A lagging power factor means current peaks after voltage, while a leading power factor means current peaks before voltage. Inductive loads such as motors and transformers cause lagging current. Capacitive loads, or too much power factor correction, cause leading current. Most plants correct a lagging power factor with capacitors, aiming for about 0.95 to 0.98 lagging to avoid overcorrection.
| Factor | Lagging power factor | Leading power factor |
|---|---|---|
| Current vs voltage | Current behind voltage | Current ahead of voltage |
| Load type | Inductive | Capacitive |
| Common causes | Motors, transformers, ballasts | Capacitor banks, overcorrection |
| Main risk | Higher current and utility charges | Voltage rise and resonance |
| Typical fix | Add capacitors | Remove or switch out capacitors |
Power Factor Correction Calculator
What Leading and Lagging Mean
Power factor compares real power (kW) with apparent power (kVA). In an AC circuit, the current can shift in time relative to the voltage. The direction of that shift is what the terms describe.
- Lagging: an inductor resists changes in current, so current arrives after the voltage.
- Leading: a capacitor charges first, so current arrives before the voltage.
- Unity: current and voltage are in step, as in a purely resistive load.
The numeric value alone does not show the direction, so always state it, for example 0.90 lagging. For the underlying kW, kVA and kVAR relationships, see our guide to electrical 3 phase calculations.
Causes and Effects
| Condition | Typical causes | Effects |
|---|---|---|
| Lagging | Induction motors, transformers, inductive lighting | Higher current and losses, reduced capacity, possible utility charges |
| Leading | Oversized capacitors, capacitors left on at light load | Voltage rise, nuisance switching, resonance and generator problems |
Utilities commonly apply a charge when power factor falls below a threshold, often around 0.90 to 0.95, but this varies by tariff, so check your own bill. Harmonics can also interact with capacitors, so review our guide to power quality problems before adding a bank.
How to Correct a Lagging Power Factor
Here θ1 is the angle of the existing power factor and θ2 is the angle of the target.
| Step | Calculation | Result |
|---|---|---|
| Existing kVAR | 100 × tan(cos⁻¹ 0.80) | 75.00 kVAR |
| Target kVAR | 100 × tan(cos⁻¹ 0.95) | 32.87 kVAR |
| Capacitor needed | 75.00 − 32.87 | 42.13 kVAR |
| Apparent power | 125 kVA to 105.3 kVA | 15.8% less current |
The Danger of Overcorrection
Too much capacitance can push a system into a leading power factor and raise the voltage. Schneider’s installation guide notes that AC generators are not normally operated at leading power factors, partly because of a tendency to self-excite.
Motor self-excitation
When a motor with capacitors at its terminals is switched off, it keeps turning. The capacitors can feed current back into the stator, and the terminal voltage can rise to dangerously high levels. To avoid this, limit the capacitor size:
Here Io is the no-load current and Un is the line voltage in kV. For an example 400 V motor with a 30 A no-load current, the limit is 0.9 × 30 × 0.4 × 1.732 = 18.7 kvar. NEPSI recommends sizing at 80% of no-load current, which is about 16.6 kvar here, and never above 90%. Ask the motor manufacturer first.
Schneider also advises that high-inertia motor circuits should be tripped rapidly on total loss of supply. If a motor keeps tripping or overheating, also check its full load amps and review common motor failure causes.
Frequently Asked Questions
What is the difference between leading and lagging power factor?
With a lagging power factor, current reaches its peak after voltage. With a leading power factor, current reaches its peak before voltage. Inductive loads cause lagging current and capacitive loads cause leading current.
Is leading or lagging power factor better?
Neither is automatically better. The goal is usually a power factor close to unity while staying slightly lagging, because a leading system can cause voltage rise and other problems.
What causes a lagging power factor?
Inductive loads such as induction motors, transformers and some lighting ballasts draw magnetizing current that lags the voltage.
What causes a leading power factor?
Capacitive loads or too much power factor correction, particularly when capacitors stay connected at light load.
How do you correct a lagging power factor?
Add capacitors sized with kVAR = kW × (tan θ1 − tan θ2). For 100 kW from 0.80 to 0.95, that is about 42.13 kVAR.
Why not correct the power factor to exactly 1.0?
Practical targets are often 0.95 to 0.98. Aiming for 1.0 raises the risk of overcorrection when the load changes.
What is motor self-excitation?
If capacitors stay connected when a motor is switched off, the spinning motor can act as a generator and create dangerously high voltage.
How large can a capacitor on a motor be?
Schneider limits it to 0.9 × no-load current × kV × √3. NEPSI recommends 80% of no-load current and never more than 90%. Ask the motor manufacturer first.
Sources and Further Reading
- Schneider Electric: Electrical Installation Guide, Chapter L: correction and self-excitation limit.
- NEPSI: Self-Excitation Concerns with Power Factor Correction: motor capacitor sizing.
- Instrumentation Blog: Power Factor Correction Explained: lagging loads, overcorrection and targets.
- CalcPanel: kW to kVAR Calculator: formula and 100 kW example.
- Voltage Disturbance: Overcompensation for Induction Motors: overcompensation effects.