208V Single Phase: How It Works, Wiring and Calculations

By editor Updated 5 min read
Three-phase phasor diagram with 120 volt legs A and B, 120 degrees apart, and 208 volts between them

208V single phase comes from connecting a load across two legs of a three-phase 120/208 V wye system. Each leg is 120 V to neutral, but the legs are 120° apart, so the voltage between them is 120 × √3 ≈ 208 V. A straight 208 V load normally uses a two-pole breaker, two hot conductors and an equipment grounding conductor. It needs a neutral only if it also has 120 V circuits.

Measurement on 120/208 V wyeNominal voltage
A to neutral120 V
B to neutral120 V
C to neutral120 V
A to B208 V
B to C208 V
C to A208 V
Nominal voltages on a 208Y/120 V system.
Safety first: Only qualified people should open panels or take live measurements. Isolate the circuit, follow your lockout/tagout procedure, and prove it dead before wiring.
208 V
Between two legs
120°
Angle between legs
75%
Heater output vs 240 V
2-pole
Breaker for 208 V

Why Two Legs Make 208 V

Phasors for 208 V wye and 240 V split-phaseTwo 120 volt legs 120 degrees apart produce 208 volts between them. Two 120 volt legs 180 degrees apart produce 240 volts.Why two legs give 208 V instead of 240 VWye: legs 120° apart120 VA to B = 120 × √3 = 208 VSplit-phase: legs 180° apart120 VL1 to L2 = 120 + 120 = 240 VIndustrialBasicsindustrialbasics.com
Figure 1: The angle between the legs sets the voltage between them.

In a wye (star) connection, the three phase windings meet at a neutral point. Their voltages are 120° apart, so the voltage between any two legs is the phase voltage multiplied by √3.

VLL = 120 V × 1.732 ≈ 208 V

A residential split-phase service is different. Its two 120 V legs come from a center-tapped winding and are 180° apart, so they add directly to 240 V. A 208 V supply cannot be turned into 240 V by changing the conductors. The source is usually the secondary of a delta-wye transformer.

How to Wire 208V Single Phase

208 V single-phase circuitA two-pole breaker feeds legs A and B to a 208 volt load with an equipment grounding conductor. A neutral is added only if the equipment has 120 volt circuits.Wiring a straight 208 V single-phase load120/208 V panelThree-phase wye2-polebreakerLeg ALeg BEquipment grounding conductorNeutral only if the load uses 120 V208 V loadAcross legs A and BIndustrialBasicsindustrialbasics.com
Figure 2: Conductor colors and sizing must follow the code and local practice.
PartStraight 208 V load208 V load with 120 V controls
Breaker2-pole2-pole
Hot conductors22
NeutralNot neededRequired
Equipment groundRequiredRequired
Conductors for a single-phase 208 V circuit.

Size the conductors and protection for the load using the applicable code. Our guides to AWG wire ampacity, ground wire size and circuit breakers can help. Do not use white or gray conductors as the hot legs.

Calculating 208V Single-Phase Current

A load connected across two legs is still a single-phase load, so do not use the √3 factor.

I = P ÷ (V × PF)
LoadCalculationCurrent
5 kW resistive5,000 ÷ 20824.0 A
3 kW resistive3,000 ÷ 20814.4 A
2 kW at 0.85 PF2,000 ÷ (208 × 0.85)11.3 A
Single-phase current at 208 V.

For loads connected across all three phases, use our electrical 3 phase calculations guide instead.

208 V vs 240 V Equipment

Always start with the nameplate. Equipment marked 208-230 V or 208/240 V is designed for the lower voltage. Equipment rated only for 240 V may underperform or fail to run correctly on 208 V.

Nameplate voltage208 V as a share of nameplateWhat it means
200 V104.0%Motor rating intended for 208 V systems
208 V100%Matched
230 V90.4%Close to a −10% limit, so little margin for voltage drop
240 V86.7%Below a −10% limit
Calculated from nominal voltages. Actual voltage at the equipment may be lower.

Worked example: 240 V heater on 208 V

A resistive heater has a fixed resistance, so power falls with the square of voltage. A 5,000 W, 240 V element has a resistance of 240² ÷ 5,000 = 11.52 Ω.

P = 208² ÷ 11.52 = 3,756 W

That is about 75% of rated output, at about 18.1 A. A water heater or oven with this element would still work, but it would heat more slowly. Check that the manufacturer allows operation at 208 V.

Reader tip: Motors behave differently from heaters. A motor run below its rated voltage may draw more current and run hotter, so use a motor rated for the supply and check it with the nameplate. See our guide to full load amps.

Balancing Single-Phase Loads

Balancing 208 V loadsThree single-phase loads connected across A-B, B-C and C-A form a balanced arrangement when they are equal.Rotate loads across the three leg pairsABCLoad 1: A-BLoad 2: B-CLoad 3: C-AIndustrialBasicsindustrialbasics.com
Figure 3: Three equal loads of 10 A each draw about 17.3 A per line.

If every 208 V load is connected across A and B, those phases carry more current than C. Rotate circuits across A-B, B-C and C-A to spread the load. When three equal loads are connected this way, they form a balanced delta. Three 10 A loads draw 10 × 1.732 = 17.3 A in each line conductor.

Safety note: This guide is educational. Use the applicable electrical code, equipment nameplate and manufacturer instructions for any installation.

If you are choosing equipment for either supply, see our comparison of 208 vs 240 volt systems, including ANSI ranges and heater output.

Frequently Asked Questions

Is 208V single phase or three phase?

A 208Y/120 V supply is three-phase. A load connected across only two of its legs is a single-phase 208 V load.

How do you get 208V single phase?

Connect the load between two phase conductors of a 120/208 V wye system, using a two-pole breaker.

Does 208V single phase need a neutral?

Not for a load that uses only 208 V. It needs two ungrounded conductors and an equipment grounding conductor. Add a neutral if the equipment has 120 V circuits.

Why is it 208 V and not 240 V?

The two 120 V legs are 120° apart, so the voltage between them is 120 × √3, or about 208 V. On a split-phase system they are 180° apart and add to 240 V.

Can I run 240 V equipment on 208 V?

Only if the nameplate or manufacturer allows it. Dual-rated 208-230 V equipment is designed for this. Equipment rated only for 240 V should be checked or re-specified.

How much power does a 240 V heater lose on 208 V?

A resistive heater produces about 75% of its rated power, because power varies with the square of voltage. A 5,000 W heater gives about 3,756 W.

What breaker is used for 208V single phase?

A two-pole breaker across the two legs. Size it for the load and conductors using the applicable code.

How do I balance 208V single-phase loads?

Spread them across the A-B, B-C and C-A leg pairs so each phase carries a similar current.

Sources and Further Reading

About the author

editor

Leave a Comment