Electrical Panel Clearance: NEC 110.26 Requirements Guide

By editor Updated 8 min read
Electrical panel on a wall with a highlighted working space measuring 30 inches wide, 3 feet deep and 6.5 feet high

Electrical panel clearance under NEC 110.26 is a clear working space at least 3 feet deep, 30 inches wide (or the width of the equipment, if greater) and 6.5 feet high. At 151 to 600 volts to ground, the depth rises to 3.5 or 4 feet depending on what faces the panel. The door must also be able to open at least 90 degrees, and the space cannot be used for storage.

Nominal voltage to groundCondition 1Condition 2Condition 3
0 to 150 V3 ft3 ft3 ft
151 to 600 V3 ft3.5 ft4 ft
601 to 1,000 V3 ft4 ft5 ft
Minimum working space depth, based on NEC Table 110.26(A)(1) as reproduced in the SLAC safety manual and IAEI guidance.
Check locally: Your local authority enforces the edition of the NEC it has adopted, plus any amendments. Confirm the requirement with that authority before you design or change an installation.
3 ft
Minimum working depth
30 in.
Minimum width
6.5 ft
Minimum height
90°
Minimum door opening

What NEC 110.26 Requires

NEC 110.26 exists so a person can examine, adjust, service or maintain equipment while it may be energized, and get away quickly if something goes wrong. The rule applies to equipment likely to need that work, including panelboards, switches, circuit breakers, switchgear, controllers and HVAC controls.

Working space width, height and depthFront and side views of a panel with a clear working zone at least 30 inches wide, 6.5 feet high and as deep as the code table requires.The three dimensions of the working spacePanelFront view30 in. or equipment width6.5 ftSide viewKeep clearDepth from Table 110.26(A)(1)IndustrialBasicsindustrialbasics.com
Figure 1: The clear zone in front of a panel. Taller or wider equipment increases the height or width.
DimensionMinimumKey detail
Depth3 to 4 ft up to 600 VSet by voltage to ground and condition
Width30 in. or equipment widthUse the greater value; may be offset from the panel
Height6.5 ft or equipment heightUse the greater value
Door swing90°Doors and hinged panels must be able to open at least 90°
FloorClear and levelKeep the floor in the working space clear and level
The core working space dimensions.

Depth is measured from exposed live parts, or from the front of the enclosure when the live parts are enclosed. Associated equipment above or below the panel, such as a wireway, may extend up to 6 inches past the front of the panel within the working height.

How to Choose Condition 1, 2 or 3

The condition describes what is on the opposite side of the working space. Getting it wrong is an easy way to end up with too little depth.

The three NEC working space conditionsPlan views showing 3 feet for Condition 1, 3.5 feet for Condition 2 and 4 feet for Condition 3 at 480Y/277 volts.Depth at 480Y/277 V by conditionCondition 1Exposed live partsNo live or grounded parts3 ftNothing conductive oppositeCondition 2Exposed live partsGrounded parts or concrete3.5 ftConcrete, brick, tile countCondition 3Exposed live partsExposed live parts4 ftLive parts on both sidesIndustrialBasicsindustrialbasics.com
Figure 2: What faces the equipment decides the condition, and the condition decides the depth.
ConditionWhat faces the equipmentTypical example
Condition 1No live or grounded parts, or live parts effectively guarded by insulationPanel facing an insulated, non-conductive surface
Condition 2Grounded parts. Concrete, brick and tile count as groundedPanel facing a concrete block wall
Condition 3Exposed live parts on both sidesTwo panels facing each other across an aisle
The three conditions from NEC 110.26(A)(1).
Reader tip: When two working spaces overlap, check whether equipment on both sides could be open at once. Overlapping spaces may need Condition 3 depth.

Worked Examples

InstallationVoltage rowConditionMinimum depth
208Y/120 V panel facing drywall0 to 150 VAny3 ft
480Y/277 V panel facing a concrete wall151 to 600 V23.5 ft
Two 480Y/277 V panels facing each other151 to 600 V34 ft
Use voltage to ground, not line-to-line voltage.

The second example catches people out. The system is called 480 V, but its voltage to ground is 277 V, which still falls in the 151 to 600 V row. The concrete wall makes it Condition 2, so a 36 inch aisle is 6 inches too shallow. For a 24 inch wide panel in the same room, the width is still 30 inches because that is the greater value.

Keep the Working Space Clear

The required working space must not be used for storage. That includes temporary items such as boxes, ladders, carts and cleaning supplies. If normally enclosed live parts are exposed in a passageway or general open area, the working space must be suitably guarded while they are open.

  • Mark the floor so the clear zone is obvious.
  • Include panel access in housekeeping checks.
  • Keep doors, racks and new equipment from moving into the zone.
  • Recheck clearance after any room layout change.

Blocked access also slows emergency isolation. Good clearance supports the safe work practices in our guides to arc flash, lockout/tagout and electrical safety PPE.

Entrance and Egress for Large Equipment

Every working space needs at least one entrance of sufficient area. Larger equipment adds stricter rules because a worker may need to get out quickly from either end of the lineup.

Entrances for large electrical equipmentPlan view of a long equipment lineup with an exit at each end of the working space and a personnel door opening outward.Large equipment needs a way out at each end1,200 A equipment, more than 6 ft wideRequired working spaceExit 1Exit 2Door opens outward, listed hardwareEach entrance: at least 24 in. wide and 6.5 ft highIndustrialBasicsindustrialbasics.com
Figure 3: One entrance can be enough with continuous exit travel or a doubled working space depth.
TriggerRequirement
Equipment rated 1,200 A or more and over 6 ft wideAn entrance at least 24 in. wide and 6.5 ft high at each end of the working space
Continuous, unobstructed exit pathOne entrance may be permitted
Working space depth doubledOne entrance may be permitted, with its nearest edge at least the required depth from the equipment
Equipment rated 800 A or more, personnel door less than 25 ft from the working spaceDoor opens in the direction of egress with listed panic or fire exit hardware
Entrance and door rules from the 2020 NEC, as explained by EC&M. Check the edition adopted locally.

Recent code text also addresses equipment doors, which must not impede entry to or exit from the working space. Check this on long lineups, where an open door can block the only path out. Equipment such as switchgear panels and switchgear assemblies often needs this review.

Dedicated Equipment Space

Working space is for people. Dedicated equipment space protects the electrical installation itself. Indoors, the space equal to the width and depth of the equipment, from the floor to 6 feet above the equipment or to the structural ceiling, whichever is lower, is reserved for electrical use.

ItemRule
Equipment coveredService equipment, switchboards, switchgear, panelboards and motor control centers
Foreign systemsPipes, ducts and unrelated equipment stay out of the dedicated zone
Above the zoneForeign systems need protection against condensation, leaks and breaks
Suspended ceilingA dropped or suspended ceiling is not a structural ceiling
OutdoorsUse suitable enclosures and protect from unauthorized people, vehicles and piping leaks
Dedicated space basics. Local amendments can be stricter.

Local rules can go further. Baltimore’s adopted code, for example, extends the indoor dedicated space to the structural ceiling and adds the required working space to it.

Lighting and OSHA Requirements

Indoor working spaces around service equipment, switchboards, panelboards and motor control centers need illumination. OSHA 29 CFR 1910.303(g) accepts an adjacent light source, but lighting in electric equipment rooms cannot be controlled by automatic means only.

OSHA also sets workplace requirements for equipment at 600 V or less. It requires a 30 inch minimum width, a 90 degree door opening and no storage in the working space. Headroom is 6.5 feet for installations built on or after August 13, 2007, and 6.25 feet for older ones.

Safety note: Do not open a panel to measure or inspect it unless you are qualified to do so. Treat exposed parts as live until they have been isolated, locked out and proven dead. This guide is educational and does not replace the NEC, OSHA rules, manufacturer instructions or your local authority.

To check whether the lighting over a working space is enough, convert fixture output with lux to lumens.

Frequently Asked Questions

How much clearance is required in front of an electrical panel?

At least 3 feet deep, 30 inches wide and 6.5 feet high for typical panels up to 150 volts to ground. At 151 to 600 volts to ground, the depth is 3, 3.5 or 4 feet depending on the condition.

What is the 36 inch rule for electrical panels?

It is the common name for the 3 foot minimum working depth in NEC Table 110.26(A)(1). It is only the minimum, and 480 V equipment facing a concrete wall needs 3.5 feet.

Does the panel have to be centered in the 30 inch width?

No. The working space can be centered on the equipment or offset, as long as it is at least 30 inches wide or the width of the equipment, whichever is greater, and the door can open at least 90 degrees.

Can I store things in front of an electrical panel?

No. The required working space cannot be used for storage, even temporarily. Boxes, shelves, carts and equipment all block safe access.

Does a concrete wall change the required clearance?

Yes. Concrete, brick and tile walls are treated as grounded. At 151 to 600 volts to ground, that makes the installation Condition 2 and raises the depth from 3 feet to 3.5 feet.

What voltage do I use for Table 110.26(A)(1)?

Use the nominal voltage to ground. A 208Y/120 V panel uses the 0 to 150 V row, while a 480Y/277 V panel uses the 151 to 600 V row.

When does an electrical room need panic hardware?

Under the 2020 NEC text, when equipment rated 800 A or more has overcurrent, switching or control devices and a personnel door is less than 25 feet from the working space. The door must open in the direction of egress and have listed panic or fire exit hardware.

Is the dedicated space the same as the working space?

No. Working space is the clear area in front of the equipment for people. Dedicated space is the footprint of the equipment, extending above it, and is reserved for the electrical installation.