Buchholz Relay: Working Principle, Construction, Diagram and Applications

By editor Updated 23 min read
buchholz relay

A Buchholz relay is a gas- and oil-flow-operated protective device fitted in the pipe between the main tank and the conservator of an oil-filled transformer. It gives an alarm when gas slowly collects inside the transformer, and it trips the transformer when oil surges violently or the oil level falls too far.

That is the short answer. The rest of this guide shows where the relay sits, how it is built and how it works, which faults it detects and misses, and how it is wired, tested and set. It also explains why it sometimes operates when nothing is wrong.

Quick Summary

  • Where: in the pipe from the transformer tank to the conservator.
  • Alarm: slow gas build-up lowers the upper float.
  • Trip: a sudden oil surge moves the flap, or the lower float drops after serious oil loss.
  • Works on: oil-filled transformers and reactors with a conservator, not dry-type or sealed units.
  • Cannot replace: differential and other electrical protection.
  • Origin: developed by Max Buchholz, with a patent filed in 1921.

What Is a Buchholz Relay and Why Is It Used?

Faults inside an oil-filled transformer, such as overheating, a poor joint, damaged core insulation or arcing, break down the oil and paper insulation and release gas. A small, slow fault may not change the line current enough for electrical protection to react quickly. The gas, however, rises towards the conservator and is caught by the relay. A severe fault makes gas so fast that it pushes oil along the pipe, and the relay senses that too.

The IEC calls it a gas and liquid actuated relay, which is why people also say gas and oil actuated. It is a mechanical device. Floats and a flap move, and sealed switches turn that movement into an electrical signal.

This is why it is used alongside electrical protection, not instead of it. Reinhausen states that other protection does not remove the need for a Buchholz relay, because the relay is specifically effective for early-stage faults. For the wider picture, see our guide to types of protection relays.

Max Buchholz, a German engineer at the Prussian electricity company in Kassel, developed the relay. His patent was filed in 1921 and the relay was tested extensively in the mid-1920s. It is still fitted to conservator-type transformers a century later.

Where Is a Buchholz Relay Located in a Transformer?

The relay is mounted in the connecting pipe between the main tank and the conservator, the expansion tank above it. The conservator gives the oil room to expand as it heats and keeps the pipe full of oil. Because the pipe is full, any gas leaving the tank, and any oil pushed towards the conservator, must pass through the relay.

Buchholz relay location diagram A transformer main tank with a pipe rising slightly to the conservator tank. The Buchholz relay is fitted in that pipe and a breather is fitted to the conservator. Main tank core, windings and oil fault gas bubbles Conservator oil expansion tank Breather Buchholz relay gas and oil flow up Pipe rises slightly towards the conservator (slope exaggerated; follow the maker’s limits) Flow arrow on the relay points to the conservator Pipe starts at the highest point of the tank cover
Position of the Buchholz relay between the main tank and the conservator (simplified, not to scale).

Installation Requirements

Poor installation is a common reason for nuisance operation. The values below come from the Reinhausen CEDASPE EB catalogue and the IEC 60076-22-1 preview. Always follow the manual for your own relay.

RequirementReference value
Relay positionEssentially horizontal; up to 5° rise towards the conservator is admissible (IEC 60076-22-1)
Pipe slopeAbout 2° to 4°, maximum 5° (CEDASPE EB); the pipe rises so gas can reach the relay instead of sitting in a low point
Pipe startFrom the highest point of the tank cover; it must not protrude into the tank
Straight pipeAt least 5 pipe diameters before the relay and 3 after it
BendsAvoid right-angle elbows near the relay
Flow arrowMust point from the tank to the conservator

Do not treat one slope as universal. Makers quote different values, so use the figure in your relay’s data sheet. Straight pipe runs matter because they keep the oil flow smooth where the flap sits. For how oil moves inside the tank, see our guide to transformer cooling methods.

Which Transformers Use a Buchholz Relay?

Transformer typeBuchholz relay?Reason
Oil-immersed with conservatorYesHas the tank-to-conservator pipe the relay needs
Oil-filled reactor with conservatorYesSame oil and gas path as a transformer
Sealed or nitrogen-cushioned oil typeNot normallyNo conservator pipe; pressure-rise protection is more relevant
Hermetic conservator with rubber bagSometimesEMB notes it can monitor air-cell failure in some designs
Dry-typeNoNo insulating oil, gas path or conservator

You will often read that a relay is required above 500 kVA or 750 kVA. Those figures appear in study notes, but not in the standards or maker data reviewed for this guide. The rating at which a relay is fitted depends on the utility and the contract, so check the project specification. To see how these units differ, read our guide to the main types of transformers and the comparison of power and distribution transformers.

Construction of a Buchholz Relay

A Buchholz relay is a small oil-tight housing with a few moving parts. The housing is normally cast aluminium, with inspection windows and a scale so you can read the oil level and the volume of collected gas.

Buchholz relay cross-section Labelled cross-section of a double-float Buchholz relay: housing, gas collection space, inspection window with scale, upper float with alarm reed switch, lower float and flap with trip reed switches, gas release valve, test button, terminal box and drain plug. From transformer tank To conservator Gas collection space (oil-filled in normal service) Upper float Lower float Terminal box Gas release valve and test cock Inspection window with gas scale Terminal box Upper float + alarm switch Lower float + trip switch Flap + trip switch (oil surge) (oil loss) Test button Drain plug The flow arrow cast on the housing must point towards the conservator
Simplified cross-section of a double-float Buchholz relay. Red bars are sealed reed switches, black bars are magnets (illustrative; real layouts vary by manufacturer).
PartWhat it does
Relay housingHolds the oil and the moving parts; sits in the pipe and carries the flow arrow
Gas collection chamberThe top of the housing; traps free gas rising from the tank
Inspection window and oil level scaleLets you read the oil level and the volume of gas collected
Upper floatDrops as gas pushes oil out of the chamber; operates the alarm contact
Lower floatDrops if oil loss continues; operates the trip contact
Flap (baffle or damper)Pushed towards the conservator by a fast oil surge; operates the trip contact
Reed switchesA magnet on each float or the flap closes a sealed reed contact
Gas release and sampling valveReleases or draws off gas; a test cock allows air-injection testing where fitted
Test buttonMoves the floats mechanically to prove the alarm and trip circuits
Terminal boxHouses the cable connections for the alarm and trip contacts

Types of Buchholz Relay

TypeHow it differsTypical use
Double-floatUpper float for alarm, lower float for oil loss, plus a flap for surgesStandard choice for power transformers
Single-floatOne float plus a flow damper; alarm and trip functions are combinedSmaller or specific designs (listed by EMB)
Reed-switchSealed reed contacts operated by magnetsCurrent mainstream design
Mercury-switchTilting glass tubes of mercury close the contactsOlder installations
Smart relayAdds gas-volume, temperature and moisture sensorsOnline monitoring; does not replace the mechanical function

Reed switches have largely replaced mercury switches. Their contacts are hermetically sealed, so the relay copes better with vibration and avoids handling mercury. Check that the contact rating suits your trip circuit.

Buchholz Relay Working Principle

The relay reacts to three different conditions: slow gas build-up, a sudden oil surge and loss of oil. The diagram shows what each one does inside the housing.

Buchholz relay operating states Four panels. Normal: chamber full of oil, floats raised. Gas build-up: gas pocket forms and the upper float drops, giving an alarm. Oil surge: the flap is pushed towards the conservator and trips. Oil loss: both floats drop, alarm then trip. 1. Normal service upper lower alarm contact trip contact NO CONTACT CLOSED 2. Slow gas build-up gas upper lower alarm contact trip contact ALARM 3. Sudden oil surge upper lower alarm contact trip contact fast oil surge to conservator TRIP 4. Oil loss gas upper lower alarm contact trip contact ALARM, THEN TRIP
The four operating states of a double-float Buchholz relay (simplified; real layouts vary by manufacturer). Blue is oil, pale amber is gas, the green bar is the flap.

1. Normal Operating Condition

The housing is full of oil and both floats sit at the top. The flap hangs at rest across the oil path, and no contact is closed. Slow oil movement from heating and cooling passes the flap without moving it.

2. Alarm Operation: Slow Gas Build-Up

A minor fault, such as local overheating, produces small gas bubbles. They rise through the oil and collect at the top of the relay. As the gas builds up it pushes oil downwards, the upper float sinks and its magnet closes the alarm contact. The transformer stays in service while someone investigates.

3. Trip Operation: Sudden Oil Surge

A severe fault, such as a winding short circuit, creates gas so quickly that oil is thrown through the pipe towards the conservator. The surge pushes the flap, which closes the trip contact. The trip signal then opens the breakers. Quick isolation keeps damage to the unit as small as possible.

4. Trip Operation: Loss of Oil

If oil leaks out, the level falls in the conservator, then the pipe and finally the relay. The upper float drops first and gives the alarm. If the level keeps falling, the lower float drops and trips the transformer. A transformer running low on oil can lose insulation and cooling, so this protects it from damage that follows. Air entering the oil system behaves in a similar way: it can raise an alarm and, if enough collects, a trip.

Do not mix up the two trip elements

The flap responds to oil flow and trips on a surge. The lower float responds to the oil level and trips on loss of oil. Some study notes describe only two floats, which hides the flap.

Buchholz Relay Alarm vs Trip: Key Differences

ComparisonAlarmTrip
Main purposeEarly fault warningTransformer protection
Main triggerGas accumulation or first drop in oil levelOil surge or continued oil loss
Operating elementUpper floatFlap or lower float, depending on the trigger
ContactAlarm contact closesTrip contact closes
ResponseWarning to annunciator or SCADACircuit breakers open, transformer isolated
Fault conditionOften a developing fault, or trapped airSevere fault or serious oil loss

An alarm does not always mean a severe fault. The gas may be air from filling or maintenance. A trip does not always mean an internal short circuit either, because loss of oil trips the relay too. Treat both as real until the cause is proved.

After an alarmAfter a trip
Log the time, and check the gas volume and oil level on the relay windowDo not re-energise until the cause is found; Reinhausen warns against immediate re-energisation
Check loading and the oil and winding temperature readingsCheck which other protection operated, such as differential, and read the relay flags
Have qualified staff take a gas sample and an oil sample for analysisInspect for leaks, a low oil level and any pressure relief device operation
Remove the transformer from service if the gas proves to be fault gasTest the unit before return to service, for example insulation resistance and oil analysis

What Faults Does a Buchholz Relay Detect?

The relay responds when a fault produces enough free gas, moves the oil, or lets oil escape. Reinhausen lists poor contacts, core and winding faults, phase, turn and earth faults, and internal bushing puncture as detectable.

ConditionWhat happens insideBuchholz responseOther protection that also helps
Inter-turn short circuitHeat or arcing between turns breaks down the oil and paperAlarm; trip if severeDifferential protection
Winding overheatingHot winding or poor joint decomposes insulationAlarm; trip if severeWinding temperature indicator
Core overheatingLocal hot spots in the core heat the oilAlarm; trip if severeOil testing and DGA
Core insulation failureShort-circuited laminations or failed core-bolt insulationAlarm; trip if severeOil testing and DGA
Internal arcingAn arc makes gas very quickly and throws oilTrip (oil surge)Differential and overcurrent protection
Insulation breakdownPaper or oil insulation fails and releases gasAlarm; trip if severeDifferential protection
Internal bushing punctureBreakdown of a bushing inside the tankAlarm or tripDifferential protection
Partial dischargeSmall discharges make gas, mostly dissolved in the oilAlarm only if enough free gas formsDGA, which usually sees it first
Oil leak or loss of oilThe oil level falls in the relayAlarm, then tripOil level indicator
Air ingressAir enters through a defect or after fillingAlarm; trip if a lot of air collectsCorrect filling and venting

What Faults Does a Buchholz Relay Not Detect?

  • External short circuits: faults on the network outside the tank do not make gas or move oil.
  • External bushing flashovers: a flashover outside the tank is outside the oil system. Surge protection such as a lightning arrester or surge arrester deals with the cause, not this relay.
  • Faults that produce neither enough gas nor oil movement: the relay has nothing to sense.
  • Faults outside the protected oil system: for example the tap-changer compartment, which has its own relay.

This is why the relay cannot replace other transformer protection. It senses gas and oil movement, while differential protection senses a difference in current, and overcurrent protection covers external faults and backup. How the devices work together is covered in protection coordination.

How the Buchholz relay responds to 13 conditions Donut chart: eight of thirteen conditions give an alarm first, one gives a trip on oil surge, one gives alarm then trip on oil loss, three are not directly detected. 13 conditions Alarm first, trip only if severe: 8 of 13 (61.5%) inter-turn, winding and core overheating, core insulation, insulation breakdown, bushing puncture, partial discharge, air ingress Trip on oil surge: 1 of 13 (7.7%) internal arcing or winding short circuit Alarm, then trip on oil loss: 1 of 13 (7.7%) oil leak Not directly detected: 3 of 13 (23.1%) external short circuit, external flashover, no gas or oil movement
Counts of the conditions listed in this guide (ten detected, three not detected). It is a summary of the tables, not field failure statistics.

Buchholz Relay Connection and Wiring Diagram

The relay has separate potential-free contacts for alarm and trip. Both end in the terminal box on the relay housing, and cables run from there to the transformer control and protection circuits. The two circuits stay separate so that an alarm can never be confused with a trip.

Buchholz relay alarm and trip circuit block diagram Separate circuits. The alarm contact feeds an annunciator or SCADA alarm input. The trip contact feeds the master trip relay 86, which trips the high-voltage and low-voltage circuit breakers. Relay terminal box Alarm contact (open) Trip contact (open) Annunciator orSCADA alarm input Alarm in thecontrol room Master trip relay(ANSI 86, lockout) HV breaker trip coil LV breaker trip coil Alarm circuit Trip circuit Alarm and trip use separate contacts, cores and terminals. Supply and return are not shown.
Conceptual block diagram only. Real wiring, contact ratings and terminal numbers follow the relay maker’s drawings and the transformer protection scheme.

Alarm and Trip Connections

The alarm contact feeds a local alarm, an annunciator or a SCADA input. The trip contact feeds the breaker trip circuit, usually through a master trip (lockout) relay, which is ANSI device 86. That relay then trips the high-voltage and low-voltage breakers. See our ANSI device numbers list to decode the numbers, and types of circuit breakers for the devices that clear the trip. Buchholz protection is usually grouped under the pressure and gas-type devices numbered 63, but check the exact wording in IEEE C37.2 before quoting it.

Normally Open and Changeover Contacts

Makers supply normally open and changeover contact options, and some relays have more than one contact per function. A magnet moving towards a reed switch closes it, and moving away opens it. Confirm which type your scheme expects, and check the contact rating against the trip circuit voltage and current. Actual wiring, ratings and terminal layout depend on the relay maker and the protection design, so follow the project drawings.

Buchholz Relay Testing and Maintenance

A Buchholz relay may sit unmoved for years, so you need proof that its contacts and floats will work when needed. These are the common checks:

  • Visual check: oil level, gas volume on the scale, leaks and window condition.
  • Alarm and trip contact test: a self-resetting test button moves the floats mechanically, and a multimeter shows whether each circuit closes.
  • Pneumatic test: where a test cock is fitted, air tests the alarm float, and a sudden air application can test the flap. Bleed the relay and refill it with oil afterwards.
  • Gas collection and sampling: gas is drawn off through the sampling valve for laboratory analysis, never vented casually.
  • Float and flap inspection: a mechanical check that nothing sticks or is damaged, done as the maker’s manual describes.
  • Wiring and contacts: continuity and insulation checks, as in any relay testing programme, plus an insulation resistance test of the cables.

Reinhausen states that the CEDASPE relay needs no periodic maintenance but recommends regular checks. How often you test depends on the maker’s guidance and your utility’s rules. Factory tests by makers such as EMB include dielectric, leakage, functional and flow tests.

Safety

Testing, gas sampling and maintenance must be done only by qualified, authorised people following the maker’s instructions, local regulations and site permits. Collected gas can be explosive or toxic, so keep ignition sources away and use a safe isolation method such as the lockout tagout procedure and suitable electrical safety PPE.

Gas Analysis in a Buchholz Relay: What Does Gas Colour Indicate?

When the alarm operates, the collected gas may be harmless air from filling or maintenance, or fault gas from decomposing oil and insulation. Older guides link the colour of the gas to the cause. Reinhausen’s catalogue lists the traditional associations below, but also advises taking a sample for analysis.

Gas colourTraditional indication
WhitishPaper or cotton insulation involved
YellowishWood or cardboard decomposition
GreyishMagnetic circuit breakdown
BlackFree arcing in oil

Treat colour as a rough clue only. It cannot confirm the exact fault type. Older practice also used flammability to separate fault gas from air, but never ignite the gas as a field test, because it is dangerous and does not identify the fault.

Free-Gas Analysis and Dissolved Gas Analysis (DGA)

Free-gas analysis tests the gas collected in the relay. Dissolved gas analysis (DGA) tests the gases dissolved in an oil sample, and repeated samples show a trend over time. Both are done in a laboratory, and the results are read using IEC 60599 and IEEE C57.104. Our guide to transformer oil testing explains DGA in detail.

GasOften linked with (indicative only)
HydrogenPartial discharge, and most fault types at low level
AcetyleneArcing
EthyleneHigh-temperature overheating of oil
Methane and ethaneLower-temperature overheating of oil
Carbon monoxide and carbon dioxideOverheating of paper insulation

Specialists read gas ratios and amounts together, not single gases, so use the table as background and not as a diagnosis.

Common Causes of Buchholz Relay False Alarms and Trips

CauseWhy it happensWhat to do
Air trapped after oil fillingAir rises and collects like fault gasFill and bleed properly; let gas settle before resetting
Air entering the oil circuitA defect in the oil circulation system draws in airFind and repair the air path; confirm with oil tests
Improper filling or refillingOil level or venting is not right after maintenanceFollow the maker’s filling procedure
Vibration or external disturbanceStrong vibration can move a contactUse vibration-resistant reed designs and correct mounting
Incorrect installationWrong pipe slope, reversed flow arrow or bends near the relayFollow the maker’s and IEC guidance
Setting not matched to pipe sizeFlap setting is wrong for the pipeSelect from the maker’s data
Relay, contact or wiring faultA damaged contact or wiring defect gives a false signalTest the relay and supervise the trip circuit

Only treat a cause as confirmed when you have evidence from the manufacturer or your utility. Reinhausen confirms air from filling as a cause of alarms. Vibration is a design concern, which is why reed switches are used, but it should not be assumed without evidence.

How to Tell a Real Fault from a Nuisance Operation

  1. Bleed the collected gas and watch whether it returns. Gas that keeps coming back points to a fault or an air leak.
  2. Send gas and oil samples for DGA. Fault gases such as acetylene suggest arcing, while clean air does not.
  3. Compare with other signs: temperatures, other relay flags, oil level and any recent oil work.
  4. If the signs point to nothing, test the relay and its wiring for a contact fault.

An alarm should never be assumed to be a nuisance. Repeated alarms need investigation, and a tripped transformer should not be re-energised until the cause is known.

Buchholz Relay vs Other Transformer Protection Devices

DeviceOperating principleCondition detectedLocationType of protection
Buchholz relayFloats and flap respond to gas and oil flowFree gas, oil surge, oil lossPipe between main tank and conservatorEarly and severe internal faults on conservator units
Sudden pressure relay (SPR)Responds to a fast rise in pressureRapid internal pressure riseTank wall or coverFast mechanical trip; works with or without a conservator
Pressure relief device (PRD)Spring-loaded valve opens at a set pressureExcess static pressureTank coverLast mechanical defence against tank rupture
OLTC protective relayFlap responds to oil surge in the tap-changerOil surge in the OLTC compartmentPipe from OLTC head to its conservatorProtects the tap-changer only
Oil level indicatorFloat or gauge reads the oil levelOil level in the conservatorConservatorIndication and alarm; not fault protection
Temperature indicatorReads oil or winding temperatureOverheating and overloadTank top or windingThermal alarm and trip

Buchholz Relay vs Sudden Pressure Relay

  • What it senses: a Buchholz relay senses gas and oil flow. A sudden pressure relay senses a rapid rise in pressure.
  • Where it sits: the Buchholz relay is in the conservator pipe. The sudden pressure relay is on the tank.
  • Slow faults: the Buchholz relay gives an early alarm on slow gas build-up. A sudden pressure relay ignores slow changes and reacts only to fast ones.
  • Transformer type: the Buchholz relay needs a conservator. A sudden pressure relay can also be used on sealed units.

The names are sometimes mixed up. The IEEE PES Relay Committee notes that a flow-sensing sudden pressure relay is commonly called a Buchholz relay in some places, so check what the device actually senses before comparing them.

Buchholz Relay vs Pressure Relief Device, OLTC Relay, Oil Level and Temperature Indicators

A pressure relief device opens to release excess pressure and protect the tank, and it does not warn of slow gas build-up. An on-load tap changer has its own oil compartment, because switching creates arcs, and a separate oil surge relay protects it. It works on a similar surge principle but has its own pipe arrangement and settings, and it does not replace the main-tank relay. Both are used in a typical substation transformer with a tap changer. An oil level indicator only measures level, and a temperature indicator only measures heat, so neither detects gas or oil surge.

The Buchholz relay is slower than differential protection for a major fault, but it catches faults that produce gas without a large change in current.

Applications of a Buchholz Relay

  • Oil-filled power transformers with a conservator.
  • Distribution transformers with a conservator, where the specification calls for one.
  • Oil-filled reactors with a conservator arrangement.
  • On-load tap changers, using a separate protective relay for the tap-changer oil compartment.

A conventional Buchholz relay is not used on dry-type transformers, because they have no oil or gas path. It also does not normally apply to sealed transformers without a conservator pipe. You will find these transformers, and the relays that protect them, in the substation equipment list and alongside switchgear in a typical site.

Advantages and Disadvantages of a Buchholz Relay

Advantages

  • Detects developing internal faults
  • Gives early warning through gas accumulation
  • Separate alarm and trip functions
  • Responds to oil surges and oil loss
  • Gas collected can be analysed to help find the fault

Disadvantages

  • Needs a suitable conservator arrangement
  • Cannot detect every type of fault
  • Can respond to trapped air
  • Needs regular inspection and testing
  • Depends on correct installation and oil flow

Buchholz Relay Standards and Technical Specifications

StandardRelevance
IEC 60076-22-1:2019Protective devices for power transformers, including gas and liquid actuated (Buchholz) relays
IEC 60076 seriesWider guidance on power transformers and their fittings
EN 50216-2European Buchholz relay requirements (legacy reference; check current edition)
IS 3637Indian specification for gas-operated relays (confirm current edition with BIS)
IEC 60599 and IEEE C57.104Interpreting dissolved and free gases
IEEE C37.2Device function numbers

There is no single “standard” setting. Gas volume and oil velocity depend on the maker, the relay model and the pipe size (commonly DN25, DN50 or DN80), so values differ between manufacturers. The charts plot published examples for you to compare.

Alarm gas volume by pipe size (cm³) Range bars of alarm gas volume for DN25, DN50 and DN80 relays from Reinhausen and IS 3637, plus an EMB range, inside the IEC 60076-22-1 window of 100 to 400 cm³. Alarm gas volume by pipe size (cm³) 0 100 200 300 400 alarm gas volume (cm³) IEC 60076-22-1 window: 100–400 cm³ DN25 · Reinhausen CEDASPE EB 150 ± 50 DN25 · IS 3637 90–165 DN50 · Reinhausen CEDASPE EB 300 ± 100 DN50 · IS 3637 175–225 DN80 · Reinhausen CEDASPE EB 300 ± 100 DN80 · IS 3637 200–300 All sizes · EMB (by type) 200–300
Published alarm gas volumes. The shaded band is the 100–400 cm³ window in IEC 60076-22-1. Makers differ, so always use your own relay’s data sheet and check the current edition of IS 3637.
Oil-surge trip setting by manufacturer (m/s) Range bars of the oil velocity at which the flap trips: Reinhausen CEDASPE EB about 1 m/s, Messko MSAFE 1.0 to 2.5 m/s depending on pipe size, EMB 0.65 to 3.00 m/s depending on type. Oil-surge trip setting by manufacturer (m/s) 0 0.5 1 1.5 2 2.5 3 oil velocity (m/s) Reinhausen · CEDASPE EB (steady flow) 1.0 ± 0.15 Messko MSAFE · DN25 flap 1.0–2.5 Messko MSAFE · DN50 flap 1.0–2.0 Messko MSAFE · DN80 flap 1.0–2.5 EMB · By relay type 0.65–3.00
Published flap settings (Messko and EMB quote ±15% tolerance). Different relay designs and pipe sizes give very different values, so never mix figures between makers.

The alarm volumes look similar across makers, while the trip settings vary much more. Do not mix values between manufacturers, and use the data sheet for your own relay.

Frequently Asked Questions

What is a Buchholz relay?

A Buchholz relay is a gas- and oil-flow-operated protective device fitted in the pipe between the main tank and the conservator of an oil-filled transformer.

What is the main function of a Buchholz relay?

It warns of slow internal faults when gas builds up, and it trips the transformer on a violent oil surge or serious oil loss.

What is the working principle of a Buchholz relay?

Gas lowers the upper float and gives an alarm. A fast oil surge pushes the flap and trips. A falling oil level lowers the lower float and trips.

Where is a Buchholz relay installed?

In the pipe that joins the main transformer tank to the conservator.

Why is a Buchholz relay used in transformers?

It catches gas-producing internal faults early, before electrical protection may see a clear change in current.

What are the main components of a Buchholz relay?

A housing with an inspection window, a gas chamber, an upper float, a lower float, a flap, reed switches, a gas valve, a test button and a terminal box.

What is the difference between Buchholz relay alarm and trip?

An alarm is an early warning and the transformer stays in service. A trip opens the circuit breakers and isolates the transformer.

Which faults can a Buchholz relay detect?

Overheating, core insulation failure, inter-turn faults, internal arcing, internal bushing puncture, partial discharge that produces gas, oil leaks and air ingress.

Which faults cannot be detected by a Buchholz relay?

External short circuits, external bushing flashovers, and internal faults that produce neither enough gas nor any oil movement.

Why does a Buchholz relay operate during oil leakage?

As oil is lost, the level in the relay falls. The upper float drops first and gives an alarm, then the lower float drops and trips.

Can a Buchholz relay give a false alarm?

Yes. Air trapped after filling or maintenance is the most common harmless cause, but every alarm must be investigated.

How do you test a Buchholz relay?

Qualified staff use the test button, air injection where a test cock is fitted, and contact and wiring checks, all following the maker’s manual.

Why is gas collected inside a Buchholz relay?

Gas rises through the oil and collects in the relay chamber, where it operates the upper float and can be sampled for analysis.

Is a Buchholz relay used in dry-type transformers?

No. A dry-type transformer has no insulating oil, no conservator and no oil pipe.

Is a Buchholz relay used in an OLTC?

An on-load tap changer has its own protective relay, usually called an oil surge relay, which is separate from the main-tank Buchholz relay.

What is the difference between a Buchholz relay and a sudden pressure relay?

A Buchholz relay senses gas and oil flow in the conservator pipe. A sudden pressure relay senses a rapid rise in pressure inside the tank.

Who invented the Buchholz relay?

Max Buchholz, a German engineer working in Kassel, whose patent was filed in 1921.

What is the purpose of the upper and lower floats?

The upper float gives the early alarm. The lower float gives a separate trip if oil loss continues.

Why is a Buchholz relay installed between the transformer tank and conservator?

It is the one place that all rising gas and all surging oil must pass through.

What is the role of gas analysis in Buchholz relay protection?

A laboratory analysis shows whether collected gas is air or fault gas and helps identify the type of fault. Colour alone cannot do this.

Conclusion

A Buchholz relay gives a conservator-type transformer an early mechanical warning of internal faults and a fast trip for severe ones. Gas lowers the upper float for the alarm, an oil surge moves the flap for the trip, and a falling oil level lowers the lower float. Its value depends on correct installation, settings matched to the relay model and pipe size, regular testing and proper gas analysis. Treat every alarm as a reason to investigate, and use the relay together with differential and other electrical protection, never in place of them.

Sources: Reinhausen CEDASPE EB catalogue and operating instructions, and Messko MSAFE technical data; EMB Buchholz relay catalogue; Hitachi Energy Buchholz relay page; IEC 60076-22-1:2019 preview; IEEE PES Relay Committee report on sudden pressure protection; PACW engineering history; Wikipedia, Buchholz relay.

About the author

editor

Leave a Comment