To convert Hz to RPM, use RPM = Hz × 120 ÷ number of poles. A 4-pole motor at 45 Hz has a synchronous speed of 1350 RPM. That is the speed of the rotating field, so a loaded induction motor turns slightly slower. Many drives can show RPM or machine speed once the motor poles and display scale are set.
Hz to RPM Calculator
Enter the drive frequency and motor poles. To scale a machine display, enter the machine speed at a known reference frequency.
Hz and RPM Chart
| Frequency | 2-pole | 4-pole | 6-pole | 8-pole |
|---|---|---|---|---|
| 10 Hz | 600 | 300 | 200 | 150 |
| 20 Hz | 1200 | 600 | 400 | 300 |
| 30 Hz | 1800 | 900 | 600 | 450 |
| 40 Hz | 2400 | 1200 | 800 | 600 |
| 45 Hz | 2700 | 1350 | 900 | 675 |
| 50 Hz | 3000 | 1500 | 1000 | 750 |
| 60 Hz | 3600 | 1800 | 1200 | 900 |
The relationship is linear, so halving the frequency halves the synchronous speed. For the theory behind the formula and a full slip calculation, see our guide on how to compute RPM.
Why Displayed RPM Can Differ From Shaft RPM
An induction motor must slip behind the rotating field to produce torque. NEMA lists a nominal full-load speed of about 1750 RPM for a 4-pole, 60 Hz motor with an 1800 RPM synchronous speed.
What your drive displays depends on its control mode. Mitsubishi’s FR-E800 manual explains that under V/F control, the displayed value is synchronous speed, or actual motor speed plus motor slip. With advanced magnetic flux vector or Real sensorless vector control, the display uses an estimated actual speed. With encoder feedback or Vector control, it uses the actual speed from the encoder.
| Control mode | What the FR-E800 displays |
|---|---|
| V/F control | Synchronous speed, including slip |
| Advanced magnetic flux vector | Estimated actual speed |
| Real sensorless vector | Estimated actual speed |
| PM sensorless vector | Estimated actual speed |
| Encoder feedback or Vector control | Actual speed from the encoder |
Setting Up a Drive Speed Display
Parameter numbers differ between drives, so this example uses one documented model, the Mitsubishi FR-E800.
| Parameter | Name | Function |
|---|---|---|
| Pr.53 | Frequency / rotation speed unit switchover | 0 = frequency, 1 = rotation speed, 4 = machine speed |
| Pr.81 | Number of motor poles | Used in the RPM calculation |
| Pr.37 | Speed display | Machine speed at the Pr.505 frequency |
| Pr.505 | Speed setting reference | Reference frequency for Pr.37 |
Worked example: conveyor speed display
A conveyor moves at 45 m/min when the drive outputs 60 Hz. You want the panel to show metres per minute.
- Set Pr.53 = 4 for machine speed display.
- Set Pr.505 = 60, the reference frequency.
- Set Pr.37 = 45, the machine speed at 60 Hz.
- At 40 Hz, the display is 45 × 40 ÷ 60 = 30.
The manual’s own example uses Pr.505 = 60 Hz and Pr.37 = 1000, so the panel shows 1000 at 60 Hz and 500 at 30 Hz. Measure the real machine speed at the reference frequency, because belts, gears and roller sizes all affect the scale.
If the speed is shown on a separate screen, use the same scale in your HMI display. For surface speed, see the RPM to FPM guide. A simple speed reference can also come from a potentiometer.
Common Display Problems
| Problem | Likely cause | Fix |
|---|---|---|
| RPM is double or half | Wrong motor pole setting | Check poles against the nameplate speed |
| RPM slightly above tachometer | V/F display includes slip | Expected, or use a vector mode with correct motor data |
| Machine speed scale is wrong | Reference values do not match | Re-measure at a known frequency |
| Value shows as dashes | FR-E800 panel limit is 4 digits | Display frequency above 9999 |
| Display jumps slightly | Rounding during conversion | Normal on converted values |
For choosing a speed control method, read VFD vs soft starter. Motor protection still needs attention at low speed, so review your overload protection as well.
Frequently Asked Questions
How do you convert Hz to RPM?
Use RPM = Hz × 120 ÷ poles. A 4-pole motor at 60 Hz has a synchronous speed of 1800 RPM.
How many RPM is 60 Hz?
It depends on poles: 3600 for 2-pole, 1800 for 4-pole, 1200 for 6-pole and 900 for 8-pole, before slip.
How many RPM is 50 Hz?
Synchronous speed is 3000 for 2-pole, 1500 for 4-pole, 1000 for 6-pole and 750 for 8-pole.
How do you convert RPM to Hz?
Use Hz = RPM × poles ÷ 120. For a 4-pole motor, 1350 RPM corresponds to 45 Hz synchronous.
Why does my VFD show a different RPM from my tachometer?
Under V/F control, a drive may display synchronous speed, which includes motor slip. A tachometer reads the actual shaft speed.
How do I show RPM on a Mitsubishi FR-E800?
Set Pr.53 to 1 and make sure the number of motor poles is set correctly in Pr.81.
Can a VFD display conveyor speed?
Yes, if it has a machine speed scale. On the FR-E800, set Pr.53 to 4, then use Pr.37 and Pr.505 to define the scale.
Is it safe to run a motor above 60 Hz?
Only within the limits of the motor, drive and driven machine. Check the maker’s maximum speed before raising the frequency.