An e-stop (emergency stop) is a red mushroom-head pushbutton on a yellow background that latches when pressed and stops the machine as quickly as possible without creating new hazards. It must override every other function and use a Category 0 stop (immediate power removal) or a Category 1 stop (controlled stop, then power removed). Releasing it must never restart the machine: a separate reset and start are required. It is a backup measure that never replaces guarding, and in the US the electrical requirements come from NFPA 79.
What an Emergency Stop Is (and Isn’t)
ISO 12100 and ISO 13850 call the emergency stop function a complementary protective measure. A person starts it with a single action, to avert or reduce an existing or impending hazard to people, machinery or work in progress. It does not keep people away from hazards, so it never replaces guards, interlocks or inherently safe design (Control Design; Machinery Safety 101). Doug Nix notes that confusion starts when designers treat the e-stop as a primary safety function rather than the last line of defense.
Not every machine needs one. CSA Z432 requires an e-stop where a risk assessment shows it helps, and at each operator station that can start motion, unless the assessment shows it will not reduce risk. Product standards for robots require one. The EU Machinery Directive likewise exempts machines where an e-stop would not reduce stopping time or risk, and hand-held machinery.
E-Stop Device Requirements
- Physical device: not a graphic on an HMI, flush button, membrane or touchscreen switch.
- Direct opening operation: contacts are forced open mechanically by the actuator.
- Self-latching: it stays in the stop position until deliberately reset by twisting, pulling or a key.
- Colors: red actuator on a yellow background. Control Design cites ANSI B65.1-2005 for a yellow background extending at least 3 mm beyond the mounting collar.
- Shape: a mushroom (palm) head that is easy to strike.
- Location: at each operator control station and anywhere else the risk assessment calls for one, clearly visible and readily accessible.
- Other actuators: pull-cord (rope-pull) switches along conveyors and foot-operated devices are also used where suitable.
Machinery Safety 101 shows non-compliant buttons, including ones with a red background or a spring-return head. The IEC 60417-5638 symbol may also be used to identify an emergency stop.
Stop Categories 0, 1 and 2
| Category | How the machine stops | Allowed for e-stop? | Drive safety function |
|---|---|---|---|
| 0 | Uncontrolled: power to actuators removed immediately | Yes | STO (Safe Torque Off) |
| 1 | Controlled stop with power available, then power removed | Yes | SS1 (Safe Stop 1) |
| 2 | Controlled stop with power left available | No | SS2 / Safe Operating Stop |
NFPA 79 requires Category 0, 1 and/or 2 stops as the risk assessment and machine function dictate. Category 0 and 1 stops must work in every operating mode, and Category 0 takes priority. Stop functions override related start functions, and resetting a stop must not create a hazard. For the emergency stop itself, ISO 13850 and IEC 60204-1 allow only Category 0 or 1. Category 2 leaves power available and needs no extra step to restart.
G.T. Engineering gives the selection rule. Choose Category 0 for moving parts with no inertia, where stopping causes no added risk. Choose Category 1 where hazardous parts have inertia or other systems need power to stop safely, such as a drive braking a heavy spindle or a holding brake that needs power.
E-Stop Stop Category Helper
Reset and Restart
ISO 13850 requires that disengaging the e-stop device must not restart the machinery, only permit restarting. Doug Nix breaks restart into three steps. First, mechanically release the e-stop device. Second, reset the safety function, with a separate blue pushbutton if manual reset is required, positioned so the operator can see the whole hazard area. Third, start the machine with the normal start control. The manual reset cannot be an HMI graphic. If resetting the e-stop would itself start hazardous motion, the design must change.
E-Stop Circuits and Safety Relays
Control Design describes a typical Category 0 circuit from Omron. The e-stop S1 and reset S2 connect to a safety (status-monitoring) relay that drives two contactors, KM1 and KM2, in series with the motor. The relay also monitors the contactors through a feedback loop. Pressing S1 opens both contactors. Power stays off until S1 is released and S2 is pressed, and the feedback lets the relay detect a contactor that fails to drop out.
On servo and VFD systems, the drive’s Safe Torque Off input can replace the contactors for a Category 0 stop. SS1 gives a monitored Category 1 ramp-down before STO. STO removes torque-producing current without cutting the drive’s supply, so restart is quicker (Mitsubishi Electric, in Control Design). Reliability must meet at least ISO 13849-1 PL c or IEC 62061 SIL 1, or higher if the risk assessment calls for it.
For energy isolation during maintenance, which an e-stop does not provide, see lockout/tagout procedure. For guarding with presence-sensing devices, see light curtain safety relays. For servo stop functions, see closed loop servo systems.
Frequently Asked Questions
What is an e-stop?
An emergency stop is a function, normally triggered by a red mushroom-head button, that a person uses with a single action to avert or reduce an actual or impending hazard. It is a complementary protective measure, not a safeguard (ISO 12100; ISO 13850).
Is an e-stop required on every machine?
Not always. US and Canadian standards require one where a risk assessment shows it reduces risk, and each operator station that can start motion normally needs one. Some product standards, such as robot standards, always require it. The EU Machinery Directive exempts machines where it would not reduce the risk, and hand-held machines (Machinery Safety 101).
What color is an e-stop button?
Red, on a yellow background. Control Design cites ANSI B65.1-2005 for a yellow background at least 3 mm beyond the mounting collar. A red background or a spring-return button is not compliant.
Can an e-stop be a button on an HMI touchscreen?
No. Touchscreen icons, flush and membrane switches do not meet the standards. The e-stop must be a physical, self-latching device with direct opening contacts (Control Design).
What are stop categories 0, 1 and 2?
Category 0 removes power immediately (uncontrolled stop). Category 1 keeps power to stop the machine under control, then removes it. Category 2 is a controlled stop that leaves power on. An e-stop must be Category 0 or 1.
Why can’t an e-stop be Category 2?
Because power stays available after the stop and nothing extra is needed to restart, which defeats the purpose of an emergency stop (Control Design, citing IEC 60204-1).
What happens when you release an e-stop?
Nothing should start. Releasing the button only permits restarting: a separate reset, typically a blue pushbutton, restores the safety function, and then a normal start command restarts the machine.
What performance level does an e-stop need?
At least PL c to ISO 13849-1 or SIL 1 to IEC 62061, or higher if the risk assessment requires it (Machinery Safety 101).
What is the difference between an e-stop and STO?
The e-stop is the function and its device; Safe Torque Off is a drive safety function that removes torque-producing current and corresponds to a Category 0 stop. SS1 decelerates and then applies STO, a Category 1 stop.
Can an e-stop be used as a normal off switch?
It should not be. The e-stop is a complementary measure for emergencies; routine stops belong to the machine’s normal stop control.
Sources and Further Reading
- Machinery Safety 101 (Doug Nix): Emergency Stop Requirements: quotes CSA Z432, ISO 13850, NFPA 79 and the EU Machinery Directive.
- Control Design: Standards and options for e-stops: device requirements, stop categories, Omron circuit, Mitsubishi STO/SS1.
- G.T. Engineering: Stop functions: IEC 60204-1 categories, ISO 13850 selection, IEC 61800-5-2 STO/SS1/SS2.