One ton of refrigeration (TR) equals 12,000 Btu/h, which is 3.517 kW of cooling. To convert tons to kW multiply by 3.517; to convert kW of cooling to tons divide by 3.517. So a 100-ton chiller removes about 352 kW of heat, and 100 kW of cooling is 28.4 tons. That kW is thermal (heat removed), not the electricity the unit uses: electrical input is the cooling kW divided by the coefficient of performance (COP), so the same 100-ton chiller at COP 5 draws about 70 kW.
What Is a Ton of Refrigeration?
Wikipedia describes the ton of refrigeration as a unit of power used especially in North America for the heat-extraction rate of refrigeration and air-conditioning equipment. It was originally defined as the rate of heat transfer that freezes or melts one short ton (2,000 lb) of ice at 32 °F in 24 hours; the modern definition is exactly 12,000 Btu/h. NIST SP 811 lists it as 3.516853 kW. US equipment capacity is often specified in tons, and smaller units in Btu/h.
Tons to kW Calculator
Tons to kW Conversion Chart
| Tons | kW (cooling) | Btu/h | Tons | kW (cooling) | Btu/h |
|---|---|---|---|---|---|
| 0.5 | 1.76 | 6,000 | 25 | 87.9 | 300,000 |
| 1 | 3.52 | 12,000 | 30 | 105.5 | 360,000 |
| 1.5 | 5.28 | 18,000 | 50 | 175.8 | 600,000 |
| 2 | 7.03 | 24,000 | 75 | 263.8 | 900,000 |
| 2.5 | 8.79 | 30,000 | 100 | 351.7 | 1,200,000 |
| 3 | 10.55 | 36,000 | 150 | 527.5 | 1,800,000 |
| 4 | 14.07 | 48,000 | 200 | 703.4 | 2,400,000 |
| 5 | 17.58 | 60,000 | 300 | 1,055.1 | 3,600,000 |
| 7.5 | 26.38 | 90,000 | 500 | 1,758.4 | 6,000,000 |
| 10 | 35.17 | 120,000 | 600 | 2,110.1 | 7,200,000 |
| 15 | 52.75 | 180,000 | 1000 | 3,516.9 | 12,000,000 |
| 20 | 70.34 | 240,000 |
Cooling kW vs Electrical kW
Wikipedia defines COP as the ratio of useful heating or cooling to the work required, and notes refrigeration systems move existing heat rather than generate it, so COP usually exceeds 1; most air conditioners have a COP of 3.5 to 5. That gives three ways of stating the same efficiency:
| COP | kW per ton (electric) | EER (Btu/h per W) | Electrical kW for 100 tons |
|---|---|---|---|
| 2.5 | 1.407 | 8.5 | 140.7 |
| 3.5 | 1.005 | 11.9 | 100.5 |
| 5 | 0.703 | 17.1 | 70.3 |
| 6 | 0.586 | 20.5 | 58.6 |
| 7 | 0.502 | 23.9 | 50.2 |
Where Tons and kW Meet in a Plant
- Process cooling: heat from machines, hydraulics or ovens in kW is divided by 3.517 to size the chiller in tons.
- Electrical design: the chiller’s electrical kW sets breaker and feeder sizing; see kVA to kW for converting with power factor.
- Motors and compressors: compressor shaft power is often in hp; see kW to hp.
- Air flow: air-side HVAC capacity also depends on flow; see SCFM vs CFM for flow definitions.
Frequently Asked Questions
How many kW is 1 ton of refrigeration?
3.517 kW. NIST and Wikipedia define 1 ton of refrigeration as exactly 12,000 Btu/h, which is 3.516853 kW of cooling.
How do you convert kW to tons of cooling?
Divide by 3.517: 100 kW of cooling = 28.4 tons.
How do you convert tons to kW?
Multiply by 3.517: a 600-ton chiller provides 2,110 kW of cooling.
Is a ton of cooling the same as electrical kW?
No. Tons and kW (thermal) measure heat removed. The electricity the unit draws is much less: cooling kW divided by the COP. A 100-ton chiller with a COP of 5 draws about 70 kW.
What does kW per ton mean?
Electrical kW drawn per ton of cooling, a common chiller efficiency measure. Lower is better. kW/ton = 3.517 ÷ COP, so COP 5 is 0.70 kW/ton.
Why is it called a ton?
Wikipedia explains it was originally the cooling effect of melting one short ton (2,000 lb) of ice in 24 hours, a unit that made sense during the move from natural ice to mechanical refrigeration.
What is TR or RT?
Abbreviations for ton of refrigeration (TR, TOR) or refrigeration ton (RT); all mean 12,000 Btu/h.
How many Btu is a ton?
12,000 Btu per hour.
What is COP?
Coefficient of performance: heat moved divided by the work (electrical energy) put in. Wikipedia notes most air conditioners have a COP of 3.5 to 5.
How do I size a chiller in tons?
Calculate the heat load in kW or Btu/h (process heat, equipment, building load), add margin as your design standard requires, and divide by 3.517 kW or 12,000 Btu/h per ton.
Sources and Further Reading
- Wikipedia: Ton of refrigeration: definition, history and conversions.
- NIST SP 811, Appendix B.8: ton of refrigeration and Btu/h in watts.
- Wikipedia: Coefficient of performance: COP definition and typical air-conditioner values.