A 1200/5 CT (also written 1200:5) is a current transformer that outputs 5 A when 1200 A flows through its primary. Its ratio is 240:1, so divide primary current by 240 to find the secondary current, or multiply a secondary reading by 240 to find the primary current. To apply one correctly, you also need to check its rating factor, burden, accuracy class and, on a multi-ratio CT, the tap in use.
| Specification | 1200/5 CT value |
|---|---|
| Ratio | 240:1 |
| Meter multiplier | 240 |
| Secondary at 1200 A | 5 A |
| Secondary at 600 A | 2.5 A |
| Ideal secondary turns | 240 (single primary pass) |
| Full-ratio terminals | X1-X5 on a standard multi-ratio CT |
| 20 times rated current | 24,000 A primary, 100 A secondary |
How to Calculate a 1200/5 CT Ratio
The ratio is the rated primary current divided by the rated secondary current: 1200 / 5 = 240. That single number handles every conversion you need in the field.
Isecondary = Iprimary / 240
Iprimary = Isecondary × 240
| Primary current | Secondary current | % of rated |
|---|---|---|
| 120 A | 0.50 A | 10% |
| 300 A | 1.25 A | 25% |
| 600 A | 2.50 A | 50% |
| 900 A | 3.75 A | 75% |
| 1200 A | 5.00 A | 100% |
| 1596 A | 6.65 A | 133% (needs RF 1.33 or higher) |
1200:5 Multi-Ratio CT Taps and Wiring
Many 1200:5 CTs are multi-ratio. The secondary winding has five terminals, X1 to X5, and the pair you connect sets the ratio. IEEE C57.13-2016 Table 11 gives the standard arrangement below. Connect the meter or relay to the chosen pair and leave the unused taps unconnected.
| Ratio | Terminals | Turns / multiplier | Approx. voltage if rated C400 |
|---|---|---|---|
| 100:5 | X2-X3 | 20 | 33 V |
| 200:5 | X1-X2 | 40 | 67 V |
| 300:5 | X1-X3 | 60 | 100 V |
| 400:5 | X4-X5 | 80 | 133 V |
| 500:5 | X3-X4 | 100 | 167 V |
| 600:5 | X2-X4 | 120 | 200 V |
| 800:5 | X1-X4 | 160 | 267 V |
| 900:5 | X3-X5 | 180 | 300 V |
| 1000:5 | X2-X5 | 200 | 333 V |
| 1200:5 | X1-X5 | 240 | 400 V |
CT Rating Factor Explained
The thermal current rating factor (RF) tells you how far above nameplate current a CT can run continuously without overheating. IEEE standard values are 1.33, 1.5, 2.0, 3.0 and 4.0, and the RF is based on a 30°C average ambient unless the nameplate says otherwise. Some manufacturers also list 1.0 and 1.25.
| Rating factor | Continuous primary | Secondary current |
|---|---|---|
| 1.0 | 1200 A | 5.00 A |
| 1.33 | 1596 A | 6.65 A |
| 1.5 | 1800 A | 7.50 A |
| 2.0 | 2400 A | 10.00 A |
| 3.0 | 3600 A | 15.00 A |
| 4.0 | 4800 A | 20.00 A |
Ambient temperature matters. GE’s application guide gives a typical nameplate example of RF 2.0 at 30°C falling to RF 1.5 at 55°C, which is why a CT inside hot switchgear may not carry what its 30°C figure suggests. On a multi-ratio CT, the stated RF normally refers to the highest ratio unless the maker says otherwise, so check the datasheet before relying on it at a lower tap.
CT Burden: What It Is and How to Calculate It
Burden is the total impedance connected to the CT secondary, including the meter or relay, the leads and any connections. More burden forces the CT to produce more voltage, and that pushes it closer to saturation and larger errors.
| Burden | Impedance | VA at 5 A | Power factor | Used for |
|---|---|---|---|---|
| B-0.1 | 0.1 Ω | 2.5 | 0.9 | Metering |
| B-0.2 | 0.2 Ω | 5.0 | 0.9 | Metering |
| B-0.5 | 0.5 Ω | 12.5 | 0.9 | Metering |
| B-0.9 | 0.9 Ω | 22.5 | 0.9 | Metering |
| B-1.8 | 1.8 Ω | 45.0 | 0.9 | Metering |
| B-1 | 1.0 Ω | 25 | 0.5 | Relaying |
| B-2 | 2.0 Ω | 50 | 0.5 | Relaying |
| B-4 | 4.0 Ω | 100 | 0.5 | Relaying |
| B-8 | 8.0 Ω | 200 | 0.5 | Relaying |
Worked example: lead and device burden
A device with a 0.1 Ω burden sits 100 ft from the CT. The current travels out and back, so use a 200 ft round trip. NEC Chapter 9 Table 8 lists stranded copper at 1.24 Ω per 1000 ft for 10 AWG and 1.98 Ω per 1000 ft for 12 AWG at 75°C.
| Item | 10 AWG leads | 12 AWG leads |
|---|---|---|
| Lead resistance (200 ft) | 0.248 Ω | 0.396 Ω |
| Device burden | 0.100 Ω | 0.100 Ω |
| Total burden | 0.348 Ω | 0.496 Ω |
| VA at 5 A (I²Z) | 8.7 VA | 12.4 VA |
| Fits within B-0.5? | Yes, with margin | Only just |
The example shows why lead size and CT location matter. The same run in 12 AWG uses almost the entire B-0.5 allowance, leaving no margin for terminal resistance or an added device.
CT Accuracy Classes: Metering vs Relaying
A CT nameplate usually states accuracy for metering, relaying or both. The two serve different goals. Metering needs precision at normal load, while relaying needs a usable signal during a fault.
Metering accuracy
| Class | Limit at 100% rated | Limit at 10% rated | Limit at 5% rated |
|---|---|---|---|
| 0.15 | ±0.15% | Not specified | ±0.30% |
| 0.15S | ±0.15% | Not specified | ±0.15% |
| 0.3 | ±0.3% | ±0.6% | None |
| 0.3S | ±0.3% | Not specified | ±0.3% |
| 0.6 | ±0.6% | ±1.2% | None |
| 1.2 | ±1.2% | ±2.4% | None |
A designation such as 0.3 B-0.5 means class 0.3 accuracy with any burden up to B-0.5. On a 1200/5 CT, class 0.3 has no stated accuracy below 120 A. A feeder that spends most of its time at 80 A would be better served by a lower ratio or an S-class CT.
Relaying accuracy
A relay class such as C400 means the CT can deliver 400 V at its terminals at 20 times rated secondary current (100 A) into a B-4 burden, with no more than 10% ratio error. The “C” means performance can be calculated from the CT’s characteristics. Standard C classes include C100, C200, C400 and C800.
The rating applies only to the full winding. As SEL explains, tapping a CT down reduces its accuracy because fewer turns are in use. With evenly distributed turns, a C400 1200:5 CT used at 600:5 behaves roughly like a C200. If the turns are not evenly distributed, it may perform worse, so use the maker’s excitation curve for that tap.
How to Size a 1200/5 CT
- Find the maximum continuous current, including realistic growth. It must not exceed the rated current times the RF at your ambient temperature.
- Check the minimum normal load. For class 0.3, it should stay above 10% of rated current, or 120 A on the full 1200:5 ratio.
- Add up the burden of the device, leads and connections, then pick a CT rated for it.
- Check the fault current for protection CTs, including the voltage required at the actual tap.
- Match the insulation class, window size and mounting to the bus or cable.
- Confirm the device input, because some relays and meters are available in 1 A and 5 A versions.
Worked example: protection check
A feeder carries 900 A with an available fault current of 18,000 A. A C400 1200:5 CT feeds a relay through the 0.348 Ω circuit from the earlier example.
| Check | 1200:5 tap | 600:5 tap |
|---|---|---|
| Normal secondary current | 3.75 A | 7.50 A (exceeds 5 A rating without suitable RF) |
| Fault secondary current | 75 A | 150 A |
| Fault as multiple of rated | 15 times | 30 times (beyond the 20 times class point) |
| Terminal voltage (I × Z) | 26.1 V | 52.2 V |
| Approximate C capability | C400 | About C200 |
| Verdict | Suitable first choice | Not suitable for this load |
For the wider protection scheme, see our guides to types of protection relays, protection coordination and ANSI device numbers. After installation, relay testing confirms that the CT circuit and relay settings work together.
Common 1200/5 CT Problems
| Symptom | Likely cause | What to check |
|---|---|---|
| Reading is half or double | Wrong tap or ratio entered | Compare terminals with the meter setting |
| Negative power reading | CT polarity reversed | H1 and X1 orientation |
| Low reading under fault | CT saturation | Burden, tap and C class |
| Hot terminal block | Loose secondary connection | De-energize or short the CT, then re-terminate |
| Humming or buzzing CT | Possible open secondary | Treat as dangerous and follow the isolation plan |
Large services often use parallel conductor sets. If your meter reads half the expected current, see CT meter shows half current on generator switchover.
Frequently Asked Questions
What does 1200/5 mean on a current transformer?
It means the CT produces 5 A in its secondary when 1200 A flows in its primary. The ratio is 240:1, so the secondary current is always the primary current divided by 240.
What is the multiplier for a 1200/5 CT?
The multiplier is 240. Multiply the secondary reading by 240 to get primary amps. A reading of 3.2 A means 768 A is flowing in the primary.
How many turns does a 1200:5 CT have?
An ideal 1200:5 CT with a single primary pass has 240 secondary turns. Real CTs may use small turns corrections to meet their accuracy class.
Can a 1200/5 CT carry more than 1200 A?
Only if its thermal rating factor allows it. With RF 1.33 at 30°C, it can carry about 1596 A continuously. With RF 1.0, the limit is 1200 A.
What does C400 mean on a 1200/5 CT?
C400 means the CT can deliver 400 V at its terminals at 20 times rated secondary current (100 A) into a standard B-4 burden, with no more than 10% ratio error. The rating applies to the full 1200:5 winding.
Which terminals give 600:5 on a 1200:5 multi-ratio CT?
Under the standard IEEE C57.13 tap table, 600:5 is connected across X2 and X4. Always confirm this against the CT nameplate before wiring.
What happens if a CT secondary is left open?
The CT tries to keep driving current into an open circuit, so the secondary voltage can rise to a dangerous level. This can injure people and damage the CT. Short the secondary before removing any device from an energized circuit.
Is a 1200/5 CT accurate at low current?
A class 0.3 CT has no accuracy requirement below 10% of rated current, which is 120 A on a 1200/5 CT. If the load often runs lower, consider a smaller ratio or an extended-range class such as 0.3S.
Sources and Further Reading
- ABB: IEEE C57.13-2016 Standard Ratings: tap, burden and metering accuracy tables.
- ABB: Instrument Transformers Application Guide: rating factor and relay accuracy classes.
- GE: Instrument Transformer Basic Technical Information: rating factor, ambient temperature and open-secondary voltage.
- SEL: Beyond the Knee Point, A Practical Guide to CT Saturation: C ratings on tapped CTs.
- Measurement Canada: S-E-07 Instrument Transformer Specifications: rating factor on multi-ratio CTs.
- PDH Online: Voltage Drop Tables (NEC Table 8 values): stranded copper values used in the lead example.
- IEEE C57.13: the standard for instrument transformers.