250.66 NEC Notes: Table Note 1 vs Note 2 Explained

By editor 5 min read
Two 500 kcmil conductors adding to 1000 kcmil under Note 1 for a 2/0 AWG grounding electrode conductor, with Note 2 below

NEC Table 250.66 Note 1 applies when multiple sets of service-entrance conductors are used: add the corresponding conductors and size the GEC from the largest sum. Note 2 applies when there are no service-entrance conductors: size the GEC from the largest service-entrance conductor that would be required for the load. For the full sizing table and rod limits, see our main guide to NEC Table 250.66.

NoteWhen it appliesWhat to do
Note 1Multiple sets of service-entrance conductorsUse the largest sum of corresponding conductors
Note 2No service-entrance conductorsUse the largest SE conductor required for the load
Note 3All installationsFollow the restrictions in 250.64
Table 250.66 notes as printed in the NFPA Article 250 fact sheet.
Check locally: Your local authority enforces its adopted NEC edition. Confirm the note wording and numbering in that edition before you finalize a design.
Largest sum
Note 1 rule
Required size
Note 2 rule
1000 kcmil
2 × 500 kcmil
3/0 AWG
Copper table maximum

Note 1 Calculator

Enter the conductors in each parallel set. The calculator adds each phase and reads the table using the largest total.

Table 250.66 Note 1 Calculator
SetPhase APhase BPhase C
IndustrialBasics calculator. It does not apply the 250.66(A), (B) or (C) electrode limits.

How Note 1 Works

Table 250.66 Note 1 exampleTwo sets have phase sums of 1000, 850 and 700 kcmil. The largest sum, 1000 kcmil, is used and requires a 2/0 AWG copper grounding electrode conductor.Note 1: add corresponding conductors in each setPhase APhase BPhase CSet 1500500350Set 2500350350Sum1000850700Largest sum: 1000Copper GEC: 2/0 AWGIndustrialBasicsindustrialbasics.com
Figure 1: Use the largest sum of corresponding conductors, in kcmil copper.

Note 1 applies where multiple sets of service-entrance conductors connect directly to a service drop, overhead service conductors, underground service conductors or a service lateral. The key word is corresponding: add the A-phase conductors of each set, then do the same for B and C.

  1. List the conductor size for each phase in every set.
  2. Add the areas for each phase separately.
  3. Take the largest phase total.
  4. Read the matching row of Table 250.66.
  5. Apply any electrode limit from 250.66(A), (B) or (C).
Reader tip: Do not add A, B and C together. That would overstate the area three times and could select the wrong row.

Note 1 examples

SetsLargest sumTable rowGEC
2 × 500 kcmil Cu1000 kcmilOver 600 through 11002/0 AWG Cu or 4/0 AWG Al
Mixed: A 500+500, B 500+350, C 350+350 Cu1000 kcmilOver 600 through 11002/0 AWG Cu or 4/0 AWG Al
3 × 300 kcmil Al900 kcmilOver 500 through 9001/0 AWG Cu or 3/0 AWG Al
4 × 350 kcmil Cu1400 kcmilOver 11003/0 AWG Cu or 250 kcmil Al
Note 1 examples, read from Table 250.66.

How Note 2 Works

Note 2 covers installations with no service-entrance conductors. There is no installed conductor to read from the table, so you first determine the service-entrance conductor size that the load would require. Then enter the table with that equivalent size.

Example: a calculated load would require 600 kcmil copper service-entrance conductors if they existed. Table 250.66 places 600 kcmil in the over 350 through 600 row, so the GEC is 1/0 AWG copper or 3/0 AWG aluminum or copper-clad aluminum.

Choosing Note 1 or Note 2If service-entrance conductors exist and there are multiple sets, use Note 1. With one set, use its largest conductor. With no service-entrance conductors, use Note 2.Note 1 or Note 2?Are there service-entranceconductors?YesNoMultiple sets?Yes: Note 1, largest sum of areasUse Note 2Largest SE conductor required for the loadOne set: use its largest conductorThen read Table 250.66IndustrialBasicsindustrialbasics.com
Figure 2: A quick route through the table notes.

Note 1 vs Note 2 at a Glance

QuestionNote 1Note 2
Do SE conductors exist?Yes, in multiple setsNo
Size is based onInstalled conductorsConductor the load would require
Main calculationSum of corresponding conductorsRequired conductor size from the load
Common mistakeAdding all phases togetherUsing the overcurrent device rating directly
Comparing the two notes.

After the Table: Electrode Limits

The notes find the table size. A portion that connects only to a rod, pipe or plate may still be limited to 6 AWG copper or 4 AWG aluminum. A portion that connects only to a concrete-encased electrode may be limited to 4 AWG copper, as explained in our Ufer ground guide. These limits do not apply if the conductor continues on to an electrode that needs a larger size.

Do not confuse the GEC with an equipment grounding conductor, which is covered in our ground wire size chart. For the wider system, see types of earthing systems.

Safety note: This guide is educational. Grounding design and installation must follow the adopted electrical code and your local inspector’s requirements.

Frequently Asked Questions

What does Note 1 to NEC Table 250.66 say?

If multiple sets of service-entrance conductors connect directly to a service drop, overhead service conductors, underground service conductors or a service lateral, use the largest sum of the areas of the corresponding conductors of each set.

What does Note 2 to Table 250.66 say?

Where there are no service-entrance conductors, size the grounding electrode conductor from the equivalent size of the largest service-entrance conductor required for the load served.

What is the difference between Note 1 and Note 2?

Note 1 is used when multiple actual sets exist, so you add their areas. Note 2 is used when no service-entrance conductors exist, so you size from what the load would require.

Do I add all phases together under Note 1?

No. Add the corresponding conductors across the sets, such as all A-phase conductors, then use the largest phase total.

What GEC is required for two sets of 500 kcmil copper?

The equivalent area is 1000 kcmil, which falls in the over 600 through 1100 row and requires a 2/0 AWG copper GEC.

Does Note 1 increase the GEC past 3/0 copper?

No. Table 250.66 tops out at 3/0 AWG copper or 250 kcmil aluminum or copper-clad aluminum.

Do the rod and concrete electrode limits still apply?

Yes. After finding the table size, 250.66(A), (B) and (C) can limit the portion that connects only to those electrodes.

What is Note 3 to Table 250.66?

It refers you to the installation restrictions in 250.64.