On IEC drawings, a disconnect switch is a switch blade with a short bar across the fixed contact. A load-break switch-disconnector adds a small circle, and a circuit breaker uses a cross instead. A fuse is a rectangle with a line through it, and a fusible disconnect is a switch-disconnector drawn in series with a fuse. On North American one-line diagrams, a disconnect is often a hinged blade marked 89, and a circuit breaker a square marked 52 (IEEE C37.2 device numbers). Multi-pole devices are linked by a dashed line.
Disconnect, Breaker and Fuse Symbol Chart
How to Read the Symbols
| Device | IEC 60617 symbol | IEEE / North American form | What it can do |
|---|---|---|---|
| Disconnector / isolator | Blade + bar at fixed contact | Hinged blade, device 89 | Isolate only; open off-load |
| Switch-disconnector (load-break) | Blade + bar + circle | Blade marked load-break | Make and break load current, isolate |
| Circuit breaker | Blade + cross | Arc over contacts (IEEE 315); box 52 on one-lines | Make, carry and interrupt fault current |
| Fuse | Rectangle with line through | Same, or S-curve | Interrupt overcurrent by melting |
| Fusible disconnect (switch-disconnector-fuse) | Switch-disconnector + fuse in series | Disconnect with fuse symbol | Load-break isolation plus fuse protection |
| Fuse-switch-disconnector | Fuse drawn on the blade | Fused blade | Fuse moves with the contact |
| Contactor | Blade + semicircle | Contacts with coil reference | Frequent load switching, no isolation |
The qualifier at the fixed contact tells you what the device can do. A bar means isolation capability, a circle means load-break duty, a cross means fault interruption, and a semicircle means a contactor. Mixing them up matters. A breaker drawn where a disconnector was intended can leave a circuit without the interrupting capacity it needs, and a fuse-switch is easily confused with a switch-fuse.
Single-Line (One-Line) Diagram Conventions
Single-line diagrams show a three-phase system with one line per circuit, so each symbol stands for all phases. North American one-lines use IEEE C37.2 device numbers inside boxes or next to symbols: 52 for an AC circuit breaker, 89 for a line disconnect switch, and 49, 50 and 51 for thermal, instantaneous and time-overcurrent relays (see the ANSI device numbers list). IEC one-lines keep the blade symbols and add rating tags; for example C16 1P 6 kA gives the trip curve, current, poles and breaking capacity.
Disconnect vs Circuit Breaker vs Recloser
A disconnector (disconnect switch, isolator) has visible contacts and makes sure a circuit is fully de-energized for maintenance. It lacks arc suppression, so it is an off-load device, opened only after a breaker or switch has interrupted the current. It usually has provision for lockout/tagout, sometimes as part of a trapped-key interlock, and may be paired with an earthing switch. IEC 62271-102 covers high-voltage disconnectors (Wikipedia). For safe isolation steps, see lockout/tagout.
A circuit breaker can make, carry and automatically interrupt both normal and fault currents (see types of circuit breakers). A recloser is essentially a breaker with built-in current and voltage sensors and a protection relay, used on overhead distribution lines. Up to 80–87% of faults there are transient, so the recloser trips and recloses automatically, at least 0.3 s apart. Standards (IEC 62271-111 / IEEE C37.60) limit it to four reclose attempts before lockout (Wikipedia).
Labels and Letter Codes
- IEC 81346: switching devices such as breakers carry -Q designations (-Q1), fuses -F (-F1), with rating and utilization category
- North America: breakers are often CB1, CB2 and so on; one-lines add IEEE C37.2 device numbers such as 52 and 89
- Breaker ratings next to the symbol: type, frame and trip rating, poles, breaking capacity (Icu/Ics or kAIC) and trip functions such as LSIG
- Disconnects: mark load-break or off-load, and note interlocks with earthing switches
For grounding and earthing symbols, see ground symbols. For contactor symbols and use, see contactor vs relay.
Frequently Asked Questions
What is the symbol for a disconnect on a wiring diagram?
In IEC 60617 drawings, a switch blade with a short perpendicular bar at the fixed contact; a load-break switch-disconnector adds a small circle. On North American one-line diagrams a disconnect is often a hinged blade labeled with device number 89 (IEEE C37.2).
What is the difference between the disconnector and circuit breaker symbols?
Both start from a switch blade. The disconnector has a bar at the fixed contact, meaning isolation only; the circuit breaker has a cross, meaning it can interrupt fault current.
What does a fusible disconnect symbol look like?
A switch-disconnector symbol with a fuse (a rectangle with a line through it) drawn in series. If the fuse is drawn on the moving blade itself, it is a fuse-switch-disconnector, where the fuse moves with the contact.
How is a circuit breaker shown on a single-line diagram?
In North America often as a small square labeled 52 (the IEEE C37.2 device number for an AC circuit breaker), or as the IEEE 315 arc symbol; drawout breakers add chevrons. IEC one-lines use the blade with a cross and a rating tag such as C16 1P 6 kA.
What is the IEEE device number for a disconnect switch?
89 (line switch / disconnect) under IEEE C37.2; 52 is the AC circuit breaker.
How are multi-pole switches drawn?
As several blades side by side linked by a dashed line, showing the poles operate together. A 3-pole disconnect shows three blades with one dashed link.
What is the fuse symbol?
A rectangle with a straight line through its full length (IEC 60617, accepted by IEEE 315). IEEE practice also uses an S-shaped curve between two terminals.
What is a disconnector used for?
To make sure a circuit is completely de-energized for service, with visible contacts and provision for lockout. It is an off-load device without arc suppression, so it is opened only after current has been interrupted by a breaker or switch (Wikipedia).
What is the difference between a recloser and a breaker?
A recloser is essentially a circuit breaker with integrated current and voltage sensors and a protection relay, designed to trip and automatically reclose on overhead distribution lines, where most faults are transient. Standards limit it to four reclose attempts before lockout (Wikipedia).
What letter code identifies a breaker or fuse on drawings?
IEC 81346 drawings label switching devices such as breakers -Q (for example -Q1) and fuses -F (-F1); many North American drawings use CB1 for a breaker.
Sources and Further Reading
- MARS Engineering: Circuit Breaker Symbol and Fuse Symbol, IEEE vs IEC Guide: IEC 60617 qualifiers, IEEE 315 forms, device numbers, labels.
- Wikipedia: Disconnector: function, off-load duty, lockout, IEC 62271-102.
- Wikipedia: Recloser: recloser vs breaker, reclose limits.
- Wikipedia: Single-line diagram.