A 3-wire RTD has one lead on one end of the sensing element and two on the other, which lets the instrument cancel lead wire resistance as long as the leads match. A 4-wire RTD has two leads on each end, so the excitation current and the voltage measurement use separate wires and lead resistance causes no error at all. A 2-wire RTD cannot separate lead resistance from the sensor, so it reads high. 4-wire gives the best accuracy, 3-wire is the usual industrial choice, and 2-wire suits short leads where accuracy is not critical. For example, 100 ft of 22 AWG cable on a 2-wire PT100 reads about 8.3 °C high.
2-Wire vs 3-Wire vs 4-Wire RTD
| 2-wire | 3-wire | 4-wire | |
|---|---|---|---|
| Leads | One at each end | One at one end, two at the other | Two at each end |
| Lead resistance | Adds to reading (cannot be separated) | Cancelled if leads match | Not in the measurement |
| Accuracy | Least accurate | Good | Best |
| Cost | Lowest | Moderate | Highest |
| Typical use | Short leads, non-critical points | Most industrial process measurement | Laboratory, calibration, high-accuracy process |
TI’s guide explains each: in the two-wire configuration “the lead wire resistances cannot be separated from the RTD resistance”, so two-wire RTDs “yield the least accurate RTD measurements”. In the three-wire configuration, circuit topology can cancel lead resistance, but “compensation for lead wire resistance assumes that the lead resistances match.” In the four-wire configuration, excitation flows through one lead at each end while resistance is sensed on the other pair, so the measurement has no error from lead wires; four-wire RTDs are the most accurate and most expensive.
Lead-Wire Error Calculator
How big is the error?
| Wire gauge (copper) | Ω per lead, 100 ft | 2-wire error at 0 °C | 3-wire error, 5% mismatch |
|---|---|---|---|
| 14 AWG | 0.253 | +1.29 °C | +0.032 °C |
| 16 AWG | 0.402 | +2.06 °C | +0.051 °C |
| 18 AWG | 0.638 | +3.27 °C | +0.082 °C |
| 20 AWG | 1.015 | +5.20 °C | +0.130 °C |
| 22 AWG | 1.614 | +8.27 °C | +0.206 °C |
| 24 AWG | 2.567 | +13.16 °C | +0.328 °C |
The numbers show why 3-wire is the industrial default: even with a 5% mismatch between leads, the error is a few hundredths of a degree on typical cable, while the same cable on a 2-wire connection can add a degree or more.
PT100 Basics
TI describes the PT100 as a platinum RTD with 100 Ω at 0 °C. Above 0 °C its resistance follows the Callendar-Van Dusen equation R = R₀(1 + AT + BT²), with IEC 60751 coefficients A = 3.9083 × 10⁻³ and B = −5.775 × 10⁻⁷; below 0 °C an extra term with C = −4.183 × 10⁻¹² applies. A PT100 reads about 138.5 Ω at 100 °C, roughly 0.39 Ω per degree.
| Class (IEC 60751 / ASTM E1137) | Tolerance | Error at 100 °C |
|---|---|---|
| IEC Class AA | ±(0.1 + 0.0017|T|) °C | ±0.27 °C |
| IEC Class A | ±(0.15 + 0.002|T|) °C | ±0.35 °C |
| IEC Class B | ±(0.3 + 0.005|T|) °C | ±0.8 °C |
| IEC Class C | ±(0.6 + 0.01|T|) °C | ±1.6 °C |
| ASTM Grade A | ±(0.13 + 0.0017|T|) °C | ±0.3 °C |
| ASTM Grade B | ±(0.25 + 0.0042|T|) °C | ±0.67 °C |
An RTD’s own tolerance is often similar to, or smaller than, the lead-wire error of a long 2-wire run, which is why wiring choice matters as much as sensor class.
Wiring a 3-Wire RTD to a PLC or Transmitter
- Identify the pair: the two leads from the same end of the element (often the same color) go to the terminals the module labels for the compensation lead and one sensing lead.
- Use the same gauge and length for all three conductors so their resistances match.
- Use shielded, twisted cable and ground the shield at one end, typically the instrument end.
- Configure the input for RTD type (PT100, IEC 0.00385 curve) and 3-wire mode.
- Keep RTD cables away from power wiring to avoid noise.
A head-mounted 4-20 mA transmitter near the sensor removes the lead-length problem entirely by converting resistance to a current signal close to the RTD; see our 4-20 mA guide. For thermocouples instead, see cold junction compensation, and for other sensor types, types of industrial sensors.
Still deciding on the sensor itself? See RTD vs thermocouple for range, accuracy and response compared.
Frequently Asked Questions
What is the difference between a 3-wire and a 4-wire RTD?
A 3-wire RTD has one lead on one end of the element and two on the other, so the instrument can subtract lead resistance if the leads match. A 4-wire RTD has two leads on each end: one pair carries the excitation current and the other measures voltage, so lead resistance causes no error. 4-wire is most accurate; 3-wire is the common industrial compromise.
Why does an RTD have 3 wires?
To cancel lead wire resistance. With two wires, the resistance of both leads adds to the sensor’s reading. The third wire lets the instrument measure and subtract the lead resistance, assuming the leads are equal.
How much error does a 2-wire RTD have?
It depends on cable length and gauge. 100 ft of 22 AWG copper adds about 3.2 Ω for two leads, which a PT100 reads as roughly 8.3 °C high.
Can I connect a 3-wire RTD to a 2-wire input?
Yes, by joining the two same-end leads, but you lose lead compensation and the reading will be high by the lead resistance.
Can I connect a 4-wire RTD to a 3-wire input?
Yes. Leave one of the paired leads unconnected (insulated) and wire the rest as a 3-wire sensor; accuracy becomes that of a 3-wire connection.
What is a PT100?
A platinum RTD with a resistance of 100 Ω at 0 °C. TI notes its resistance-temperature relationship is described by the Callendar-Van Dusen equation with IEC 60751 coefficients.
What is the resistance of a PT100 at 100 °C?
About 138.5 Ω, from R = 100(1 + AT + BT²) with A = 3.9083 × 10⁻³ and B = −5.775 × 10⁻⁷.
What is the 3-wire RTD color code?
Commonly the two leads on the same end share a color and the single lead on the other end is a different color, but color codes vary by manufacturer and standard; check the sensor data sheet.
How long can an RTD cable be?
With 3-wire or 4-wire connections and matched leads, hundreds of feet can work. The limits are lead mismatch (3-wire), noise pickup and the instrument’s maximum lead resistance; use the calculator to estimate error.
Is an RTD more accurate than a thermocouple?
Generally yes. TI notes RTDs are more accurate and interchangeable thanks to tight tolerance standards, while thermocouples cover wider ranges and respond faster. See cold junction compensation for thermocouple measurement.
Sources and Further Reading
- Texas Instruments SBAA275: A Basic Guide to RTD Measurements (PDF): wiring configurations, Callendar-Van Dusen coefficients and tolerance classes.
- Wikipedia: Resistance thermometer: RTD background.
- Wikipedia: American wire gauge: copper resistance per foot by gauge.