An insulation resistance test checks how well the insulation on a cable, winding or circuit stops current leaking away. A megger (also called a megohmmeter or insulation resistance tester) applies a high DC voltage, measures the tiny leakage current and shows the result in megohms (MΩ). For most building circuits you test at 250 V, 500 V or 1,000 V DC and look for at least 1 MΩ. Motors, cables and transformers use test voltages up to 5 kV or more, with limits that depend on the equipment and standard.
This guide explains how a megger works, which voltage to choose, how to carry out the test safely, and how to judge the reading for motors, generators, transformers, cables, switchgear, house wiring and solar PV systems. It follows UK practice (BS 7671) and also covers IEEE 43, IEC 60364-6 and IEC 62446-1.
Quick answers
- Test voltage: 250 V for SELV/PELV, 500 V for circuits up to 500 V, 1,000 V above 500 V (BS 7671).
- Minimum reading (BS 7671): 0.5 MΩ for SELV/PELV circuits and 1.0 MΩ for all other circuits.
- Polarization index (PI): 10-minute reading ÷ 1-minute reading. A value of 2.0 or more is generally good.
- Dielectric absorption ratio (DAR): 60-second reading ÷ 30-second reading. A value of 1.4 or more is generally good.
- Live circuits: never. The circuit must be isolated, proved dead and discharged afterwards.
This guide is for general learning. Only competent, authorised people should carry out insulation testing, following site rules, the equipment maker’s instructions and the standard that applies to the job.
What is an insulation resistance test?
Insulation resistance (IR) is the resistance of an insulating material to a DC voltage. Good insulation has a very high resistance, so only a tiny current leaks through it. As insulation ages, gets damp or becomes dirty, more current leaks and the resistance falls.
The test is used to find problems before they cause a fault. It can show:
- moisture or water inside insulation
- dirt, dust or chemical contamination on insulation surfaces
- ageing and overheating damage
- cracks, cuts and other physical damage
It is done on new installations before they are energised, as routine maintenance, and after repairs, flooding or faults. It does not prove that the insulation can withstand a surge or overvoltage; that is the job of a withstand (hipot) test, covered later.
Insulation matters most in rotating machines. Surveys of motor failures consistently put winding and stator insulation among the leading causes, although the share varies by study from about a quarter to a half of failures.
- Bearings: 41%
- Stator windings: 36%
- Rotor: 9%
- Other: 14% (remainder)
What is a megger?
A megger is an instrument that measures very high resistances, in megohms (MΩ) and gigohms (GΩ), by applying a high DC test voltage. The proper technical names are megohmmeter and insulation resistance tester.
“Megger” is also a brand name. It started with the hand-cranked insulation tester developed by Evershed & Vignoles in the early 1900s, and the word has since become everyday trade language, as in “to megger a cable”. In this guide, “megger” means any insulation resistance tester, whatever the make.
A megger is not the same as a multimeter. A multimeter uses a few volts, so it cannot stress insulation enough to show leakage or measure the very high resistances involved.
Types of megger
| Type | How it works | Advantages | Limits |
|---|---|---|---|
| Hand-cranked | A hand generator produces the DC test voltage | No battery needed; simple | Voltage and timing depend on the operator |
| Electronic (battery) | An electronic converter gives a steady, regulated test voltage | Timers, PI/DAR, data logging, automatic discharge | Needs charged batteries |
| High-voltage (multi-kV) | Higher-voltage DC source, often 5 kV to 10 kV or more | Suits motors, cables and transformers | Greater hazard; needs stricter procedures |
How does an insulation resistance tester work?
The tester applies a DC voltage (V) across the insulation and measures the small current (I) that flows. It then calculates resistance using Ohm’s law:
R = V ÷ I
For example, 500 V driving 0.5 µA through insulation gives 500 ÷ 0.0000005 = 1,000,000,000 Ω, which the display shows as 1,000 MΩ or 1 GΩ.
The three current components
The current the tester measures is made up of three parts that change over time:
| Current | What causes it | Behaviour during the test |
|---|---|---|
| Capacitive charging current | Charging the capacitance of the cable or winding | High at first, falls away within seconds |
| Dielectric absorption current | Polarisation (slow alignment) of molecules in the insulation | Falls more slowly, over minutes |
| Conduction (leakage) current | Steady current through and over the insulation | Stays constant |
Why does insulation resistance increase with time?
In the first few seconds, charging and absorption currents add to the leakage current, so the total current is high and the calculated resistance looks low. As those two currents die away, only the steady leakage current is left, so the same voltage produces less current and the reading rises. On clean, dry insulation the reading keeps climbing for several minutes. On damp or dirty insulation, leakage current dominates early, so the reading stays low and flat. This difference is what PI and DAR tests measure.
Megger terminals and the guard terminal
| Terminal | Purpose |
|---|---|
| Line (L) | Carries the test voltage to the conductor or winding under test |
| Earth (E) | Connects to earth, the frame, the cable screen or the reference conductor |
| Guard (G) | Diverts surface leakage current away from the measurement so only the current through the insulation is read |
The guard terminal matters when damp or dirt on the surface of insulation (for example on a cable end or transformer bushing) would otherwise add leakage current and make the insulation look worse than it is. You wrap a bare conductor around the dirty surface and connect it to G. The surface current flows into the guard instead of through the meter, so the reading shows only the leakage through the insulation itself. Many everyday tests do not need the guard terminal, but it is useful when you are trying to tell surface contamination from real insulation deterioration.
Insulation resistance test voltage: how to choose
The correct test voltage depends on the equipment’s rated voltage, the standard being followed and the manufacturer’s instructions. As a general rule, the test voltage is a little above the working voltage of the circuit, but never above what the equipment is rated to withstand. Too high a voltage can stress or damage insulation, especially on older or sensitive equipment. Too low a voltage may not reveal faults.
| Equipment or circuit | Typical DC test voltage |
|---|---|
| SELV/PELV circuits | 250 V |
| Low-voltage circuits up to 500 V | 500 V |
| Circuits above 500 V | 1,000 V |
| Medium-voltage equipment | 1,000 V to 2,500 V |
| High-voltage equipment | 2,500 V to 5,000 V or higher |
For rotating machines, IEEE 43 gives test voltages by winding rating:
| Winding rated voltage | IEEE 43 insulation resistance test voltage (DC) |
|---|---|
| Below 1,000 V | 500 V |
| 1,000 V to 2,500 V | 500 V to 1,000 V |
| 2,501 V to 5,000 V | 1,000 V to 2,500 V |
| 5,001 V to 12,000 V | 2,500 V to 5,000 V |
| Above 12,000 V | 5,000 V to 10,000 V |
- 500 V megger: most 230 V and 400 V circuits, and motors rated below 1 kV.
- 1,000 V megger: circuits above 500 V, and cables and switchgear rated at 600 V to 1,000 V.
- 5 kV megger: medium- and high-voltage motors, generators, transformers and cables.
Types of insulation resistance test
| Test | How it is done | What it shows |
|---|---|---|
| Spot reading | One reading, usually after 1 minute | Insulation condition at that time, voltage and temperature |
| Time-resistance | Readings taken at intervals, often up to 10 minutes | How the reading rises; drying and contamination trends |
| Polarization index (PI) | 10-minute reading ÷ 1-minute reading | Moisture and contamination in windings |
| Dielectric absorption ratio (DAR) | 60-second reading ÷ 30-second reading | A quick version of PI |
| Step voltage | Voltage raised in steps, with the same time at each step | Weak insulation that fails at higher stress |
| Ramp voltage | Voltage raised smoothly while leakage current is monitored | Sudden leakage increases that point to defects |
Spot reading test
This is the standard test for building wiring and routine checks. Apply the test voltage, wait for the reading to settle (normally 1 minute), then record it with the voltage, temperature and time. It is quick, but it only gives a snapshot, so compare it with earlier results where you have them.
Polarization index (PI) test
PI = IR at 10 minutes ÷ IR at 1 minute. Because dirty or damp insulation leaks steadily from the start, its reading barely rises, so PI is close to 1. Clean, dry insulation keeps rising, giving a higher PI. Because both readings are taken in the same test, PI is much less affected by temperature than a single spot reading.
- Generally, a PI of 2.0 or above indicates good insulation.
- IEEE 43 minimum PI values reported in secondary guides: 1.5 for Class A insulation and 2.0 for Class B, F and H.
- PI is not meaningful when the 1-minute reading is already very high (above about 5,000 MΩ), because the leakage current is too small to measure reliably.
Dielectric absorption ratio (DAR) test
DAR = IR at 60 seconds ÷ IR at 30 seconds. It works like PI but takes only a minute, so it suits quick checks and smaller equipment. A DAR of 1.4 or above is generally considered good.
Step voltage and ramp voltage tests
In a step voltage test, you raise the voltage in equal steps (for example 500 V, 1,000 V, 1,500 V and so on), holding each step for the same time. Sound insulation gives roughly the same resistance at every step. A resistance that drops as voltage rises suggests a weakness. A ramp voltage test does the same job but raises the voltage smoothly while the instrument records leakage current. Both are specialist tests for high-voltage machines and need suitable instruments and the maker’s guidance.
How to carry out an insulation resistance test using a megger
You will need: a calibrated insulation resistance tester with the right voltage range and a suitable safety category rating (IEC 61010), test leads in good condition, an approved voltage indicator, a thermometer, lock-off devices and PPE.
- Plan the test. Identify the equipment, its rated voltage, the standard or specification to follow and the previous test results.
- Isolate and lock off. Switch off, isolate and apply your lock-out/tag-out (LOTO) procedure.
- Prove dead. Use an approved voltage indicator, proving it on a known source before and after.
- Disconnect sensitive equipment. Remove or isolate electronic devices, dimmers, drives, capacitors and surge protection devices, as they can be damaged or give false readings.
- Clean and dry accessible terminals. Record ambient and equipment temperature and humidity.
- Select the test voltage using the standard, rated voltage and manufacturer’s data.
- Connect the leads. Connect L to the conductor or winding and E to earth (or the frame, screen or second conductor). Add G where surface leakage could affect the result.
- Apply the voltage for the required time (1 minute for a spot reading, 10 minutes for PI) and do not touch the leads or equipment while testing.
- Record the results: reading, test voltage, time, temperature and connection used.
- Discharge the equipment (see the safety section), then verify it is discharged.
- Restore the equipment, remove locks and complete the test record.
Common connections
- Line to earth: a conductor or winding against earth, the frame or the screen. This is the main test for most equipment.
- Conductor to conductor: between phases, between windings or between circuits, with the other conductors earthed or left open as the procedure requires.
How to read a megger display
Digital testers show the resistance in kΩ, MΩ or GΩ, the test voltage actually applied and a timer. Many also show PI and DAR automatically. If the display shows “>” followed by a value (for example “>2 GΩ”), the insulation is better than the top of the instrument’s range, which is a good result. Always note the units: 500 kΩ is only 0.5 MΩ.
Insulation resistance testing by equipment type
Motors
Disconnect the motor leads from the starter, drive and cables first, as a drive can be damaged by the test voltage. Test each winding to the frame (earth), and between phases if the motor has six accessible leads. For a motor with a winding voltage below 1 kV, such as a 415 V motor, IEEE 43 gives 500 V DC as the test voltage. Record the winding temperature and run a PI test on larger motors. Compare against IEEE 43 limits (see the values section) and the motor’s previous records.
Generators
Test the stator and field windings separately, and disconnect the automatic voltage regulator, rotating rectifier and any other electronics from the field circuit first. Use the voltage that matches each winding’s rating under IEEE 43 and run a PI test. Typical problems are moisture after a long shutdown, oil and dust contamination and ageing insulation.
Transformers
Short together all the bushings of each winding, then test high-voltage winding to earth, low-voltage winding to earth, and high-voltage to low-voltage winding, with the other windings earthed. Record the oil or winding temperature, because it strongly affects the reading. ANSI/NETA gives minimum values by voltage class (see the values table), and IEEE 62.1 covers transformer diagnostic testing.
Cables
Disconnect both ends of the cable and discharge it. Test each core to earth (or the screen) with the other cores earthed, then core to core. Choose the voltage to suit the cable’s rating and the project specification. Long cables hold more charge, so the reading takes longer to settle and discharge takes longer. A megger test is a basic condition check. Medium- and high-voltage cables also use diagnostic methods such as very low frequency (VLF) testing, covered by the IEEE 400 series, which find defects an insulation resistance test can miss.
Switchgear and busbars
Insulation faults in switchgear often start with moisture, dust or tracking across supports. Test each phase to earth with the others earthed, and phase to phase. For circuit breakers, test with the breaker open (across the open contacts) and closed. Disconnect voltage transformers, surge arresters, control power transformers and electronic devices first. The same principles apply when you test a busbar, where insulating supports and barriers are the weak points. Where the maker gives no figures, ANSI/NETA provides minimum values. If you are unsure which assembly you are working on, see our guide to the types of switchgear panels, and note that different types of circuit breakers have different test connections.
House wiring and electrical installations
For a normal installation, BS 7671 and IEC 60364-6 require insulation resistance testing before an installation is put into service and during periodic inspection. With the circuit isolated:
- switch off and remove lamps and disconnect appliances and electronic equipment
- test between the live conductors (line and neutral) and between each live conductor and earth, which is usually done by linking line and neutral together and testing to earth
- if surge protection devices or other equipment cannot be disconnected, BS 7671 allows the test voltage to be reduced to 250 V DC, but the reading must still be at least 1 MΩ
Leave connected surge protection devices out of the test where you can, because they are designed to conduct at high voltages.
Solar PV systems
PV insulation testing finds damaged cable insulation, water ingress and module faults before they become earth faults or fire risks. IEC 62446-1 sets the test voltage by array voltage and requires testing between the positive and earth, and negative and earth. A PV array produces voltage in daylight and cannot be switched off like an ordinary circuit, so use the PV-specific method and equipment, and follow the inverter manufacturer’s isolation guidance. Do not short-circuit an array unless the procedure and equipment are designed for it.
| PV array voltage | Test voltage (DC) | Minimum resistance |
|---|---|---|
| Below 120 V | 250 V | 0.5 MΩ |
| 120 V to 500 V | 500 V | 1 MΩ |
| 500 V to 1,000 V | 1,000 V | 1 MΩ |
| Above 1,000 V | 1,500 V | 1 MΩ |
Insulation resistance values and acceptance criteria
There is no single “good” insulation resistance for all equipment. The correct limit depends on the equipment, its voltage, its age, the temperature and the standard in use. There are two ideas to keep apart: the minimum acceptable value (below this, the equipment should not be energised or needs investigation) and a healthy value (what good equipment normally reads, often far higher than the minimum). New, clean equipment usually reads hundreds or thousands of megohms.
| Equipment | Test voltage | Minimum resistance | Standard |
|---|---|---|---|
| SELV/PELV circuits | 250 V | 0.5 MΩ | BS 7671 / IEC 60364-6 |
| LV circuits up to 500 V | 500 V | 1.0 MΩ | BS 7671 / IEC 60364-6 |
| Circuits above 500 V | 1,000 V | 1.0 MΩ | BS 7671 / IEC 60364-6 |
| Motors: random-wound, or form-wound below 1 kV | Per winding rating | 5 MΩ at 40 °C | IEEE 43 |
| Motors: form-wound, made after about 1970 | Per winding rating | 100 MΩ at 40 °C | IEEE 43 |
| Motors: windings made before about 1970 | Per winding rating | Rated kV + 1 MΩ at 40 °C | IEEE 43 |
| Transformer 0 to 600 V | 1,000 V | 100 MΩ liquid-filled; 500 MΩ dry | ANSI/NETA |
| Transformer 601 V to 5 kV | 2,500 V | 1,000 MΩ liquid-filled; 5,000 MΩ dry | ANSI/NETA |
| Transformer above 5 kV | 5,000 V | 5,000 MΩ (check the NETA table for liquid-filled and dry types) | ANSI/NETA |
| Switchgear/bus rated 250 V | 500 V | 25 MΩ | ANSI/NETA |
| Switchgear/bus rated 600 V to 1,000 V | 1,000 V | 100 MΩ | ANSI/NETA |
| PV arrays | 250 V to 1,500 V | 0.5 MΩ to 1 MΩ | IEC 62446-1 |
For cables there is no single value that fits every cable, because resistance falls with length and depends on the insulation type. Compare against the commissioning result, the project specification and previous tests on the same cable.
The 1 MΩ per kV rule
This is an old rule of thumb for motors: minimum insulation resistance (MΩ) = rated voltage in kV + 1. A 415 V motor gives 0.415 + 1 ≈ 1.4 MΩ, and an 11 kV motor gives 12 MΩ.
It is not a universal pass mark. It is much lower than the limits in current IEEE 43 for most modern windings, it ignores temperature, and it says nothing about trends. Use it only as a historical guide for old windings and let the equipment standard and manufacturer’s data take priority.
Worked examples
Example data for learning only, not measurements from a real asset.
1. Basic insulation resistance. A tester applying 500 V reads 2 µA. R = 500 ÷ 0.000002 = 250,000,000 Ω = 250 MΩ.
2. DAR and PI. A motor winding reads 200 MΩ at 30 seconds, 320 MΩ at 60 seconds (1 minute) and 800 MΩ at 10 minutes.
DAR = 320 ÷ 200 = 1.6
PI = 800 ÷ 320 = 2.5
Both are above the commonly quoted “good” levels of 1.4 and 2.0. For a real machine, compare with IEEE 43 and the maker’s limits.
3. Temperature correction. A winding reads 120 MΩ at 30 °C. Using the 40 °C correction (explained next): KT = 0.5(40−30)/10 = 0.5, so R₄₀ = 120 × 0.5 = 60 MΩ.
Temperature, humidity and other factors that affect readings
| Factor | Effect on the reading |
|---|---|
| Temperature | Hotter insulation reads lower |
| Humidity and moisture | Lowers the reading, especially through surface films |
| Dust and contamination | Creates surface leakage paths |
| Insulation ageing | Gradual fall over the years |
| Mechanical or chemical damage | Local weak points and lower readings |
| Test voltage and duration | Different voltages and times give different readings, so always record both |
Temperature correction
Insulation resistance falls as temperature rises, roughly halving for every 10 °C increase. To compare readings taken at different temperatures, IEEE 43 corrects them to a standard 40 °C. The commonly used approximation is:
R₄₀ = Rₜ × 0.5(40 − T) ÷ 10
where Rₜ is the reading at winding temperature T in °C. A winding measured below 40 °C reads higher than it would at 40 °C, so the corrected value is lower. A reading taken above 40 °C is corrected upwards. Use a correction factor (KT) from the table below:
For formal reports on rotating machines, use the exact correction method in IEEE 43 or the one built into your tester, rather than the rule of thumb alone.
Humidity and moisture
Moisture can sit inside the insulation or form a film on its surface. Surface moisture usually improves once the surface is cleaned and dried, and a guard terminal can help show how much of the leakage is on the surface. Moisture inside windings is more serious and usually needs controlled drying. Always record humidity, and avoid testing equipment at or below the dew point, where condensation forms on cold surfaces.
Safety precautions and discharging
Never use a megger on a live circuit. It can damage the instrument and cause serious shock or injury. The tester itself produces hazardous voltage, so treat the leads and the equipment as live while the test runs.
- Isolate, lock off and prove the circuit dead before connecting.
- Use a tester and leads with a suitable IEC 61010 measurement category rating, and check the leads for damage first. IEC 61557-2 expects at least CAT III for instruments used on distribution systems.
- Disconnect or protect electronics, capacitors and surge protection devices.
- Keep clear of the leads and equipment during the test, and stop others touching them.
- Wear the PPE required by the site and follow the manufacturer’s instructions and local regulations.
- Discharge, and verify discharge, before touching anything.
Why discharging matters
Cables and windings act like capacitors. During the test they store charge at the test voltage, and they can hold it long after the tester is switched off. Touching them can then give a dangerous shock, and the stored charge can also damage the next instrument connected.
- Leave the leads connected after the test and let the tester discharge the equipment through its internal discharge path.
- Keep discharging for at least as long as the voltage was applied, and longer for long cables and large windings, as set out by the maker’s instructions.
- Check the tester’s voltage display, then confirm with an approved voltage indicator that the equipment is at zero volts.
- Only then disconnect the leads and handle the equipment.
Common causes of low insulation resistance
| Cause | Typical sign | What to do |
|---|---|---|
| Moisture or water ingress | Low, flat reading; low PI; improves on drying | Dry the equipment by an approved method and retest |
| Dirt, dust or chemical contamination | Reading changes when the guard terminal is used or after cleaning | Clean the surfaces and retest |
| Overheating or ageing | Readings that fall steadily from test to test | Investigate the cause; plan repair or replacement |
| Cracked, cut or damaged insulation | Sudden low reading or one weak phase or core | Inspect, repair or replace the damaged part |
| Poor connections or fault in a connected device | Reading differs when parts are disconnected | Disconnect parts one by one to find the fault |
After any cleaning, drying or repair, retest and compare the new result with earlier records. Keeping the history is what turns a single number into useful information.
Insulation resistance test vs other electrical tests
| Test | Main purpose | Voltage or signal | Can it damage insulation? |
|---|---|---|---|
| Insulation resistance | Measures leakage resistance of insulation | DC, typically 250 V to 5 kV or more | Non-destructive at normal test voltages |
| Hipot (withstand) | Checks dielectric withstand strength | Much higher AC or DC stress | Can damage insulation that is already weak |
| Continuity | Checks that a conductor path is complete | Low voltage and current | No |
| Earth resistance | Measures the resistance of an earth electrode | Dedicated earth tester | No |
| Partial discharge | Detects local discharge activity in insulation | Specialist excitation and detection | No |
- Insulation resistance vs hipot: an IR test tells you the insulation’s condition. A hipot test proves it can survive a specified overvoltage. They are not interchangeable.
- Insulation resistance vs continuity: continuity checks for a good, low-resistance path in the conductor. IR checks for unwanted leakage through the insulation around it.
- Insulation resistance vs earth resistance: earth resistance tests the electrode that connects your installation to the ground, so a megger cannot do it. See types of earthing systems and earthing vs grounding for more on earthing.
- Protection devices: IR testing checks insulation, not whether protection will operate. That is covered by relay testing.
How often should you test insulation resistance?
There is no single interval for every asset. Test at these times:
- Commissioning: before an installation or machine is first energised.
- Routine maintenance: at intervals set by the maker, your insurer, ANSI/NETA (where it applies) and site policy. For wiring in the UK, periodic inspection intervals depend on the type of installation and its use.
- After events: repairs, flooding, moisture exposure, overheating, a fault, or a long shutdown.
Test critical or ageing equipment more often, and always at the same temperature, voltage and duration so the results can be compared. Where several protection devices rely on healthy insulation, remember that good protection coordination does not replace regular insulation testing.
Insulation resistance test report and checklist
| Field | Record |
|---|---|
| Asset ID and location | e.g. Pump motor M-12, Plant room 2 |
| Rated voltage | e.g. 415 V |
| Test voltage and duration | e.g. 500 V DC, 10 minutes |
| Connection used | e.g. U-V-W to frame, guard not used |
| Ambient temperature, humidity, winding temperature | e.g. 22 °C, 55%, 30 °C |
| Readings: 30 s, 1 min, 10 min | e.g. 200 MΩ, 320 MΩ, 800 MΩ |
| DAR and PI | e.g. 1.6 and 2.5 |
| Corrected value at 40 °C and method used | e.g. 160 MΩ (IEEE 43 correction) |
| Applicable standard and limit | e.g. IEEE 43, 5 MΩ minimum |
| Instrument make, serial number, calibration date | As on the calibration certificate |
| Discharge confirmed | Yes / No |
| Result and tester’s name | Pass / investigate, signature, date |
Testing checklist
- ☐ Equipment, rated voltage and standard identified
- ☐ Isolated, locked off and proved dead
- ☐ Electronics, SPDs and capacitors disconnected
- ☐ Tester checked, in calibration, with the correct voltage selected
- ☐ Temperature and humidity recorded
- ☐ Readings and times recorded
- ☐ Equipment discharged and verified at zero volts
- ☐ Equipment restored, locks removed, report completed
Common megger testing mistakes
- Choosing the wrong test voltage
- Testing without proper isolation, or without proving dead
- Leaving electronic devices and surge protection connected
- Ignoring temperature and humidity
- Recording a number without the voltage, duration and connection
- Confusing continuity with insulation resistance
- Not using the guard terminal when surface leakage matters
- Skipping discharge
- Using one pass mark for every type of equipment
- Ignoring previous results and trends
Testing a motor specifically? Our guide to megging a motor covers 480 V test values, temperature correction, polarization index and what to do with the result.
Frequently asked questions
What is a megger used for?
It measures insulation resistance on cables, windings, circuits and equipment to check the insulation is in good condition and safe to energise.
What is the working principle of a megger?
It applies a DC test voltage across the insulation, measures the small leakage current and calculates resistance using R = V ÷ I.
What is a good insulation resistance reading?
It depends on the equipment and standard. New, clean equipment usually reads hundreds or thousands of megohms. Judge a reading against the applicable limit, the temperature and previous results, not against a single number.
What is the minimum acceptable insulation resistance?
For UK installations under BS 7671, 1.0 MΩ for most circuits and 0.5 MΩ for SELV and PELV circuits. Motors, transformers and switchgear have their own minimums (see the values table).
What voltage should be used for a 415 V motor megger test?
500 V DC. IEEE 43 recommends 500 V for windings rated below 1,000 V.
What is the difference between a 500 V and a 1000 V megger?
The maximum test voltage. A 500 V tester suits circuits up to 500 V, while a 1,000 V tester is used for circuits above 500 V and for equipment rated at 600 V to 1,000 V.
Can you perform a megger test on a live circuit?
No. The circuit must be isolated, locked off and proved dead first.
Why does insulation resistance decrease with temperature?
Heat makes insulation conduct more easily, so more current leaks. As a rule of thumb, resistance roughly halves for every 10 °C rise.
Why does megger resistance increase over time?
Charging and absorption currents fade as the test continues, leaving only the steady leakage current, so the calculated resistance rises.
What is the difference between PI and DAR?
PI compares the 10-minute and 1-minute readings. DAR compares the 60-second and 30-second readings. PI gives a fuller picture; DAR is quicker.
What is a good polarization index value?
2.0 or above is generally good. IEEE 43 minimums are reported as 1.5 for Class A and 2.0 for Class B, F and H insulation.
What is the purpose of the guard terminal?
It diverts surface leakage current away from the measuring circuit so the reading shows only the leakage through the insulation.
How long should you perform a megger test?
One minute for a spot reading on most circuits, and 10 minutes for a PI test on a motor or generator winding.
How long should you discharge a cable after a megger test?
There is no single fixed time. A common practice is to discharge for at least as long as the voltage was applied, and longer for long cables. Always confirm zero volts before touching.
Can a megger damage electrical equipment?
Yes, if the voltage is too high for the equipment or electronics are left connected. Choose the voltage carefully and disconnect sensitive devices.
How often should insulation resistance testing be performed?
At commissioning, at routine intervals set by the maker or standard, and after repairs, faults, flooding or long shutdowns.
What is the difference between a megger and a multimeter?
A megger applies a high DC voltage to measure insulation resistance in megohms. A multimeter uses a low voltage and cannot properly test insulation.
What causes low insulation resistance?
Moisture, dirt, ageing, overheating, chemical attack and physical damage to the insulation.
Conclusion
An insulation resistance test is one of the quickest ways to find weak insulation before it causes a fault. The result is only as good as the preparation behind it: choose the correct test voltage, isolate and prove dead, disconnect sensitive equipment, record temperature, and discharge before touching anything. Then judge the reading against the standard for that equipment (BS 7671 for UK wiring, IEEE 43 for motors and generators, ANSI/NETA for transformers and switchgear, IEC 62446-1 for solar PV) and against your own previous results. A falling trend is often the earliest warning. Always check limits against the current standard and the manufacturer’s instructions before you sign off a test.