3-Wire vs 4-Wire RTD: Wiring, Lead Resistance and Accuracy

By editor 6 min read
Two-wire, three-wire and four-wire RTD lead configurations side by side

A 3-wire RTD has one lead on one end of the sensing element and two on the other, which lets the instrument cancel lead wire resistance as long as the leads match. A 4-wire RTD has two leads on each end, so the excitation current and the voltage measurement use separate wires and lead resistance causes no error at all. A 2-wire RTD cannot separate lead resistance from the sensor, so it reads high. 4-wire gives the best accuracy, 3-wire is the usual industrial choice, and 2-wire suits short leads where accuracy is not critical. For example, 100 ft of 22 AWG cable on a 2-wire PT100 reads about 8.3 °C high.

100 Ω
PT100 at 0 °C
≈ 0.39 Ω/°C
PT100 sensitivity
+8.3 °C
2-wire, 100 ft of 22 AWG
4-wire
no lead-wire error
Two-wire, three-wire and four-wire RTD lead configurationsA two-wire RTD has one lead at each end of the element, so lead resistance adds to the reading. A three-wire RTD has one lead at one end and two at the other, allowing matched lead resistance to be cancelled. A four-wire RTD has two leads at each end, so current and voltage sensing are separate and lead resistance causes no error.2-wire, 3-wire and 4-wire RTD connections2-wireRTDLead resistance adds to the reading3-wireRTDMatched leads cancel out4-wireRTDSeparate sense leads: no lead errorDot colors only illustrate which leads share an end; check the sensor data sheet for its color code.IndustrialBasicsindustrialbasics.com
Figure 1: Configurations from TI application note SBAA275. 2-wire is least accurate and cheapest; 4-wire most accurate and most expensive.

2-Wire vs 3-Wire vs 4-Wire RTD

2-wire3-wire4-wire
LeadsOne at each endOne at one end, two at the otherTwo at each end
Lead resistanceAdds to reading (cannot be separated)Cancelled if leads matchNot in the measurement
AccuracyLeast accurateGoodBest
CostLowestModerateHighest
Typical useShort leads, non-critical pointsMost industrial process measurementLaboratory, calibration, high-accuracy process
Comparison from TI application note SBAA275, A Basic Guide to RTD Measurements.

TI’s guide explains each: in the two-wire configuration “the lead wire resistances cannot be separated from the RTD resistance”, so two-wire RTDs “yield the least accurate RTD measurements”. In the three-wire configuration, circuit topology can cancel lead resistance, but “compensation for lead wire resistance assumes that the lead resistances match.” In the four-wire configuration, excitation flows through one lead at each end while resistance is sensed on the other pair, so the measurement has no error from lead wires; four-wire RTDs are the most accurate and most expensive.

Lead-Wire Error Calculator

PT100 Lead-Wire Error Calculator
IndustrialBasics calculator. PT100 per IEC 60751 Callendar-Van Dusen (T ≥ 0 °C): R = 100(1 + AT + BT²), A = 3.9083×10⁻³, B = −5.775×10⁻⁷ (TI SBAA275). Copper resistance per foot from the Wikipedia AWG table at about 20 °C. 2-wire error from both leads; 3-wire error from the mismatch between leads; 4-wire treated as zero.

How big is the error?

Wire gauge (copper)Ω per lead, 100 ft2-wire error at 0 °C3-wire error, 5% mismatch
14 AWG0.253+1.29 °C+0.032 °C
16 AWG0.402+2.06 °C+0.051 °C
18 AWG0.638+3.27 °C+0.082 °C
20 AWG1.015+5.20 °C+0.130 °C
22 AWG1.614+8.27 °C+0.206 °C
24 AWG2.567+13.16 °C+0.328 °C
Copper resistance from the Wikipedia AWG table; PT100 conversion with IEC 60751 coefficients (TI SBAA275). One-way cable length 100 ft.

The numbers show why 3-wire is the industrial default: even with a 5% mismatch between leads, the error is a few hundredths of a degree on typical cable, while the same cable on a 2-wire connection can add a degree or more.

PT100 Basics

TI describes the PT100 as a platinum RTD with 100 Ω at 0 °C. Above 0 °C its resistance follows the Callendar-Van Dusen equation R = R₀(1 + AT + BT²), with IEC 60751 coefficients A = 3.9083 × 10⁻³ and B = −5.775 × 10⁻⁷; below 0 °C an extra term with C = −4.183 × 10⁻¹² applies. A PT100 reads about 138.5 Ω at 100 °C, roughly 0.39 Ω per degree.

Class (IEC 60751 / ASTM E1137)ToleranceError at 100 °C
IEC Class AA±(0.1 + 0.0017|T|) °C±0.27 °C
IEC Class A±(0.15 + 0.002|T|) °C±0.35 °C
IEC Class B±(0.3 + 0.005|T|) °C±0.8 °C
IEC Class C±(0.6 + 0.01|T|) °C±1.6 °C
ASTM Grade A±(0.13 + 0.0017|T|) °C±0.3 °C
ASTM Grade B±(0.25 + 0.0042|T|) °C±0.67 °C
RTD tolerance classes from TI SBAA275 (Table 1-1).

An RTD’s own tolerance is often similar to, or smaller than, the lead-wire error of a long 2-wire run, which is why wiring choice matters as much as sensor class.

Wiring a 3-Wire RTD to a PLC or Transmitter

  • Identify the pair: the two leads from the same end of the element (often the same color) go to the terminals the module labels for the compensation lead and one sensing lead.
  • Use the same gauge and length for all three conductors so their resistances match.
  • Use shielded, twisted cable and ground the shield at one end, typically the instrument end.
  • Configure the input for RTD type (PT100, IEC 0.00385 curve) and 3-wire mode.
  • Keep RTD cables away from power wiring to avoid noise.

A head-mounted 4-20 mA transmitter near the sensor removes the lead-length problem entirely by converting resistance to a current signal close to the RTD; see our 4-20 mA guide. For thermocouples instead, see cold junction compensation, and for other sensor types, types of industrial sensors.

Still deciding on the sensor itself? See RTD vs thermocouple for range, accuracy and response compared.

Frequently Asked Questions

What is the difference between a 3-wire and a 4-wire RTD?

A 3-wire RTD has one lead on one end of the element and two on the other, so the instrument can subtract lead resistance if the leads match. A 4-wire RTD has two leads on each end: one pair carries the excitation current and the other measures voltage, so lead resistance causes no error. 4-wire is most accurate; 3-wire is the common industrial compromise.

Why does an RTD have 3 wires?

To cancel lead wire resistance. With two wires, the resistance of both leads adds to the sensor’s reading. The third wire lets the instrument measure and subtract the lead resistance, assuming the leads are equal.

How much error does a 2-wire RTD have?

It depends on cable length and gauge. 100 ft of 22 AWG copper adds about 3.2 Ω for two leads, which a PT100 reads as roughly 8.3 °C high.

Can I connect a 3-wire RTD to a 2-wire input?

Yes, by joining the two same-end leads, but you lose lead compensation and the reading will be high by the lead resistance.

Can I connect a 4-wire RTD to a 3-wire input?

Yes. Leave one of the paired leads unconnected (insulated) and wire the rest as a 3-wire sensor; accuracy becomes that of a 3-wire connection.

What is a PT100?

A platinum RTD with a resistance of 100 Ω at 0 °C. TI notes its resistance-temperature relationship is described by the Callendar-Van Dusen equation with IEC 60751 coefficients.

What is the resistance of a PT100 at 100 °C?

About 138.5 Ω, from R = 100(1 + AT + BT²) with A = 3.9083 × 10⁻³ and B = −5.775 × 10⁻⁷.

What is the 3-wire RTD color code?

Commonly the two leads on the same end share a color and the single lead on the other end is a different color, but color codes vary by manufacturer and standard; check the sensor data sheet.

How long can an RTD cable be?

With 3-wire or 4-wire connections and matched leads, hundreds of feet can work. The limits are lead mismatch (3-wire), noise pickup and the instrument’s maximum lead resistance; use the calculator to estimate error.

Is an RTD more accurate than a thermocouple?

Generally yes. TI notes RTDs are more accurate and interchangeable thanks to tight tolerance standards, while thermocouples cover wider ranges and respond faster. See cold junction compensation for thermocouple measurement.

Sources and Further Reading