NEC Table 250.66 Note 1 applies when multiple sets of service-entrance conductors are used: add the corresponding conductors and size the GEC from the largest sum. Note 2 applies when there are no service-entrance conductors: size the GEC from the largest service-entrance conductor that would be required for the load. For the full sizing table and rod limits, see our main guide to NEC Table 250.66.
| Note | When it applies | What to do |
|---|---|---|
| Note 1 | Multiple sets of service-entrance conductors | Use the largest sum of corresponding conductors |
| Note 2 | No service-entrance conductors | Use the largest SE conductor required for the load |
| Note 3 | All installations | Follow the restrictions in 250.64 |
Note 1 Calculator
Enter the conductors in each parallel set. The calculator adds each phase and reads the table using the largest total.
| Set | Phase A | Phase B | Phase C |
|---|
How Note 1 Works
Note 1 applies where multiple sets of service-entrance conductors connect directly to a service drop, overhead service conductors, underground service conductors or a service lateral. The key word is corresponding: add the A-phase conductors of each set, then do the same for B and C.
- List the conductor size for each phase in every set.
- Add the areas for each phase separately.
- Take the largest phase total.
- Read the matching row of Table 250.66.
- Apply any electrode limit from 250.66(A), (B) or (C).
Note 1 examples
| Sets | Largest sum | Table row | GEC |
|---|---|---|---|
| 2 × 500 kcmil Cu | 1000 kcmil | Over 600 through 1100 | 2/0 AWG Cu or 4/0 AWG Al |
| Mixed: A 500+500, B 500+350, C 350+350 Cu | 1000 kcmil | Over 600 through 1100 | 2/0 AWG Cu or 4/0 AWG Al |
| 3 × 300 kcmil Al | 900 kcmil | Over 500 through 900 | 1/0 AWG Cu or 3/0 AWG Al |
| 4 × 350 kcmil Cu | 1400 kcmil | Over 1100 | 3/0 AWG Cu or 250 kcmil Al |
How Note 2 Works
Note 2 covers installations with no service-entrance conductors. There is no installed conductor to read from the table, so you first determine the service-entrance conductor size that the load would require. Then enter the table with that equivalent size.
Example: a calculated load would require 600 kcmil copper service-entrance conductors if they existed. Table 250.66 places 600 kcmil in the over 350 through 600 row, so the GEC is 1/0 AWG copper or 3/0 AWG aluminum or copper-clad aluminum.
Note 1 vs Note 2 at a Glance
| Question | Note 1 | Note 2 |
|---|---|---|
| Do SE conductors exist? | Yes, in multiple sets | No |
| Size is based on | Installed conductors | Conductor the load would require |
| Main calculation | Sum of corresponding conductors | Required conductor size from the load |
| Common mistake | Adding all phases together | Using the overcurrent device rating directly |
After the Table: Electrode Limits
The notes find the table size. A portion that connects only to a rod, pipe or plate may still be limited to 6 AWG copper or 4 AWG aluminum. A portion that connects only to a concrete-encased electrode may be limited to 4 AWG copper, as explained in our Ufer ground guide. These limits do not apply if the conductor continues on to an electrode that needs a larger size.
Do not confuse the GEC with an equipment grounding conductor, which is covered in our ground wire size chart. For the wider system, see types of earthing systems.
Frequently Asked Questions
What does Note 1 to NEC Table 250.66 say?
If multiple sets of service-entrance conductors connect directly to a service drop, overhead service conductors, underground service conductors or a service lateral, use the largest sum of the areas of the corresponding conductors of each set.
What does Note 2 to Table 250.66 say?
Where there are no service-entrance conductors, size the grounding electrode conductor from the equivalent size of the largest service-entrance conductor required for the load served.
What is the difference between Note 1 and Note 2?
Note 1 is used when multiple actual sets exist, so you add their areas. Note 2 is used when no service-entrance conductors exist, so you size from what the load would require.
Do I add all phases together under Note 1?
No. Add the corresponding conductors across the sets, such as all A-phase conductors, then use the largest phase total.
What GEC is required for two sets of 500 kcmil copper?
The equivalent area is 1000 kcmil, which falls in the over 600 through 1100 row and requires a 2/0 AWG copper GEC.
Does Note 1 increase the GEC past 3/0 copper?
No. Table 250.66 tops out at 3/0 AWG copper or 250 kcmil aluminum or copper-clad aluminum.
Do the rod and concrete electrode limits still apply?
Yes. After finding the table size, 250.66(A), (B) and (C) can limit the portion that connects only to those electrodes.
What is Note 3 to Table 250.66?
It refers you to the installation restrictions in 250.64.