Wye-Wye Transformer vs Delta-Wye: Distribution Trade-Offs

By editor 5 min read
Wye-wye transformer symbol with zero degree shift above a delta-wye symbol with thirty degree shift

A wye-wye transformer has both windings connected in wye, with no phase shift and a neutral on each side, while a delta-wye transformer has a delta primary and a 30° phase shift. Delta-wye is the usual choice for building and plant distribution because its delta winding gives triplen harmonic current a closed path. Wye-wye can work well, but it normally needs a solidly grounded primary neutral or a tertiary delta winding.

FactorWye-wyeDelta-wye
Phase shift0° (Yy0)30°
Primary neutralAvailable, normally groundedNone
Secondary neutralAvailableAvailable
Triplen currentNeeds a grounded neutral path or tertiaryCirculates in the delta
Primary winding voltageLine voltage ÷ √3Full line voltage
Typical useUtility, solar and battery step-upCommercial and industrial supply
Wye-wye vs delta-wye at a glance.
Safety first: Never parallel transformers with different phase shifts, and never change a transformer’s neutral bonding without an engineering review. Isolate and prove dead using your lockout/tagout procedure before working on connections.
0°
Yy0 phase shift
30°
Delta-wye shift
57.7%
Wye winding vs line voltage
26:1
Example Yy turns ratio

How the Two Connections Differ

Wye-wye and delta-wye connectionsA wye-wye transformer has a neutral on both sides and zero phase shift. A delta-wye transformer has a delta high-voltage winding, a wye low-voltage winding and a thirty degree shift.The two connections comparedWye-wye (Yy0)HVLV0° shiftNeutral available on both sidesDelta-wyeHVLV30° shiftDelta gives triplen current a closed pathIndustrialBasicsindustrialbasics.com
Figure 1: The connection sets the phase shift, grounding and harmonic behavior.

In a wye-wye transformer, each winding is connected from a line to a neutral point on both sides. Because the windings see the same phase relationship, there is no angular displacement in a standard Yy0 unit. In a delta-wye transformer, each primary coil connects line to line, which creates a 30° shift. Our guide to transformer vector groups explains the notation.

Worked Example: 225 kVA, 12.47 kV to 480Y/277 V

QuantityWye-wyeDelta-wye
HV line current10.4 A10.4 A
HV coil voltage7,200 V12,470 V
HV coil current10.4 A6.0 A
LV coil voltage277 V277 V
LV line current270.6 A270.6 A
Turns ratio per phase26.0:145.0:1
Same rating and line voltages, different coil conditions.

The line currents match, but the coils do not. A wye primary coil sees 7,200 V, about 57.7% of line voltage, while a delta coil sees the full 12,470 V. That lower coil voltage is a key attraction of wye windings at high voltage. The delta coil carries less current, at 6.0 A instead of 10.4 A. For the formulas, see our guide to electrical 3 phase calculations.

Third Harmonics: The Main Trade-Off

A transformer’s magnetizing current is not a pure sine wave. It includes triplen harmonics, which are in phase across all three phases and so need a path that a normal three-phase line does not offer.

ConnectionTriplen pathResult
Delta-wyeCirculates in the closed deltaContained in the transformer
Wye-wye with grounded source neutralThrough the neutralCurrent can flow, but it enters the supply system
Wye-wye with tertiary deltaCirculates in the tertiaryContained in the transformer
Wye-wye with no neutral pathBlockedThird-harmonic voltage can appear phase to neutral
How each arrangement handles triplen harmonics.

Core construction also matters. Voltage Disturbance notes that three-leg cores tend to have lower third-harmonic voltage than shell and four- or five-limb cores. For the wider effects of distortion, see our guide to power quality problems.

Grounding and Fault Behavior

IssueWye-wyeDelta-wye
Zero-sequence currentCan pass through when both neutrals are groundedBlocked from the primary lines
Secondary ground faultsCan be seen by upstream ground relaysNot seen as ground current upstream
Unbalanced line-to-neutral loadNeeds a stable neutral referenceDelta supports the unbalance
Primary neutralGrounding must be coordinated with the utilityNot applicable
Grounding and fault differences.

If a wye-wye secondary neutral floats on a system with mixed loads, the neutral can shift and put damaging voltage on some loads. Follow the required system grounding, and review protection coordination whenever the transformer connection changes.

Which Should You Choose?

Wye-wye or delta-wye selectionDelta-wye is the usual general supply choice. Wye-wye suits a utility grounded-wye primary. Without a grounded primary neutral, avoid plain wye-wye or add a tertiary delta.Which connection should you specify?Choosing a distributiontransformerGeneral building or plant supplyDelta-wye is the usual choiceUtility requires a grounded-wye primaryWye-wye with the required groundingNo grounded primary neutral availableAvoid plain wye-wye, or add a tertiary deltaIndustrialBasicsindustrialbasics.com
Figure 2: Confirm the arrangement with the utility and transformer maker.
Wye-wye is suited toDelta-wye is suited to
Utility systems with a grounded-wye sourceCommercial and industrial building supply
Some solar and battery step-up designsLoads with line-to-neutral circuits
Applications needing no phase shiftSites without a grounded primary neutral
High-voltage winding insulation savingsNon-linear loads with triplen harmonics
Typical applications. The design must match the utility and project requirements.

If you are replacing a unit, match its vector group unless an engineer has reviewed the change. A mismatch can prevent paralleling and upset protection. See our overview of types of transformers for other options.

Safety note: This guide is educational. Transformer selection, grounding and protection should be designed by a qualified engineer and coordinated with the utility.

Frequently Asked Questions

What is a wye-wye transformer?

It is a three-phase transformer with both its high-voltage and low-voltage windings connected in wye. Each side has a neutral point.

Does a wye-wye transformer have a phase shift?

A standard Yy0 connection has no phase shift between the primary and secondary. A delta-wye transformer has a 30° shift.

Why is delta-wye more common than wye-wye?

The delta winding gives triplen harmonic current a closed path and helps stabilize the secondary neutral, without relying on a grounded primary neutral.

What is the main problem with a wye-wye transformer?

Without a suitable path for triplen current, such as a grounded primary neutral or tertiary delta, it can have third-harmonic voltage and neutral instability.

Should the primary neutral of a wye-wye be grounded?

Wye-wye units normally rely on a solidly grounded source neutral. Follow the utility requirements and the transformer manufacturer’s instructions.

What is a tertiary winding?

It is a third winding, commonly connected in delta, that provides a path for triplen currents in a transformer that would otherwise lack one.

Can wye-wye and delta-wye transformers be paralleled?

No. They have different phase shifts, so paralleling them would drive large circulating currents.

Where are wye-wye transformers used?

They are used in utility systems and some solar and battery step-up applications where a grounded source is available and the design calls for it.

Sources and Further Reading

About the author

editor

Leave a Comment