 AWG aluminum, and a sole connection to a concrete-encased electrode is not required to be larger than 4 AWG copper. For how these conductors fit into a complete system, see our guides to earthing systems and earthing vs grounding.

When the Ground Wire Must Be Upsized

If you increase the ungrounded conductors beyond the size needed for ampacity, usually to reduce voltage drop, NEC 250.122(B) requires a wire-type EGC to increase by the same circular-mil ratio.

New EGC area = Table EGC area × (Larger conductor area / Original conductor area)

Worked example: 200 A feeder

A 200 A feeder would normally use 3/0 copper with a 6 AWG copper EGC. It is upsized to 250 kcmil for voltage drop.

StepCalculationResult
Original conductor3/0 AWG copper167,800 cmil
Larger conductor250 kcmil copper250,000 cmil
Ratio250,000 / 167,8001.49
Table EGC6 AWG copper26,240 cmil
Required EGC area26,240 × 1.49About 39,100 cmil
Next standard size4 AWG = 41,740 cmil4 AWG copper
Upsizing the EGC in proportion to the phase conductors.
Code note: Increasing conductor size only because of temperature correction or bundling is generally treated differently from upsizing for voltage drop. Check the exact wording of 250.122(B) in your adopted code edition.

Sizing the Ground in Multiconductor Cable and Parallel Runs

In a parallel installation, the EGC is not divided between the runs. Under NEC 250.122(F), each raceway or cable gets its own EGC, sized from the full rating of the overcurrent device.

Full-size EGC in each parallel conduitA 1600 amp feeder in three parallel conduits has a 4/0 copper equipment grounding conductor in every conduit.Parallel run: a full-size EGC in every racewayConduit 14/0 copper EGCConduit 24/0 copper EGCConduit 34/0 copper EGCIndustrialBasicsindustrialbasics.com
Figure 3: Example for a 1600 A device. The EGC is not divided between the conduits.
Overcurrent deviceParallel setsEGC in each raceway or cable (copper)
400 A23 AWG
800 A21/0 AWG
1200 A33/0 AWG
1600 A34/0 AWG
The EGC size depends on the device rating, not the number of sets.

This matters most with factory-made multiconductor cable. The built-in ground is sized for the cable’s use as a single run, so it may be too small when several cables are paralleled on one large breaker. Compare the cable’s actual ground size with the table before you buy it, and check the multiconductor cable provisions in 250.122(F) for your code edition. Our guide to types of electrical cables covers common constructions.

Motor circuits

For motor circuits, NEC 250.122(D) bases the EGC on the rating of the motor’s short-circuit and ground-fault protective device. If you need the motor current first, see our guide to full load amps.

Common Ground Wire Sizing Mistakes

MistakeWhy it is wrongCorrect approach
Sizing from the load currentThe table uses the device ratingUse the breaker or fuse rating
Using Table 250.66 for a feeder EGCThat table is for GECsUse Table 250.122
Rounding a 50 A circuit downThere is no 50 A rowUse the 60 A row
Not upsizing with the hotsThe fault path stays too weakApply the circular-mil ratio
Dividing the EGC across parallel runsEach run needs a full EGCSize each from the full device rating
Assuming cable grounds are adequateParalleling can change the needCheck against the table
Errors that weaken the fault-current path.
Safety note: A poor ground path can leave metal enclosures live during a fault. De-energize and prove dead before working, follow your lockout/tagout procedure, and verify any design against the code adopted locally. This guide is educational and does not replace NFPA 70.

To see where Table 250.122 sits among the other grounding rules, read our NEC Article 250 guide.

Frequently Asked Questions

What size ground wire do I need for a 200 amp circuit?

NEC Table 250.122 requires 6 AWG copper or 4 AWG aluminum for an equipment grounding conductor on a 200 A device. A service grounding electrode conductor is sized differently, from Table 250.66.

What size ground wire for a 100 amp circuit?

Use 8 AWG copper or 6 AWG aluminum as the equipment grounding conductor.

What size ground wire for a 50 amp circuit?

Table 250.122 has no 50 A row, so use the 60 A row: 10 AWG copper or 8 AWG aluminum.

What size ground wire for a 30 amp circuit?

A 30 A circuit also uses the 60 A row, which is 10 AWG copper or 8 AWG aluminum.

Does the ground wire have to be the same size as the hot wire?

No. It is usually smaller. It must meet Table 250.122 but generally does not have to be larger than the circuit conductors.

Do I have to upsize the ground wire for voltage drop?

Generally yes. If the ungrounded conductors are made larger than needed for ampacity, NEC 250.122(B) requires a wire-type EGC to increase in proportion by circular mil area.

How do I size the ground in parallel conduits?

Each raceway or cable gets its own EGC, sized from the full rating of the overcurrent device, as described in NEC 250.122(F).

What is the difference between Table 250.122 and Table 250.66?

Table 250.122 sizes equipment grounding conductors from the overcurrent device rating. Table 250.66 sizes grounding electrode conductors from the service conductor size.

Sources and Further Reading

About the author

editor

Leave a Comment