Leading vs Lagging Power Factor: Causes, Effects and Fixes

By editor 5 min read
Phasor diagram with voltage, leading current and lagging current beside capacitor and inductor symbols

A lagging power factor means current peaks after voltage, while a leading power factor means current peaks before voltage. Inductive loads such as motors and transformers cause lagging current. Capacitive loads, or too much power factor correction, cause leading current. Most plants correct a lagging power factor with capacitors, aiming for about 0.95 to 0.98 lagging to avoid overcorrection.

FactorLagging power factorLeading power factor
Current vs voltageCurrent behind voltageCurrent ahead of voltage
Load typeInductiveCapacitive
Common causesMotors, transformers, ballastsCapacitor banks, overcorrection
Main riskHigher current and utility chargesVoltage rise and resonance
Typical fixAdd capacitorsRemove or switch out capacitors
Leading vs lagging power factor at a glance.
Safety first: Capacitors can hold a lethal charge after disconnection. Do not work on a capacitor bank until it has been isolated, discharged and proven dead, following your lockout/tagout procedure.
0.95–0.98
Common practical target
42.13
kVAR, 100 kW 0.80 to 0.95
80%
NEPSI motor capacitor size
90%
Maximum of no-load current

Power Factor Correction Calculator

Power Factor Correction Calculator
IndustrialBasics estimate. This does not check harmonics, resonance or motor self-excitation limits.

What Leading and Lagging Mean

Lagging and leading current phasorsWith a lagging power factor, the current phasor is behind the voltage. With a leading power factor, the current phasor is ahead of the voltage.Current position relative to voltageLagging power factorVI lags VInductive loadLeading power factorVI leads VCapacitive loadIndustrialBasicsindustrialbasics.com
Figure 1: Phasors rotate counterclockwise, so a current drawn behind voltage is lagging.

Power factor compares real power (kW) with apparent power (kVA). In an AC circuit, the current can shift in time relative to the voltage. The direction of that shift is what the terms describe.

  • Lagging: an inductor resists changes in current, so current arrives after the voltage.
  • Leading: a capacitor charges first, so current arrives before the voltage.
  • Unity: current and voltage are in step, as in a purely resistive load.

The numeric value alone does not show the direction, so always state it, for example 0.90 lagging. For the underlying kW, kVA and kVAR relationships, see our guide to electrical 3 phase calculations.

Causes and Effects

ConditionTypical causesEffects
LaggingInduction motors, transformers, inductive lightingHigher current and losses, reduced capacity, possible utility charges
LeadingOversized capacitors, capacitors left on at light loadVoltage rise, nuisance switching, resonance and generator problems
Causes and effects of each condition.

Utilities commonly apply a charge when power factor falls below a threshold, often around 0.90 to 0.95, but this varies by tariff, so check your own bill. Harmonics can also interact with capacitors, so review our guide to power quality problems before adding a bank.

Reader tip: Size and control capacitors for the whole load range. A bank that looks right at full load can overcorrect at night or during a shutdown.

How to Correct a Lagging Power Factor

kVAR = kW × (tan θ1 − tan θ2)

Here θ1 is the angle of the existing power factor and θ2 is the angle of the target.

Power factor correction triangleFor a 100 kilowatt load, reactive power falls from 75 to 32.87 kilovars when 42.13 kilovars of capacitors raise the power factor from 0.80 to 0.95.Capacitors reduce lagging kVAR100 kWCapacitors: 42.13 kVARAfter: 32.87 kVARBefore: 75.00 kVARIndustrialBasicsindustrialbasics.com
Figure 2: Real power stays at 100 kW while reactive power from the supply falls.
StepCalculationResult
Existing kVAR100 × tan(cos⁻¹ 0.80)75.00 kVAR
Target kVAR100 × tan(cos⁻¹ 0.95)32.87 kVAR
Capacitor needed75.00 − 32.8742.13 kVAR
Apparent power125 kVA to 105.3 kVA15.8% less current
Worked example for a 100 kW load at constant voltage.

The Danger of Overcorrection

Too much capacitance can push a system into a leading power factor and raise the voltage. Schneider’s installation guide notes that AC generators are not normally operated at leading power factors, partly because of a tendency to self-excite.

Motor self-excitation

When a motor with capacitors at its terminals is switched off, it keeps turning. The capacitors can feed current back into the stator, and the terminal voltage can rise to dangerously high levels. To avoid this, limit the capacitor size:

Qc ≤ 0.9 × Io × Un × √3

Here Io is the no-load current and Un is the line voltage in kV. For an example 400 V motor with a 30 A no-load current, the limit is 0.9 × 30 × 0.4 × 1.732 = 18.7 kvar. NEPSI recommends sizing at 80% of no-load current, which is about 16.6 kvar here, and never above 90%. Ask the motor manufacturer first.

Schneider also advises that high-inertia motor circuits should be tripped rapidly on total loss of supply. If a motor keeps tripping or overheating, also check its full load amps and review common motor failure causes.

Safety note: This guide is educational. Have a qualified engineer assess harmonics, switching and protection before installing power factor correction.

Frequently Asked Questions

What is the difference between leading and lagging power factor?

With a lagging power factor, current reaches its peak after voltage. With a leading power factor, current reaches its peak before voltage. Inductive loads cause lagging current and capacitive loads cause leading current.

Is leading or lagging power factor better?

Neither is automatically better. The goal is usually a power factor close to unity while staying slightly lagging, because a leading system can cause voltage rise and other problems.

What causes a lagging power factor?

Inductive loads such as induction motors, transformers and some lighting ballasts draw magnetizing current that lags the voltage.

What causes a leading power factor?

Capacitive loads or too much power factor correction, particularly when capacitors stay connected at light load.

How do you correct a lagging power factor?

Add capacitors sized with kVAR = kW × (tan θ1 − tan θ2). For 100 kW from 0.80 to 0.95, that is about 42.13 kVAR.

Why not correct the power factor to exactly 1.0?

Practical targets are often 0.95 to 0.98. Aiming for 1.0 raises the risk of overcorrection when the load changes.

What is motor self-excitation?

If capacitors stay connected when a motor is switched off, the spinning motor can act as a generator and create dangerously high voltage.

How large can a capacitor on a motor be?

Schneider limits it to 0.9 × no-load current × kV × √3. NEPSI recommends 80% of no-load current and never more than 90%. Ask the motor manufacturer first.