Cold Junction Compensation: How Thermocouple CJC Works

By editor 7 min read
Thermocouple wired to an isothermal cold junction block with an RTD measuring its temperature

Cold junction compensation (CJC) corrects a thermocouple reading for the temperature at the point where the thermocouple wires connect to the instrument, the cold (reference) junction. A thermocouple’s voltage depends on the temperature difference between its hot and cold junctions, and thermocouple tables assume the cold junction is at 0 °C, so the instrument measures the terminal temperature, converts it to an equivalent voltage, adds it to the measured voltage, and only then converts to temperature. Example: a type K reading of 16.000 mV with terminals at 50 °C is really 438.4 °C; simply adding 50 °C to the uncompensated temperature would give 440.6 °C, 2.2 °C too high.

Vtotal = Vmeasured + V(TCJ)   →   Thot = T(Vtotal)
0 °C
table reference junction
≈ 41 µV/°C
type K sensitivity
2.022 mV
type K at 50 °C
Add volts
not degrees

What the Cold Junction Is

Wikipedia describes the standard thermocouple configuration: two dissimilar conductors meet at the measuring (hot) junction and at the reference (cold) junction, where the thermocouple connects to the electrical system. The measured voltage V gives the sensed temperature only if the reference temperature Tref is known, by solving E(Tsense) = V + E(Tref). This comes from the Seebeck effect: a voltage develops across a conductor when its two ends are at different temperatures.

Thermocouple measuring junction, cold junction block and measurement circuitTwo dissimilar thermocouple wires meet at the measuring (hot) junction and connect to copper at an isothermal block, the cold junction, whose temperature is measured by an RTD or thermistor. The measurement circuit reads the thermocouple voltage and the cold junction temperature.Where the cold junction is and why it must be measuredmeasuring(hot) junctionthermocouple wire A (e.g. chromel)thermocouple wire B (e.g. alumel)isothermal block= cold junctionRTD / thermistorcopperADC / PLC modulemeasures V_TCand T_CJThe voltage depends on the hot–cold difference, so the cold-junction temperature must be known.IndustrialBasicsindustrialbasics.com
Figure 1: Based on the TI thermocouple guide and Wikipedia. The isothermal block keeps both cold-junction connections at the same, measured temperature.

TI’s Basic Guide to Thermocouple Measurements explains that the cold-junction block holds both thermocouple leads at the same temperature, often using a connector with a large metal mass; on circuit boards, generous copper fill can help, and an enclosure may be needed because air currents affect the temperature. The block’s temperature is measured with a diode, thermistor or RTD.

How Cold Junction Compensation Works

TI gives the correct procedure in three steps:

  1. Convert the cold-junction temperature TCJ to a voltage VCJ using the thermocouple table or polynomial.
  2. Add the cold-junction voltage to the measured thermocouple voltage: VCJ + VTC.
  3. Convert the sum to the thermocouple temperature TTC.
Steps of cold junction compensation with a numerical type K exampleA type K thermocouple reads 16.000 millivolts with the cold junction at 50 degrees Celsius. The cold junction temperature corresponds to 2.022 millivolts; adding gives 18.022 millivolts, which converts to 438.4 degrees. Adding 50 degrees to the uncompensated temperature instead would give 440.6 degrees.Correct CJC: add voltages, not temperatures (type K example)1 MeasureV_TC = 16.000 mV2 Cold junctionT_CJ = 50 °C→ V_CJ = 2.022 mV3 Add voltages16.000 + 2.022= 18.022 mV4 ConvertT = 438.4 °CWrong shortcut: convert 16.000 mV to 390.6 °C, then add 50 °C = 440.6 °C(error +2.2 °C, because the thermocouple curve is not linear)IndustrialBasicsindustrialbasics.com
Figure 2: Method from the TI thermocouple guide; values calculated with the ITS-90 type K inverse coefficients it publishes.

TI stresses that thermocouple voltages are non-linear with temperature, so you cannot just add the cold-junction temperature to the temperature computed from the thermocouple voltage. The compensated voltage is what the thermocouple would have produced with its cold junction at 0 °C, which is the reference used by the NIST ITS-90 tables.

Type K CJC Calculator

Type K Cold Junction Compensation Calculator (0–500 °C)
IndustrialBasics calculator using the ITS-90 type K inverse polynomial for 0–500 °C (0 to 20.644 mV) published in TI application note SBAA274. Valid only for type K within that range; use the NIST ITS-90 tables for other types and ranges.

Methods of Cold Junction Compensation

MethodHow it worksNotes
Ice bathReference junction held at 0 °C in ice waterClassical laboratory method (TI); matches tables directly
RTD at the terminalsMeasures the isothermal block temperatureAccurate; common in quality instruments
ThermistorMeasures block temperature; needs linearizationLow cost, good over a narrow range
Diode or IC temperature sensorSemiconductor sensor near the terminalsCommon in integrated thermocouple front ends
Cold-junction methods from the TI thermocouple guide.

Thermocouple Types and Sensitivity

TypeSensitivityNotes (Wikipedia)
K (chromel–alumel)About 41 µV/°CInexpensive, −200 to +1,350 °C range
J (iron–constantan)About 50 µV/°CUpper limit set by iron’s Curie point (770 °C)
BVery low near room temperatureSame output at 0 °C and 42 °C, so CJC barely matters
Sensitivities from the Wikipedia thermocouple article. Exact voltages come from the NIST ITS-90 tables.

Because sensitivity is only tens of microvolts per degree, a few degrees of error at the terminals produces the same error in the reading. That is why the cold-junction sensor must sit right at the thermocouple terminals, on the same isothermal block. For comparison with resistance sensors, see types of industrial sensors.

Practical Tips for PLC and Field Wiring

  • Use matching extension wire all the way to the input terminals. A copper splice creates a new junction at an unmeasured temperature.
  • Keep terminals out of drafts and heat sources so the block stays isothermal; close the terminal cover.
  • Fit the cold-junction sensor accessory if the module requires one, and enable CJC in the configuration.
  • Check polarity: reversed leads give readings that move the wrong way.
  • Verify with a calibrator that sources thermocouple millivolts with its own CJC, or a known reference temperature.
Safety note: Thermocouples are often installed on hot process lines and furnaces. Follow lockout procedures and allow equipment to cool before working on sensor connections.

Choosing between sensors? Compare with our 3-wire vs 4-wire RTD guide, which covers PT100 accuracy and wiring.

If you are still choosing a sensor, compare RTD vs thermocouple first.

Frequently Asked Questions

What is cold junction compensation?

A correction for the temperature of the point where the thermocouple wires connect to the measuring instrument (the cold or reference junction). A thermocouple only produces a voltage proportional to the difference between its hot and cold junctions, so the instrument measures the cold-junction temperature and adds the matching voltage.

Why is cold junction compensation needed?

Because thermocouple tables are referenced to a cold junction at 0 °C. If the terminals are at 25 °C, the raw voltage is lower than the table value for the true temperature; TI explains the compensation “gives the voltage that would have been developed if TCJ had been at 0 °C.”

How is cold junction compensation done?

Measure the cold-junction temperature (with an RTD, thermistor, diode or IC sensor), convert it to the equivalent thermocouple voltage, add that to the measured voltage, and convert the total to temperature.

Can I just add the cold junction temperature to the reading?

No. TI warns that thermocouple voltages are non-linear, so you cannot simply add the cold-junction temperature to the temperature computed from the thermocouple voltage. Add voltages, then convert.

What was the ice bath method?

The classical method: place the reference junctions in an ice bath so they are at exactly 0 °C, matching the tables. Modern instruments measure the terminal temperature instead.

What is an isothermal block?

A terminal block, often a large metal mass, that keeps both thermocouple-to-copper connections at the same temperature so a single sensor can measure it. Air currents can upset it, so it may be enclosed.

Do PLC thermocouple cards do CJC automatically?

Most dedicated thermocouple input modules have built-in cold-junction sensors at the terminals; some need a separate cold-junction sensor accessory fitted to the terminal block. Check the module manual.

What happens if I use copper wire instead of thermocouple extension wire?

The junction moves to wherever the copper starts, and that point’s temperature is not measured, so the reading is wrong. Run thermocouple or matching extension wire all the way to the compensated terminals.

How much voltage does a type K thermocouple produce?

About 41 µV/°C, per Wikipedia; type J is about 50 µV/°C. A K-type at 500 °C (cold junction 0 °C) produces about 20.6 mV.

Is a thermocouple or RTD more accurate?

TI notes RTDs are generally more accurate, while thermocouples cover a wider range, are self-powered and respond faster.