Ufer Ground: Copper to Rebar Connections in Concrete

By editor 6 min read
Concrete footing in soil with rebar, a stub-up, a clamp and a 4 AWG copper grounding conductor

A Ufer ground is a concrete-encased grounding electrode: at least 20 ft of ½ in. rebar or 4 AWG bare copper, inside at least 2 in. of concrete that is in direct contact with the earth. It is covered by NEC 250.52(A)(3). Connect copper to the rebar with a listed clamp or exothermic weld. The part of the grounding electrode conductor serving only the Ufer does not need to be larger than 4 AWG copper.

RequirementRebar electrodeCopper electrode
Minimum length20 ft20 ft
Minimum size½ in. (#4)4 AWG bare copper
SurfaceBare, zinc-galvanized or conductive coatingBare
Concrete coverAt least 2 in.At least 2 in.
LocationFooting or foundation in direct earth contactFooting or foundation in direct earth contact
Concrete-encased electrode basics under NEC 250.52(A)(3). Confirm the edition adopted locally.
Plan ahead: Coordinate the electrode before the concrete pour, because hidden connections cannot be inspected or fixed easily. Your local inspector may need to see the electrode first.
20 ft
Minimum length
½ in.
Minimum rebar
2 in.
Concrete cover
4 AWG
Copper GEC cap

How a Ufer Ground Works

Concrete-encased electrode requirementsA footing in direct contact with earth containing at least 20 feet of half inch rebar or 4 AWG bare copper with at least 2 inches of concrete cover.What makes a footing a Ufer groundAt least 2 in. of concreteAt least 20 ft of ½ in. rebar, or 4 AWG bare copperFooting or foundation in direct contact with earthNo continuous insulating barrier between concrete and soilIndustrialBasicsindustrialbasics.com
Figure 1: The electrode must be in concrete that is in direct contact with the earth.

Concrete in contact with soil provides a large contact area with the earth. Embedding the electrode in that concrete turns the building’s foundation into part of the earthing system. The name comes from Herbert G. Ufer, who is associated with its development during World War II work at military sites in Arizona.

If you are new to the terminology, our guide to earthing vs grounding explains how these terms are used.

What Qualifies as a Ufer Ground

SituationQualifies?Why
20 ft of bare ½ in. rebar in a footingYesMeets length, size and encasement
Several tied bars totaling 20 ftYesBars may be joined by tie wire, welding or another effective means
20 ft of 4 AWG bare copper in a footingYesCopper option
Zinc-galvanized rebarYesConductive coating
Ordinary epoxy-coated rebarNoCoating is insulating
Footing isolated by a continuous barrierNoNo direct earth contact
Rebar with less than 2 in. of coverNoDoes not meet encasement
Common site conditions.
Reader tip: A slab over a vapor barrier may not qualify, but the perimeter footing beside it might. Check the actual section drawing rather than assuming the whole foundation is the same.

Where a qualifying concrete-encased electrode is present, it forms part of the grounding electrode system under NEC 250.50. If a building has several, only one needs to be connected. In an existing building, rebar that cannot be reached without disturbing the concrete is generally treated differently, so ask the local authority.

Copper to Rebar Connections

Copper to rebar connection pathA rebar stub-up connects through a listed clamp or exothermic weld to a copper grounding electrode conductor that runs to the service.Connecting copper to the rebarRebar stub-upContinuous with the electrodeListed connectorClamp or exothermic weldCopper GECSized from Table 250.66ServiceGrounded systemAvoid hose clamps, unlisted parts and ordinary clamps not rated for the locationIndustrialBasicsindustrialbasics.com
Figure 2: The connection must be listed for its location, including concrete encasement if it will be buried.
MethodUseCheck
Listed rebar clampCommon for stub-upsListed for the rebar and conductor size
Direct-burial or encasement-rated clampConnections in concrete or earthMarked for that location
Exothermic weldPermanent connectionCorrect mold and procedure
Irreversible compressionPermanent connectionListed connector and correct tool
Hose clamp or unlisted partDo not useFails inspection
Connection methods. Follow the connector listing and instructions.
  1. Identify the rebar that forms the 20 ft electrode.
  2. Confirm the bars are continuous through ties or another effective means.
  3. Bring out a stub-up, or plan a connection point before the pour.
  4. Select a connector listed for both the rebar and conductor size.
  5. Keep any accessible clamp protected and available for inspection.
  6. Route the copper conductor to the service and protect it from damage.

Sizing the Grounding Electrode Conductor

Start with NEC Table 250.66. Section 250.66(B) then sets a cap: the part of the conductor that goes only to the concrete-encased electrode is not required to be larger than 4 AWG copper. The cap does not make a smaller table size larger.

Service conductor (copper)Table 250.66 GECTo Ufer only
2 AWG8 AWG Cu8 AWG Cu
1/0 AWG6 AWG Cu6 AWG Cu
3/0 AWG4 AWG Cu4 AWG Cu
350 kcmil2 AWG Cu4 AWG Cu
500 kcmil1/0 AWG Cu4 AWG Cu
Over 1100 kcmil3/0 AWG Cu4 AWG Cu
Worked sizes from Table 250.66 with the 250.66(B) limit.

Example: a service with 500 kcmil copper conductors has a Table 250.66 GEC of 1/0 AWG copper. A conductor running only to the Ufer can be 4 AWG copper. If that same conductor continues on to a water pipe electrode, the 4 AWG limit no longer applies to the section feeding it.

Ufer Ground vs Ground Rod

FactorUfer groundGround rod
InstalledBefore the concrete pourCan be added later
Length in contactAt least 20 ftRod length
Supplemental electrodeNot required for a single compliant electrodeA single rod may need one
GEC limit4 AWG copper6 AWG copper
Main riskMissed before the pourPoor soil contact
Comparison under the guidance reviewed.

The rules for conductors connected to other electrodes are explained in our ground wire size chart and Table 250.66 guides.

Safety note: This guide is educational. Grounding work must follow the adopted electrical code, connector listings and your local inspector’s requirements. Isolate the system and follow your lockout/tagout procedure before working on an existing grounding conductor.

Frequently Asked Questions

What is a Ufer ground?

It is a concrete-encased grounding electrode. Rebar or bare copper inside a footing or foundation uses the concrete’s contact with the earth to form a grounding electrode.

What are the NEC requirements for a Ufer ground?

NEC 250.52(A)(3) calls for at least 20 ft of ½ in. or larger rebar, or 4 AWG or larger bare copper, encased in at least 2 in. of concrete that is in direct contact with the earth.

What size wire goes to a Ufer ground?

Start with Table 250.66. The part of the conductor that serves only the concrete-encased electrode is not required to be larger than 4 AWG copper, and smaller table sizes still apply.

How do you connect copper to rebar?

Use a connector listed for the purpose, such as a listed rebar clamp, or an exothermic weld. If it will be buried in concrete, it must be suitable for encasement.

Can epoxy-coated rebar be used for a Ufer ground?

No. The rebar must be bare, zinc-galvanized or have another electrically conductive coating. Ordinary epoxy coating does not qualify.

Does a vapor barrier stop a Ufer ground from working?

A continuous barrier that isolates the concrete from the earth can disqualify it. A perimeter footing in contact with soil may still qualify, so evaluate the actual construction.

Does a Ufer ground need a ground rod too?

A single compliant concrete-encased electrode does not need a supplemental rod under the NEC guidance reviewed here. Local rules can add requirements.

Why is it called a Ufer ground?

It is named after Herbert G. Ufer, the engineer associated with its development during World War II work at military sites in Arizona.