CT Ratio 1200/5: Rating Factor, Burden and Sizing Guide

By editor Updated 9 min read
Toroidal 1200/5 current transformer around a 1200 amp conductor with X1 to X5 secondary terminals and a 5 amp output

A 1200/5 CT (also written 1200:5) is a current transformer that outputs 5 A when 1200 A flows through its primary. Its ratio is 240:1, so divide primary current by 240 to find the secondary current, or multiply a secondary reading by 240 to find the primary current. To apply one correctly, you also need to check its rating factor, burden, accuracy class and, on a multi-ratio CT, the tap in use.

Specification1200/5 CT value
Ratio240:1
Meter multiplier240
Secondary at 1200 A5 A
Secondary at 600 A2.5 A
Ideal secondary turns240 (single primary pass)
Full-ratio terminalsX1-X5 on a standard multi-ratio CT
20 times rated current24,000 A primary, 100 A secondary
Quick reference for a 1200/5 current transformer.
Safety first: Never open the secondary of an energized CT. Short it first with a shorting block or CT-rated test switch. An open secondary can develop a lethal voltage.
240:1
Current ratio
5 A
Rated secondary current
X1-X5
Full 1200:5 winding
120 A
Lowest class 0.3 accuracy point

How to Calculate a 1200/5 CT Ratio

The ratio is the rated primary current divided by the rated secondary current: 1200 / 5 = 240. That single number handles every conversion you need in the field.

CT ratio = 1200 / 5 = 240
Isecondary = Iprimary / 240
Iprimary = Isecondary × 240
How a 1200/5 current transformer scales currentA primary current of 1200 amps passes through a 240 to 1 current transformer and produces 5 amps in the secondary circuit.How a 1200/5 CT scales currentPrimary current1200 ARatio240:1Secondary current5 ASecondary amps = primary amps / 240. Primary amps = secondary amps x 240.IndustrialBasicsindustrialbasics.com
Figure 1: A 1200/5 CT divides the primary current by 240.
Primary currentSecondary current% of rated
120 A0.50 A10%
300 A1.25 A25%
600 A2.50 A50%
900 A3.75 A75%
1200 A5.00 A100%
1596 A6.65 A133% (needs RF 1.33 or higher)
Primary to secondary conversion for a 1200/5 CT.
Reader tip: When programming a meter or relay, check whether it asks for the CT ratio (240), or the primary and secondary values (1200 and 5). Entering the wrong one is a common cause of readings that are off by a large factor.

1200:5 Multi-Ratio CT Taps and Wiring

Many 1200:5 CTs are multi-ratio. The secondary winding has five terminals, X1 to X5, and the pair you connect sets the ratio. IEEE C57.13-2016 Table 11 gives the standard arrangement below. Connect the meter or relay to the chosen pair and leave the unused taps unconnected.

Standard 1200 to 5 multi-ratio tap layoutThe secondary winding sections are 200 between X1 and X2, 100 between X2 and X3, 500 between X3 and X4, and 400 between X4 and X5.Standard 1200:5 tap layout (IEEE C57.13 Table 11)200X1100X2500X3400X4X5Add the sections between two terminals to get the ratio. X2 to X4 = 100 + 500 = 600:5.IndustrialBasicsindustrialbasics.com
Figure 2: Section values are in primary amps. Always confirm the layout on the CT nameplate.
RatioTerminalsTurns / multiplierApprox. voltage if rated C400
100:5X2-X32033 V
200:5X1-X24067 V
300:5X1-X360100 V
400:5X4-X580133 V
500:5X3-X4100167 V
600:5X2-X4120200 V
800:5X1-X4160267 V
900:5X3-X5180300 V
1000:5X2-X5200333 V
1200:5X1-X5240400 V
Standard 1200:5 taps from IEEE C57.13-2016 Table 11. The voltage column assumes evenly distributed turns.
Wiring note: The unused taps on a multi-ratio CT still have voltage induced across them. Keep them insulated and do not ground or jumper them unless the manufacturer’s connection diagram calls for it.

CT Rating Factor Explained

The thermal current rating factor (RF) tells you how far above nameplate current a CT can run continuously without overheating. IEEE standard values are 1.33, 1.5, 2.0, 3.0 and 4.0, and the RF is based on a 30°C average ambient unless the nameplate says otherwise. Some manufacturers also list 1.0 and 1.25.

Rating factorContinuous primarySecondary current
1.01200 A5.00 A
1.331596 A6.65 A
1.51800 A7.50 A
2.02400 A10.00 A
3.03600 A15.00 A
4.04800 A20.00 A
Continuous current for a 1200/5 CT at 30°C ambient, on the full ratio.

Ambient temperature matters. GE’s application guide gives a typical nameplate example of RF 2.0 at 30°C falling to RF 1.5 at 55°C, which is why a CT inside hot switchgear may not carry what its 30°C figure suggests. On a multi-ratio CT, the stated RF normally refers to the highest ratio unless the maker says otherwise, so check the datasheet before relying on it at a lower tap.

CT Burden: What It Is and How to Calculate It

Burden is the total impedance connected to the CT secondary, including the meter or relay, the leads and any connections. More burden forces the CT to produce more voltage, and that pushes it closer to saturation and larger errors.

BurdenImpedanceVA at 5 APower factorUsed for
B-0.10.1 Ω2.50.9Metering
B-0.20.2 Ω5.00.9Metering
B-0.50.5 Ω12.50.9Metering
B-0.90.9 Ω22.50.9Metering
B-1.81.8 Ω45.00.9Metering
B-11.0 Ω250.5Relaying
B-22.0 Ω500.5Relaying
B-44.0 Ω1000.5Relaying
B-88.0 Ω2000.5Relaying
Standard 5 A CT burdens from IEEE C57.13-2016 Table 10.

Worked example: lead and device burden

A device with a 0.1 Ω burden sits 100 ft from the CT. The current travels out and back, so use a 200 ft round trip. NEC Chapter 9 Table 8 lists stranded copper at 1.24 Ω per 1000 ft for 10 AWG and 1.98 Ω per 1000 ft for 12 AWG at 75°C.

Item10 AWG leads12 AWG leads
Lead resistance (200 ft)0.248 Ω0.396 Ω
Device burden0.100 Ω0.100 Ω
Total burden0.348 Ω0.496 Ω
VA at 5 A (I²Z)8.7 VA12.4 VA
Fits within B-0.5?Yes, with marginOnly just
Adding impedances directly is slightly conservative, which is acceptable for a first check.

The example shows why lead size and CT location matter. The same run in 12 AWG uses almost the entire B-0.5 allowance, leaving no margin for terminal resistance or an added device.

CT Accuracy Classes: Metering vs Relaying

A CT nameplate usually states accuracy for metering, relaying or both. The two serve different goals. Metering needs precision at normal load, while relaying needs a usable signal during a fault.

Metering accuracy

ClassLimit at 100% ratedLimit at 10% ratedLimit at 5% rated
0.15±0.15%Not specified±0.30%
0.15S±0.15%Not specified±0.15%
0.3±0.3%±0.6%None
0.3S±0.3%Not specified±0.3%
0.6±0.6%±1.2%None
1.2±1.2%±2.4%None
Derived from the correction factor limits in IEEE C57.13-2016 Table 8. The 100% limit also applies up to the rating factor current.

A designation such as 0.3 B-0.5 means class 0.3 accuracy with any burden up to B-0.5. On a 1200/5 CT, class 0.3 has no stated accuracy below 120 A. A feeder that spends most of its time at 80 A would be better served by a lower ratio or an S-class CT.

Relaying accuracy

A relay class such as C400 means the CT can deliver 400 V at its terminals at 20 times rated secondary current (100 A) into a B-4 burden, with no more than 10% ratio error. The “C” means performance can be calculated from the CT’s characteristics. Standard C classes include C100, C200, C400 and C800.

Approximate C400 voltage capability by tapWith evenly distributed turns, a C400 1200 to 5 CT supports about 400 volts at 1200:5, 300 at 900:5, 200 at 600:5, 133 at 400:5 and 67 at 200:5.What happens to a C400 rating on lower taps1200:5about 400 V900:5about 300 V600:5about 200 V400:5about 133 V200:5about 67 VIndustrialBasicsindustrialbasics.com
Figure 3: The C rating applies to the full winding. Lower taps support proportionally less voltage.

The rating applies only to the full winding. As SEL explains, tapping a CT down reduces its accuracy because fewer turns are in use. With evenly distributed turns, a C400 1200:5 CT used at 600:5 behaves roughly like a C200. If the turns are not evenly distributed, it may perform worse, so use the maker’s excitation curve for that tap.

How to Size a 1200/5 CT

  1. Find the maximum continuous current, including realistic growth. It must not exceed the rated current times the RF at your ambient temperature.
  2. Check the minimum normal load. For class 0.3, it should stay above 10% of rated current, or 120 A on the full 1200:5 ratio.
  3. Add up the burden of the device, leads and connections, then pick a CT rated for it.
  4. Check the fault current for protection CTs, including the voltage required at the actual tap.
  5. Match the insulation class, window size and mounting to the bus or cable.
  6. Confirm the device input, because some relays and meters are available in 1 A and 5 A versions.

Worked example: protection check

A feeder carries 900 A with an available fault current of 18,000 A. A C400 1200:5 CT feeds a relay through the 0.348 Ω circuit from the earlier example.

Check1200:5 tap600:5 tap
Normal secondary current3.75 A7.50 A (exceeds 5 A rating without suitable RF)
Fault secondary current75 A150 A
Fault as multiple of rated15 times30 times (beyond the 20 times class point)
Terminal voltage (I × Z)26.1 V52.2 V
Approximate C capabilityC400About C200
VerdictSuitable first choiceNot suitable for this load
A simplified steady-state check. Real fault studies must include DC offset, remanence and CT winding resistance.

For the wider protection scheme, see our guides to types of protection relays, protection coordination and ANSI device numbers. After installation, relay testing confirms that the CT circuit and relay settings work together.

Common 1200/5 CT Problems

SymptomLikely causeWhat to check
Reading is half or doubleWrong tap or ratio enteredCompare terminals with the meter setting
Negative power readingCT polarity reversedH1 and X1 orientation
Low reading under faultCT saturationBurden, tap and C class
Hot terminal blockLoose secondary connectionDe-energize or short the CT, then re-terminate
Humming or buzzing CTPossible open secondaryTreat as dangerous and follow the isolation plan
Typical faults on 1200/5 CT circuits.
Safety note: Before working on CT wiring, follow your lockout/tagout procedure, assess arc flash risk and wear suitable electrical PPE. This guide is educational and does not replace the IEEE standard, the CT datasheet or a qualified engineer’s fault study.

Large services often use parallel conductor sets. If your meter reads half the expected current, see CT meter shows half current on generator switchover.

Frequently Asked Questions

What does 1200/5 mean on a current transformer?

It means the CT produces 5 A in its secondary when 1200 A flows in its primary. The ratio is 240:1, so the secondary current is always the primary current divided by 240.

What is the multiplier for a 1200/5 CT?

The multiplier is 240. Multiply the secondary reading by 240 to get primary amps. A reading of 3.2 A means 768 A is flowing in the primary.

How many turns does a 1200:5 CT have?

An ideal 1200:5 CT with a single primary pass has 240 secondary turns. Real CTs may use small turns corrections to meet their accuracy class.

Can a 1200/5 CT carry more than 1200 A?

Only if its thermal rating factor allows it. With RF 1.33 at 30°C, it can carry about 1596 A continuously. With RF 1.0, the limit is 1200 A.

What does C400 mean on a 1200/5 CT?

C400 means the CT can deliver 400 V at its terminals at 20 times rated secondary current (100 A) into a standard B-4 burden, with no more than 10% ratio error. The rating applies to the full 1200:5 winding.

Which terminals give 600:5 on a 1200:5 multi-ratio CT?

Under the standard IEEE C57.13 tap table, 600:5 is connected across X2 and X4. Always confirm this against the CT nameplate before wiring.

What happens if a CT secondary is left open?

The CT tries to keep driving current into an open circuit, so the secondary voltage can rise to a dangerous level. This can injure people and damage the CT. Short the secondary before removing any device from an energized circuit.

Is a 1200/5 CT accurate at low current?

A class 0.3 CT has no accuracy requirement below 10% of rated current, which is 120 A on a 1200/5 CT. If the load often runs lower, consider a smaller ratio or an extended-range class such as 0.3S.

Sources and Further Reading