Corner Grounded Delta: Voltages, Breakers and NEC Rules

By editor 8 min read
Delta triangle with corners A and C at 480 volts and corner B connected to earth at zero volts

A corner grounded delta is a three-phase, three-wire system in which one corner of a delta transformer secondary is solidly grounded. On a 480 V system, the grounded phase (usually B) reads 0 V to ground, while the other two phases read the full 480 V to ground. Schneider Electric says these systems are not recommended for new installations, but many older services remain in use and they need correctly rated equipment.

Measurement240 V system480 V system600 V system
Phase to phase (all pairs)240 V480 V600 V
Ungrounded phase to ground (A, C)240 V480 V600 V
Grounded phase to ground (B)0 V0 V0 V
Nominal voltages on a corner grounded delta. Schneider Electric notes that the ungrounded phases are generally A and C.
Safety first: Voltage to ground is the full system voltage on two phases. Only qualified people should take live measurements, using suitable test equipment and PPE. Follow your lockout/tagout procedure before working on the equipment.
480 V
A and C to ground
0 V
B to ground
3-wire
No neutral
1Ø–3Ø
Required 2-pole marking

How a Corner Grounded Delta Works

In a delta connection, the three windings form a closed loop with no neutral point. To create a grounded system from a delta, one corner is solidly connected to ground. That conductor is still a phase conductor, but it is now also the system’s grounded conductor.

Corner grounded delta connection and voltagesA delta with corner B solidly grounded. All phase-to-phase voltages are 480 volts, A and C measure 480 volts to ground, and B measures zero.Corner grounded delta at 480 VACB480 V480 V480 VMeter readingsA to B480 VB to C480 VC to A480 VA to ground480 VC to ground480 VB to ground0 VIndustrialBasicsindustrialbasics.com
Figure 1: Grounding one corner puts the two remaining phases at full line voltage to ground.

The system is also known as a grounded B phase, grounded phase service or end-grounded delta. For the wider picture, see our guide to types of earthing systems.

Why it was used

Older low-voltage systems were commonly supplied from delta-connected transformers, which offered no neutral to ground. Grounding one phase was a low-cost way to obtain a grounded system. As delta-wye transformers became common, the arrangement became rare. Our delta-wye transformer guide explains the connection that largely replaced it.

How to Identify One With a Meter

A qualified person can identify the system from six readings: the three phase-to-phase voltages and the three phase-to-ground voltages.

System at 480 VA to groundB to groundC to ground
Solidly grounded wye277 V277 V277 V
Corner grounded delta480 V0 V480 V
Expected nominal readings. Confirm the grounded phase at the source and on the drawings.
Wye and corner grounded delta comparedA 480Y/277 volt wye has 277 volts from phase to ground, while a 480 volt corner grounded delta has 480 volts from A and C to ground.Same 480 V system, different voltage to ground480Y/277 V solidly grounded wye480 V corner grounded deltaPhase to ground: 277 VA: 480 VC: 480 VA and C to ground: 480 VIndustrialBasicsindustrialbasics.com
Figure 2: This difference is why slash-rated 480Y/277 V breakers cannot be used on a 480 V corner grounded delta.
Reader tip: Do not assume the grounded phase is white or marked correctly in an older installation. The system requires positive identification of the grounded phase throughout, so verify it before connecting equipment.

Advantages and Disadvantages

AdvantagesDisadvantages
Stabilizes the ungrounded phases to groundCannot supply dual-voltage lighting and power loads
Reduces transient overvoltagesGrounded phase must be positively identified throughout
Allows ground faults to be detected and clearedHigher line-to-ground voltage on two phases
Could be created from an existing delta bankMost distribution equipment is not rated for it
Low-cost grounded system when it was installedFault clearing is more severe, and ratings may be greatly reduced
Based on Schneider Electric Data Bulletin 2700DB0202R03/12.

A first ground fault can draw high current and must be cleared immediately. Schneider Electric recommends providing some type of equipment ground fault protection on equipment used with these systems.

Breaker Ratings: Straight vs Slash

This is where corner grounded systems most often go wrong. NEC 240.85, as quoted by Schneider Electric, sets two tests:

  • Straight rating (such as 480 V): the voltage between any two conductors must not exceed the rating.
  • Slash rating (such as 480Y/277 V): voltage to ground must not exceed the lower value, and voltage between conductors must not exceed the higher value.
SystemBreaker ratingTestVoltage rule met?
480 V corner grounded480 V straight480 V ≤ 480 VYes
480 V corner grounded600 V straight480 V ≤ 600 VYes
480 V corner grounded480Y/277 V slash480 V to ground > 277 VNo
480 V corner grounded600Y/347 V slash480 V to ground > 347 VNo
240 V corner grounded120/240 V slash240 V to ground > 120 VNo
240 V corner grounded480Y/277 V slash240 V ≤ 277 V and 240 V ≤ 480 VYes
Voltage rule only. Equipment must also have a suitable interrupting rating for this system.
Important: Passing the voltage test is not enough. On a corner grounded system, one pole can be required to clear a fault at full line voltage. The NEC informational note says proper application considers the breaker’s individual pole-interrupting capability, and ratings may be greatly reduced. Confirm the rating with the manufacturer.

A 2-pole breaker must not protect a three-phase corner grounded circuit unless it is marked 1Ø–3Ø. NEMA and UL standards carry the same marking requirement. For background on device types, see types of circuit breakers and MCB vs MCCB vs ACB.

Fuses and the Grounded B Phase

NEC 240.22 generally prohibits an overcurrent device in series with an intentionally grounded conductor. The device is allowed only if it opens all circuit conductors with no pole operating independently, or where 430.36 or 430.37 requires it for motor overload protection.

Fuse placement on a corner grounded deltaA service or distribution switch uses a solid copper link in grounded phase B. Where fuses provide motor overload protection, a motor controller has a fuse in all three phases.Where a fuse can go in the grounded B phaseService or distribution switchMotor controller, fused overloadAFBCFAFBFCFSolid copper link in B, no fuseFuse in every phase, including BIndustrialBasicsindustrialbasics.com
Figure 3: The B phase fuse is allowed only at the motor controller, where fuses are the motor overload protection.
LocationGrounded B phaseReason
Service or distribution fused switchSolid copper link, no fuseA blown fuse must not open the grounded conductor alone
Circuit breaker opening all poles togetherMay include the grounded conductorAll conductors open simultaneously
Motor controller with fused overload protectionFuse requiredNEC 430.36 requires it on a 3-wire, 3-phase system with one conductor grounded
Rules as quoted in the Schneider Electric bulletin (2012). Check the NEC edition adopted locally.

For motor circuits, overload protection is covered in our guide to the thermal overload relay.

Drives and Other Equipment

Always check that equipment is rated for a corner grounded supply. Electronic equipment needs special care because internal components may be connected from phase to ground. Voltage Disturbance notes that VFD EMC filters are often rated for phase-to-ground voltage and can misoperate or be damaged on a corner grounded system unless they are reconfigured as the drive maker instructs. See our VFD vs soft starter guide for more on drives.

The grounded phase also connects to the electrode system through a grounding electrode conductor, sized using NEC Table 250.66.

Checklist Before Connecting Equipment

  • Confirm the system with six voltage readings.
  • Identify the grounded phase at the source and at the equipment.
  • Check that the equipment is rated for corner grounded delta use.
  • Do not use slash-rated devices unless both voltage tests pass.
  • Check individual pole-interrupting capability.
  • Use only 1Ø–3Ø marked breakers for 2-pole three-phase protection.
  • Keep fuses out of the grounded phase, except at a motor controller using fused overload protection.
  • Check drive and filter configuration in the manufacturer’s manual.
Safety note: This guide is educational and does not replace the NEC, manufacturer instructions or your local authority. Some rule text here comes from a 2012 bulletin, so confirm it against the edition adopted where you work.

Frequently Asked Questions

What is a corner grounded delta system?

It is a three-phase, three-wire system with a delta-connected transformer secondary and one corner solidly grounded. It is also called a grounded B phase or end-grounded delta system.

What is the voltage to ground on a 480 V corner grounded delta?

The two ungrounded phases, generally A and C, measure 480 V to ground. The grounded phase, generally B, measures 0 V to ground.

How do I identify a corner grounded delta with a meter?

A qualified person measures each phase to phase and each phase to ground. If two phases read full line voltage to ground and the third reads zero, the system is corner grounded.

Can I use a 480Y/277 V breaker on a corner grounded delta?

Not on a 480 V corner grounded delta. The voltage to ground is 480 V, which exceeds the breaker’s lower 277 V rating. Use suitably rated equipment with a straight voltage rating.

Can a fuse be installed in the grounded B phase?

Not on service or distribution disconnects. The exception is motor overload protection using fuses, where a fuse is required in the grounded conductor at the motor controller.

What does 1Ø–3Ø mean on a 2-pole breaker?

It shows the breaker is suitable for protecting a three-phase corner grounded delta circuit. A 2-pole breaker without that marking must not be used for this purpose.

They cannot provide dual-voltage service, need positive identification of the grounded phase, have higher voltage to ground, and place more severe duty on clearing devices. Much equipment is not rated for them.

Can a VFD run on a corner grounded delta?

Sometimes, but check the drive manual first. EMC filters are often rated for phase-to-ground voltage, so the drive may need its filter configuration changed for this system.

Sources and Further Reading

About the author

editor

Leave a Comment