Short answer. Electrical safety PPE is the protective equipment that limits injury from the two main electrical hazards: electric shock and arc flash. They need different kit. Rubber insulating gloves (worn under leather protectors), insulating sleeves and mats guard against shock. Arc-rated clothing, a face shield or hood, safety glasses and hearing protection guard against arc flash burns and blast. A Class E safety helmet and electrical hazard footwear add head and foot protection. What you need depends on a task-specific risk assessment, the voltage and the incident energy. PPE is the last line of defence: make the equipment dead, isolate it and prove it dead first.
Electrical work can hurt you in several ways at once: current through the body (shock), a burst of heat and light (arc flash), a pressure wave (arc blast), burns, and flying metal and debris. No single item of PPE covers all of them. This guide explains which equipment protects against which hazard, how to choose and check it, and which rules and standards apply in the US, UK and India.
What electrical safety PPE protects against
Electric shock
Electric shock happens when current passes through your body, usually after you touch a live part or a conductor that has become live. It can cause burns, muscle lock, heart problems and falls. Typical causes are exposed live parts, damaged insulation, wet conditions and faulty tools. The path current takes also depends on the installation’s earthing system.
Insulating PPE (rubber gloves, sleeves, mats) puts a rated barrier between you and the live part. Low voltage is not safe by default: HSE warns that a shock can cause serious or fatal injury even when an RCD is fitted.
Arc flash
An arc flash is a sudden release of heat and light when current jumps through air between conductors, or from a conductor to earth. A dropped tool, dust, moisture, worn insulation or a switching error can start one. You do not need to touch anything to be hurt. The arc core is commonly quoted at up to about 35,000°F (around 19,400°C), and as little as 1.2 calories per square centimetre (cal/cm²) can cause a second-degree burn on bare skin.
The risk is highest around switchgear and busbars. Arc-rated clothing and face protection reduce the heat reaching your skin. For causes, boundaries and incident energy, see our full guide to arc flash.
Arc blast
An arc blast is the pressure wave from the same event. Heated air and vaporised metal expand violently, throwing molten droplets and debris with a very loud bang. Injuries include blast trauma, shrapnel wounds, hearing damage and falls. A face shield or hood, safety glasses and hearing protection reduce exposure.
Electrical burns and secondary injuries
Current can burn tissue along its path, so internal damage can be worse than the skin suggests. Arcs also ignite clothing, and melting synthetic fabric deepens burns. Eyes face flash and flying particles, and ears face blast noise. Protection must therefore cover the head, face, eyes, ears, body, arms, hands and feet, not just the hands.
Why electrical safety PPE matters
Used correctly, PPE reduces how badly you are hurt when a control fails. It also helps an employer show that it assessed the risk and provided suitable protection. The US figures below show how serious the problem still is.
- The US Bureau of Labor Statistics recorded 142 worker deaths from exposure to electricity in 2023 and 130 in 2024.
- ESFI counts 2,070 workplace electrical deaths between 2011 and 2024.
- Non-fatal electrical injuries that kept workers off work totalled 5,180 across 2023 and 2024 combined, up 59% on the previous two years (ESFI, from BLS data).
Two lessons follow. First, many victims were not electricians, so electrical hazard training matters well beyond the electrical trade. Second, PPE does little against an overhead line strike. Planning, clearance distances and isolation do. That is why PPE sits last in the hierarchy of controls.
Safety first: the hierarchy of controls and de-energisation
What is the hierarchy of controls?
The hierarchy ranks safety measures from most to least effective. Always start at the top.
Why PPE is the last line of defence
PPE does not remove the hazard. It only reduces harm if something goes wrong, and only if it is the right type, fits, is undamaged and is worn. HSE describes PPE as a last line of defence where risk cannot otherwise be eliminated or controlled. Higher controls protect everyone nearby, not just the wearer. Examples include faster-acting protection such as the right fuse or circuit breaker, well-set protection coordination that clears faults quickly, and regular relay testing so protection trips when it should.
De-energisation, lockout/tagout and isolation
The safest electrical work is done dead. In the UK this means isolation, lock-off and proving dead. In the US it is called lockout/tagout (LOTO). The steps are the same in principle:
- Switch off and isolate every source of supply.
- Lock off and tag the isolation point so nobody can re-energise it.
- Test with a suitable instrument that you have proved works, then prove it again.
- Only then start work, still alert to stored energy and other hazards.
HSE says supplies should be made dead and proved dead before work starts, with isolation that prevents re-energisation. Our lockout/tagout procedure guide covers the process in detail.
When can live work be considered?
Rarely. HSE says live work is acceptable only after it has been decided that working dead is unreasonable. Under the Electricity at Work Regulations 1989, HSG85 sets three conditions that must all be met. If any one fails, work dead. In the US, NFPA 70E expects energised work to be justified and, where required, permitted.
PPE does not make live work safe. HSE states plainly that it is never absolutely safe to work on live electrical equipment. Live work needs specific justification, a written procedure and qualified people. PPE reduces the harm if something goes wrong. It is not permission to work live.
Shock protection vs arc flash protection
Many articles blur this point, and mixing the two causes real injuries. Shock PPE and arc flash PPE do different jobs and cannot replace each other.
Shock protection PPE
It stops current passing through your body. It includes rubber insulating gloves, insulating sleeves, mats and blankets, and dielectric overshoes. Selection depends on voltage and the shock risk.
Arc flash protection PPE
It limits the thermal energy reaching your skin. It includes arc-rated clothing, face shields, balaclavas, hoods and arc flash suits. Selection depends on the assessed arc flash exposure.
| Comparison | Shock protection | Arc flash protection |
|---|---|---|
| Main hazard | Current through the body | Thermal burns, plus blast, light and noise |
| Main purpose | Stop current passing through you | Reduce the heat reaching your skin |
| Main equipment | Rubber gloves, sleeves, mats, dielectric overshoes | Arc-rated clothing, face shield or hood, balaclava, suit |
| Selection basis | Voltage and shock risk | Incident energy and hazard assessment |
| Key standards | ASTM D120, ASTM F496, IEC 60903 | ASTM F1506, ASTM F1959, ASTM F2178, NFPA 70E |
| Important limit | Gives no arc flash heat protection | Gives no shock insulation |
Can one type of PPE protect against both?
No. Rubber insulating gloves are tested for insulation, not for arc heat. Arc-rated clothing resists heat, not current. On the same live task you may need both, chosen so they work together. Never assume that one set of PPE covers the other hazard.
Electrical safety PPE checklist
Use this as a quick reference. The final list depends on your task risk assessment.
| PPE item | Main protection | Hazard |
|---|---|---|
| Rubber insulating gloves | Electric shock | Shock |
| Leather protector gloves | Protect rubber gloves from cuts and punctures | Shock (support) |
| Insulating sleeves | Arm and shoulder contact with live parts | Shock |
| Insulating mats and blankets | Contact with live parts or earth | Shock |
| Insulated tools | Reduce accidental contact | Shock |
| Arc-rated clothing | Arc flash heat | Arc flash |
| Arc flash suit | Higher arc flash exposure | Arc flash |
| Arc-rated face shield | Face protection | Arc flash |
| Arc-rated balaclava or hood | Head and neck | Arc flash |
| Electrical safety helmet (Class E) | Head impact and electrical contact | Both |
| Safety glasses | Flying particles and debris | Both |
| Hearing protection | Blast noise | Arc flash |
| Electrical hazard footwear | Secondary protection against live-circuit contact | Shock |
Insulating mats, blankets and tools are work equipment rather than wearable PPE in some frameworks, but they appear on the same task plan, so they are listed here.
Shock protection PPE: gloves, sleeves and footwear
Rubber insulating gloves
Rubber insulating gloves are the main shock protection when hands may touch live parts. Choose the class from the highest voltage that could be present and check the class marking. OSHA 1910.137 requires inspection before each day’s use, with an air test for gloves. Limits: they give no arc flash heat protection, and ozone, oil, heat, cuts and punctures degrade them.
Glove classes and voltage ratings
Gloves are sorted into six classes by maximum use voltage. Values below are AC rms from OSHA Table I-4, checked on 9 November 2026. DC maximums are higher. Re-verify against the current OSHA table or ASTM D120 before you rely on them.
| Class | Maximum use voltage (AC rms) | What to check |
|---|---|---|
| 00 | 500 V | Marked class, test date, system voltage |
| 0 | 1,000 V | Marked class, test date, system voltage |
| 1 | 7,500 V | Marked class, test date, system voltage |
| 2 | 17,000 V | Marked class, test date, system voltage |
| 3 | 26,500 V | Marked class, test date, system voltage |
| 4 | 36,000 V | Marked class, test date, system voltage |
Which class for 480 V? On voltage alone, both Class 00 (500 V) and Class 0 (1,000 V) cover a 480 V system. Many sites choose Class 0 for margin, which is good practice rather than a rule. Always compare the maximum use voltage with the highest voltage that could appear, then follow your risk assessment.
Leather protector gloves
Leather protectors go over the rubber gloves to guard against cuts, punctures and abrasion. OSHA requires them, with limited exceptions, and says gloves used without protectors must be tested before reuse. Ordinary leather work gloves are not a substitute. Use protectors made for the job (ASTM F696 in the US) that fit snugly without bunching.
Insulating sleeves
Sleeves protect the arms and shoulders when you reach into equipment where bare arms could touch live parts. OSHA’s retest interval for sleeves is 12 months, plus the usual triggers. Inspect them before each day’s use.
Dielectric boots and electrical hazard footwear
Electrical hazard (EH) footwear, rated to ASTM F2413 in the US, has non-conducting soles and heels. It is secondary protection against accidental contact with live circuits, mainly in dry conditions. Wet, worn or contaminated soles lose that value.
Dielectric overshoes (ASTM F1117) are designed to insulate, so they can form part of primary shock protection where your risk assessment calls for it. Never treat EH boots as a substitute for gloves or isolation.
Insulating mats and blankets
Mats and blankets cover live parts or the floor so a slip or stray contact does less harm. HSG85 names insulating matting under BS EN 61111:2009, and OSHA tests blankets before first issue and every 12 months. Inspect before use and replace damaged ones.
Insulated tools
Insulated screwdrivers, pliers and cutters reduce accidental contact when work cannot be made dead. HSG85 names BS EN 60900:2012 for hand tools up to 1,000 V AC and 1,500 V DC. Look for the rating mark on the tool, and take any tool with chipped, cracked or worn insulation out of service.
Arc flash PPE: clothing, suits and ratings
What is arc-rated clothing?
Arc-rated (AR) clothing is flame-resistant fabric that has also been tested for electric arc exposure and marked with an arc rating. It resists ignition and slows heat transfer so burns are less severe. You need it where the hazard assessment shows an arc flash risk. Typical garments are shirts, trousers, coveralls, jackets and hoods.
Arc-rated shirts and trousers
Wear long sleeves and full-length trousers, fastened as the maker instructs, so no skin or non-rated fabric is exposed. Check the label for the arc rating, and inspect for holes, tears, damaged seams and contamination. Wash and repair only as the manufacturer allows. Do not add up the ratings of layers yourself: use the maker’s data and the standard.
Arc flash suits
An arc flash suit is a full set, usually a jacket, trousers or bib overalls and a hood with a face window. It is used for higher incident energy tasks. Choose it from the assessed incident energy, not the highest rating on the shelf. Suits are hot and heavy and reduce vision and dexterity, so an oversized rating adds its own risks.
Arc rating: ATPV and EBT explained
Four terms matter:
- Incident energy: the heat energy that would reach a surface at a given distance during an arc, in cal/cm².
- ATPV (Arc Thermal Performance Value): the energy level at which there is a 50% chance of a second-degree burn through the fabric.
- EBT (Energy Breakopen Threshold): the energy level at which the fabric breaks open.
- Arc rating: the ATPV or EBT, whichever is lower, marked on the garment in cal/cm². It is measured by the test method in ASTM F1959.
The rule is simple: the arc rating must meet or exceed the incident energy from your assessment. For example, if a label shows 8.5 cal/cm² at the stated working distance, garments rated below 8.5 are not suitable. This example is illustrative only and is not a selection instruction.
Flame-resistant (FR) vs arc-rated (AR) clothing
| Feature | FR clothing | Arc-rated clothing |
|---|---|---|
| Main purpose | Resist ignition and flame spread | Tested protection against electric arc exposure |
| Arc rating | Not necessarily marked | Marked in cal/cm² |
| Testing | Depends on its own standard | Arc tested (ASTM F1506 / F1959) |
| Use for electrical work | Not automatically suitable | Selected against the assessed hazard |
All arc-rated clothing is flame-resistant, but not all flame-resistant clothing is arc-rated. ASTM F1506 covers both flame-resistant and arc-rated textiles, so check the label for an actual arc rating.
Why undergarments matter
Non-rated synthetic fabrics such as nylon and polyester can melt onto the skin in an arc event and deepen the burn. Wear non-melting underwear and socks, or AR undergarments, as the garment maker and the standard direct.
Head, eye, face and hearing protection
Electrical safety helmets (hard hats)
In the US, ANSI/ISEA Z89.1 gives helmets an electrical class. Impact protection and electrical protection are separate things, so check both marks.
| Class | Electrical rating | Use for electrical work? |
|---|---|---|
| Class E (Electrical) | Tested at 20,000 V | Yes, the class for electrical work |
| Class G (General) | Tested at 2,200 V | Limited low-voltage protection only |
| Class C (Conductive) | None | No. Often vented and conductive |
Inspect the shell and suspension before each use, and replace to the manufacturer’s date and service-life guidance. In the UK, ask the supplier for the standard marking that shows the helmet is suitable for electrical work.
Safety glasses and goggles
Safety glasses stop flying particles and debris. Choose impact-rated eyewear marked ANSI/ISEA Z87.1 (US) or BS EN 166 (UK), ideally with non-metal frames. Ordinary prescription glasses are not safety eyewear. Under an arc-rated shield, glasses still protect against debris that gets past the shield.
Arc flash face shields
An arc-rated face shield protects the face from heat, molten metal and debris, and its arc rating must match the assessed exposure (ASTM F2178 covers arc-rated face protection in the US). A shield alone leaves the head and neck exposed, so pair it with a balaclava or use a full hood.
Balaclavas and hoods
An arc-rated balaclava covers the head and neck under a face shield and helmet. A full arc flash hood covers the head, neck and face in one piece, usually as part of a suit. Whichever you choose, check that the shield, balaclava, helmet and glasses fit together without gaps.
Hearing protection
An arc blast produces a very loud bang. NFPA lists ear protection among typical electrical PPE. Earplugs that fit under a hood are common, and earmuffs may not fit under a face shield. The exact requirement depends on your assessment and local noise rules, so confirm it for your task.
OSHA, NFPA 70E and other standards
Not every rule is law. We label each item so you can tell the difference:
Legal requirement government regulation. Consensus standard voluntary technical standard. Manufacturer guidance maker’s instructions. General good practice accepted good practice.
OSHA electrical PPE requirements
OSHA is the US workplace safety regulator. The key rules are:
- 29 CFR 1910.132 Legal requirement: general PPE hazard assessment, selection and training.
- 29 CFR 1910.137 Legal requirement: design, in-service care and testing of insulating equipment.
- 29 CFR 1910.335 Legal requirement: electrical protective equipment for the body part and task.
- 29 CFR 1926.97 Legal requirement: the construction equivalent of 1910.137.
- 29 CFR 1910.269 Legal requirement: electric power generation, transmission and distribution, including clothing that will not melt or ignite.
OSHA does not require “NFPA 70E PPE” as a blanket rule. Its enforceable duties come through these provisions and your hazard assessment. See OSHA’s page on electric arc flash hazards and the construction rule 1926.97.
What is NFPA 70E?
NFPA 70E is the Standard for Electrical Safety in the Workplace. It Consensus standard sets out safe work practices, risk assessment and PPE selection for shock, arc flash and arc blast. OSHA describes it as guidance that helps employers comply with its electrical rules, but has not adopted it wholesale. Many employers follow it to show compliance.
The 2024 edition took effect on 13 May 2023. NFPA has since announced a 2027 edition with changes that include an extra person for certain justified energised work, tighter evidence that arc-rated PPE meets its standard, and new wording on testing for absence of voltage. Confirm the edition and effective date on NFPA’s site before you update your programme.
NFPA 70E lets you choose PPE by an incident energy analysis or by the arc flash PPE category method. Do not treat category numbers as universal. They only apply when the table’s conditions are met.
Important ASTM standards
Five ASTM standards matter most. All are Consensus standard voluntary standards, though regulators reference some of them. D120 is the specification for rubber insulating gloves. F496 covers in-service care and testing of insulating gloves and sleeves. F1506 covers flame-resistant and arc-rated clothing. F1959 is the test method that produces an arc rating. F2178 covers arc-rated face protection. The chart below adds the rest.
IEC and other international standards
IEC publishes international standards that Europe adopts as EN standards and the UK as BS EN. IEC 60903 (BS EN 60903) covers insulating gloves, and the IEC/EN 61482 series covers arc protective clothing. Check the current edition with the supplier.
Electrical PPE standards chart
| PPE type | Relevant standard | Status | Main purpose |
|---|---|---|---|
| Rubber insulating gloves | ASTM D120 / IEC 60903 (BS EN 60903) | Consensus standard | Shock protection |
| Leather protectors | ASTM F696 | Consensus standard | Protect rubber gloves |
| In-service care of gloves and sleeves | ASTM F496 | Consensus standard | Care and test methods |
| Insulating equipment testing | OSHA 1910.137 / 1926.97 | Legal requirement | Test intervals, inspection, certification |
| Arc-rated clothing | ASTM F1506 (F1506-25 is current) | Consensus standard | Arc exposure protection |
| Arc rating test | ASTM F1959 | Consensus standard | Measures arc rating |
| Arc-rated face protection | ASTM F2178 | Consensus standard | Face protection |
| Safety helmets | ANSI/ISEA Z89.1 | Consensus standard | Impact and electrical classes |
| Electrical hazard footwear | ASTM F2413 | Consensus standard | Secondary shock protection |
| Dielectric overshoes | ASTM F1117 | Consensus standard | Insulating footwear |
Standards are copyrighted and revised often. Use this chart to know what to ask for, then read the official text, such as ASTM F1506, for exact requirements.
Electrical safety PPE requirements in the US, UK and India
United States
OSHA enforces the rules above, and NFPA 70E and ASTM standards fill in the technical detail. Employers must assess hazards, provide suitable PPE, train workers and certify testing of insulating equipment. Workers must use PPE correctly and report damage.
United Kingdom
HSE enforces electrical safety in Great Britain. The main laws are:
- Electricity at Work Regulations 1989 Legal requirement: prevent danger, and allow live work only when all three conditions are met. Regulation 4(4) requires protective equipment to be suitable, maintained and properly used.
- Personal Protective Equipment at Work Regulations 1992, as amended Legal requirement: employers must provide suitable PPE free of charge, maintain it and train people to use it.
- HSG85, Electricity at work: safe working practices General good practice: HSE guidance. It names insulating gloves and matting, and thermally insulating flame-resistant PPE where arc burns cannot be avoided, and says PPE should be inspected frequently and replaced if damaged.
BS EN standards such as BS EN 60903 (gloves), BS EN 61111 (matting) and BS EN 60900 (hand tools) define product performance. HSE sets no single fixed glove retest interval, so follow the standard, the manufacturer and your risk assessment. BS 7671 covers how installations are designed and installed. It is not a PPE standard.
India
The Central Electricity Authority (CEA) sets safety rules under the Electricity Act 2003. The CEA (Measures relating to Safety and Electric Supply) Regulations, 2023, were notified in June 2023 and cover tools and PPE such as rubber gloves and rubber safety footwear for electrical work. The Bureau of Indian Standards (BIS) publishes the product standards.
A CEA public-comment draft list of relevant standards names IS 4770 (rubber gloves), IS 2925 (industrial helmets) and IS 1989 (safety footwear). It is a draft, so confirm the final list and current BIS editions, and check for amendments to the regulations, before you make a compliance claim.
| Region | Enforcer | Key legal basis | Main technical standards |
|---|---|---|---|
| United States | OSHA | 29 CFR 1910 Subparts I and S; 1926 Subpart E and K | NFPA 70E, ASTM, ANSI/ISEA |
| United Kingdom | HSE | Electricity at Work Regulations 1989; PPE at Work Regulations 1992 | BS EN, IEC |
| India | CEA (with BIS for products) | Electricity Act 2003; CEA Safety Regulations 2023 | BIS (IS) standards, IEC |
How to choose the right electrical safety PPE
Selection is a risk assessment, not a shopping list. Work through these steps in order.
- Identify the hazards. Decide whether the task has a shock hazard, an arc flash hazard or both. Consider the equipment, the environment and what could go wrong.
- Check the voltage. Find the highest voltage that could be present and match insulating equipment to it. Verify the class marking on gloves and sleeves.
- Check the arc flash incident energy. Use the assessment or equipment label. Choose clothing, face and head protection with an arc rating that meets or exceeds it. Make sure the label’s date and method are current.
- Check standards and certification. Look for the standard on the label (ASTM, IEC, ANSI/ISEA, EN) and follow the manufacturer’s instructions. Reject damaged or unmarked items.
- Check fit and compatibility. Gloves, sleeves, clothing, helmet, shield and glasses must fit properly, allow movement and work together.
- Put a qualified person in charge. A qualified electrical worker, electrical safety engineer or competent safety officer should select PPE and sign off the task.
Electrical PPE inspection, testing and storage
Inspection finds damage before it hurts you. Testing proves the insulation still works. Storage keeps the equipment in good condition between uses.
Daily pre-use inspection
Check every item before use, and again after any incident that could have damaged it. Look for:
- Cracks, holes, cuts, tears and punctures.
- Ozone cracking, embedded objects, and swelling, softening, hardening or stickiness in rubber.
- Contamination from oil, chemicals or paint.
- Damaged stitching, seams or loose components.
- Worn insulation on tools.
- Cracked or clouded shields and damaged harnesses.
- Missing or unreadable labels, class marks and test dates.
Remove defective equipment from service until it is repaired and retested, or replaced.
How often should rubber insulating gloves be tested?
Under OSHA 1910.137, gloves need an electrical test before first issue and every six months after. They also need a test whenever their insulating value is suspect, after repair, and after use without protectors. Gloves tested but not issued may go into service only if tested within the previous 12 months. Employers must certify that testing was done. Daily visual inspection and an air test still apply in between.
For example, gloves issued on 10 January 2026 would be due for their next electrical test by 10 July 2026 (illustrative dates). This is separate from an insulation resistance test on cables and equipment, which checks installed equipment, not your PPE.
Inspection and testing chart
| PPE item | Before each use | Electrical testing | Source of interval |
|---|---|---|---|
| Rubber insulating gloves | Visual and air test | Before first issue, every 6 months, plus triggers | OSHA 1910.137 Legal requirement |
| Insulating sleeves | Visual | Before first issue, every 12 months, plus triggers | OSHA 1910.137 Legal requirement |
| Insulating blankets | Visual | Before first issue, every 12 months, plus triggers | OSHA 1910.137 Legal requirement |
| Leather protectors | Visual for cuts and contamination | No fixed OSHA electrical test | Manufacturer Manufacturer guidance |
| Arc-rated clothing | Holes, seams, contamination, labels | None. Care as the maker directs | Manufacturer Manufacturer guidance |
| Face shield, hood, balaclava | Cracks, clouding, fit, harness | None | Manufacturer Manufacturer guidance |
| Safety helmet | Shell and suspension | None | Manufacturer Manufacturer guidance |
| EH footwear | Soles, uppers, markings | None | Manufacturer Manufacturer guidance |
Storage requirements
OSHA requires insulating equipment to be cleaned as needed and stored away from light, temperature extremes, excessive humidity and ozone. As good practice, and per most manufacturers:
- Keep gloves and sleeves clean, dry and uncrushed, not folded or creased.
- Keep them away from sharp objects, oil and chemicals.
- Store arc-rated clothing clean and dry, away from heat and contamination.
- Follow the manufacturer’s storage instructions for each item.
When to replace PPE
Replace an item when it shows visible damage, fails inspection or testing, has an expired or unknown test status, is contaminated or deteriorating, or reaches the manufacturer’s replacement limit.
Electrical safety training and qualified person requirements
Who is a qualified electrical worker?
In the US, a qualified person has demonstrated skills and knowledge in the construction and operation of electrical equipment and installations and has received safety training to identify and avoid the hazards. In the UK the equivalent is a competent person. They understand the electrical hazards, know the protective equipment and can use it correctly.
Employer responsibilities
- Assess workplace electrical hazards.
- Provide suitable PPE.
- Arrange training on hazards, PPE use, inspection, limitations and emergency response.
- Keep inspection, test and certification records.
- Make sure safe work procedures, including isolation, are followed.
Worker responsibilities
- Wear the PPE the task requires.
- Inspect it before use.
- Follow instructions and the safe system of work.
- Report damaged equipment.
- Never misuse electrical protective equipment.
Downloadable electrical safety PPE checklist
Use this one-page checklist before each task. It is built for electricians, supervisors and safety officers.
| Check | Done |
|---|---|
| Task description, location and risk assessment reference recorded | ☐ |
| Equipment de-energised, isolated, locked off and proved dead (or live work justified and permitted) | ☐ |
| Qualified or competent person confirmed | ☐ |
| Hazard identified: shock, arc flash, or both | ☐ |
| Required PPE listed for the task | ☐ |
| PPE inspected before use (gloves air tested) | ☐ |
| Glove class checked against voltage; test date in date | ☐ |
| Arc rating checked against assessed incident energy | ☐ |
| Standards and ratings verified on labels | ☐ |
| Leather protectors fitted and undamaged | ☐ |
| Head, eye, face, hearing and foot protection checked | ☐ |
| Storage condition checked | ☐ |
| Supervisor or safety officer sign-off, date and comments | ☐ |
Common electrical safety PPE mistakes to avoid
- Using ordinary gloves instead of rated insulating gloves. Only rated rubber gloves insulate.
- Wearing rubber gloves without protectors. Cuts and punctures can go unseen. Retest if used without them.
- Confusing FR with arc-rated clothing. Look for a marked arc rating.
- Choosing PPE without a hazard assessment. No assessment means no basis for the choice.
- Using damaged insulating equipment. Remove it from service.
- Ignoring glove test dates. Out-of-date gloves must not be used.
- Using the wrong helmet. Class C helmets give no electrical protection.
- Assuming safety footwear replaces insulating equipment. EH boots are secondary protection.
- Wearing an arc rating that does not match the assessed exposure. Too low is dangerous. Far too high adds heat stress.
- Treating PPE as a replacement for de-energisation. It never is.
Your meter is part of your protection too: see multimeter CAT ratings explained.
Frequently asked questions about electrical safety PPE
What PPE is required for electrical work?
It depends on the task, voltage and risk assessment. Typically: insulating gloves with protectors (shock), arc-rated clothing with face, eye and hearing protection (arc flash), a Class E helmet and EH footwear. Make the equipment dead first.
What are the different types of electrical safety PPE?
Shock protection (gloves, sleeves, mats, dielectric overshoes), arc flash protection (arc-rated clothing, face shields, hoods, suits) and general protection (helmet, safety glasses, hearing protection, footwear).
What is the difference between shock PPE and arc flash PPE?
Shock PPE insulates you from current. Arc flash PPE limits the heat reaching your skin. One cannot replace the other.
What are the four categories of arc flash PPE?
NFPA 70E’s category method groups tasks into Categories 1 to 4, with minimum arc ratings of 4, 8, 25 and 40 cal/cm² in editions that use this table. They apply only when the table’s conditions are met, so they are not universal. Check your edition or use an incident energy analysis.
What class of electrical gloves do I need for 480 V?
Class 00 (500 V) and Class 0 (1,000 V) both exceed 480 V on voltage alone. Check the maximum use voltage against the highest voltage that could be present, and follow your risk assessment.
How often should electrical gloves be tested?
Under OSHA 1910.137, before first issue and every six months, plus after repair, suspected damage or use without protectors. Inspect and air test them every day of use.
Is flame-resistant clothing the same as arc-rated clothing?
No. All arc-rated clothing is flame-resistant, but flame-resistant clothing needs a marked arc rating to count as arc-rated.
Does OSHA require electrical safety PPE?
Yes. Employers must assess hazards and provide suitable protective equipment, and insulating equipment must meet OSHA’s inspection and testing rules. NFPA 70E is a consensus standard, not an OSHA regulation.
Can you work on live electrical equipment with PPE?
PPE does not make live work safe. Live work must be justified, planned and done by qualified people. Work dead wherever you can.
What is an arc flash suit used for?
It gives full-body arc flash protection for higher incident energy tasks. It combines a jacket, trousers or bib overalls and a hood.
Do electricians need dielectric boots?
Not always. EH boots give secondary protection. Dielectric overshoes are used where footwear must provide primary insulation, as your risk assessment decides.
What is the difference between Class E and Class C hard hats?
Class E helmets are tested at 20,000 V. Class C helmets give no electrical protection.
What is ATPV in electrical PPE?
Arc Thermal Performance Value, in cal/cm². It is the energy level at which there is a 50% chance of a second-degree burn through the fabric.
Can rubber gloves protect against arc flash?
No. They are tested for insulation, not arc heat. Choose hand protection for arc exposure from your assessment and the standard.
Do workers need PPE when equipment is de-energised?
Only treat equipment as dead once it is isolated, locked off and proved dead. Other workplace hazards may still need PPE.
Choosing the right electrical safety PPE
Electrical safety PPE protects against two different hazards, and the equipment for each is different. Insulating gloves, sleeves and mats guard against shock. Arc-rated clothing, face and head protection and hearing protection guard against arc flash. Choose by risk assessment, follow the regulations and standards that apply where you work, and inspect and test equipment on schedule. Download the checklist above, and remember that PPE is always the last line of defence, after elimination, isolation and engineering controls.
Sources and last reviewed
Last reviewed: 9 November 2026. Reviewed by: [Name, qualification and role of the qualified electrical safety reviewer to be added before publishing]. Next review: May 2027, or sooner after a new NFPA 70E edition, an OSHA, HSE or CEA change, or an ASTM, IEC or BIS revision.
| Date | Change |
|---|---|
| 9 November 2026 | First published. Standards and figures checked against the sources below. |
Sources
- OSHA 29 CFR 1910.137, Electrical protective equipment
- OSHA 29 CFR 1926.97, Electrical protective equipment (construction)
- OSHA, Electric arc flash hazards
- NFPA 70E standard development
- ASTM F1506, flame-resistant and arc-rated textile materials
- HSE, Electricity at work: safe working practices (HSG85)
- HSE, Electricity at work: safe isolation (HSG141)
- HSE, electricity FAQs on live working
- HSE, electrical equipment and RCDs
- US Bureau of Labor Statistics, fatal occupational injuries by event, 2023–24
- ESFI, workplace electrical injury and fatality statistics
- CEA, Measures relating to Safety and Electric Supply
This guide is general information, not professional advice. PPE selection must follow a task-specific risk assessment by a qualified person and the regulations and standards that apply where you work.