Megging a Motor: 480V Test Values and Procedure

By editor 6 min read
Insulation tester reading 62 megohms at 500 volts DC, connected between a motor terminal and the motor frame

To meg a 480V motor, isolate it, apply 500 V DC between the winding and ground for 1 minute, then correct the reading to 40 °C. For a typical random-wound motor, guidance based on IEEE 43-2013 gives a minimum of 5 MΩ at 40 °C. A single pass is not the whole story: compare the result with earlier readings and check the polarization index when you can.

ItemTypical value for a 480 V random-wound motor
Test voltage500 V DC
Reading time1 minute (IR1)
Minimum IR at 40 °C5 MΩ
PI time10 minutes ÷ 1 minute
Minimum PI1.5 Class A, 2.0 Class B and above
DischargeAt least 4 times the test duration
Values as summarized from IEEE 43-2013 by the sources below. Check the motor maker’s requirements.
Safety first: Test only an isolated, locked-out motor that has been proven dead. Disconnect VFDs, soft starters, surge devices and other electronics. The test voltage can shock you, and the winding stores charge after the test.
500 V DC
Test voltage
5 MΩ
Minimum at 40 °C
2.0
PI, Class B and above
4×
Discharge time

Motor Megger Result Calculator

Motor Megger Result Calculator
IndustrialBasics check for random-wound motors using a 5 MΩ minimum at 40 °C. Do not use below the dew point.

How to Meg a 3 Phase Motor

Motor insulation test connectionThe tester line lead connects to T1, while T2, T3 and the motor frame are connected to the tester ground lead.Test one phase with the others groundedInsulation tester500 V DCT1T2T3Motor windingsLine leadT2, T3 and the frame connected to groundIndustrialBasicsindustrialbasics.com
Figure 1: Repeat for each phase. Testing all three together checks phase to ground only.
  1. Isolate the motor. Apply lockout/tagout and prove it dead.
  2. Disconnect the leads from any VFD, soft starter, capacitor or surge device.
  3. Record conditions: winding temperature, ambient, humidity and time out of service.
  4. Connect the tester. Put the line lead on one phase and ground the other phases and frame.
  5. Apply 500 V DC for 1 minute and record IR1.
  6. Continue to 10 minutes if you need a PI.
  7. Discharge the winding through a suitable grounding path for at least four times the test time.
  8. Repeat for each phase, then correct and compare the results.
Reader tip: Testing all three phases together is quicker, but it checks only phase-to-ground insulation. Testing one phase with the other two grounded also stresses the insulation between phases.

For the basics of the instrument, see our guide to insulation resistance testing.

Minimum Insulation Resistance Values

Minimum IR1 at 40 °CApplies to
5 MΩRandom-wound stator coils, form-wound coils below 1 kV, and DC armatures
100 MΩAC form-wound windings built after about 1970
kV + 1 MΩWindings made before about 1970, field windings and others not listed above
Minimum values as summarized from IEEE 43-2013.

Most 480 V motors are random-wound, so 5 MΩ is usually the relevant value. For an older winding in the kV + 1 category, a 480 V motor works out to 0.48 + 1 = 1.48 MΩ. These are minimums for deciding whether to proceed, not a sign that the motor is in good condition.

Correct the Reading to 40 °C

Insulation resistance changes strongly with temperature, so compare readings at the same reference. Multiply the measured value by the correction factor KT.

R40 = KT × Rmeasured
Winding tempKT thermoplasticKT thermosetting
10 °C0.1250.7
20 °C0.250.8
30 °C0.50.9
40 °C1.01.0
50 °C2.01.5
60 °C4.02.3
70 °C8.03.3
80 °C16.04.6
Correction factors as published by the sources below. Do not apply below the dew point.

Example: a winding reads 12 MΩ at 20 °C. If it is thermosetting, R40 = 0.8 × 12 = 9.6 MΩ, which meets 5 MΩ. If it is thermoplastic, R40 = 0.25 × 12 = 3 MΩ, which does not. Knowing the insulation type can change the decision.

Polarization Index

PI = IR10 min ÷ IR1 min

A clean, dry winding usually keeps absorbing charge, so its resistance rises during the test. For example, 50 MΩ at 1 minute and 130 MΩ at 10 minutes gives a PI of 2.6, which is above the 2.0 minimum for Class B and higher.

PI does not need temperature correction because the factor cancels. It need not be calculated when IR1 is above 5,000 MΩ. Small random-wound motors may finish absorbing within a few minutes, so PI is less useful there, and the trend matters more.

What to Do With the Result

Interpreting motor insulation resultsAfter correcting to 40 degrees and calculating PI, passing results are compared to trend. Low IR with PI near one calls for cleaning and drying. Low results after drying need investigation.What to do with the resultCorrect IR to 40 °CThen calculate PIIR and PI meet minimumsCompare with the trend, then return to serviceLow IR, PI near 1.0Clean and dry, then retest. Do not hipotLow after dryingInvestigate. Do not return to serviceIndustrialBasicsindustrialbasics.com
Figure 2: Based on guidance summarizing IEEE 43-2013.
ResultLikely meaningAction
IR and PI pass, stable trendInsulation looks healthyRecord and return to service
Passes, but sharply lower than last timeDeveloping problemInvestigate before it fails
Low IR, PI near 1.0Moisture or contaminationClean, dry and retest
Still low after dryingInsulation damageFurther diagnosis or repair
One phase is much lowerLocal faultCheck leads, then the winding
Interpreting motor insulation results.

Do not high-potential test a wet or contaminated winding. Insulation resistance also cannot see every fault, so pair it with motor phase angle testing when you suspect shorted turns. Moisture in the connection area is covered in our motor terminal box guide, and other problems are in motor failure causes.

Safety note: This guide is educational and summarizes published guidance on IEEE 43. Follow the standard, the motor manufacturer’s limits and your site procedures.

Frequently Asked Questions

What voltage should I use to meg a 480V motor?

Guidance summarizing IEEE 43-2013 lists 500 V DC for windings rated below 1000 V.

What is a good megger reading on a 480V motor?

For a typical random-wound 480 V motor, the IEEE 43-2013 minimum commonly cited is 5 MΩ at 40 °C. Healthy motors often read far higher, so compare with the motor’s trend.

Is kV + 1 still the minimum for motors?

It remains in the table for windings made before about 1970, field windings and others not otherwise described. Modern random-wound stators use 5 MΩ.

How long should you meg a motor?

Take the insulation resistance at 1 minute. For a polarization index, continue to 10 minutes.

What is a good polarization index?

The cited minimums are 1.5 for Class A and 2.0 for Class B and higher. PI need not be calculated when the 1-minute reading is above 5,000 MΩ.

How do you meg a three-phase motor?

Isolate it, disconnect drives and sensitive devices, then test each phase to ground with the other phases grounded, or test all phases together for a simple phase-to-ground check.

Can you meg a motor connected to a VFD?

Do not apply test voltage to a VFD. Disconnect the motor leads from the drive first and follow the drive maker’s instructions.

How long should a winding be discharged after testing?

Ground it for at least four times the test duration: 4 minutes after a 1-minute test and 40 minutes after a 10-minute test.

Sources and Further Reading

About the author

editor

Leave a Comment