To select a 12 VDC micro PLC with RS-232 modem support, first check two lines on the data sheet: the permissible supply range (it must reach below your lowest battery voltage) and the communication ports. Few micro PLCs offer both. The Siemens LOGO! 12/24RCE runs from 10.8 to 28.8 V DC but has Ethernet rather than RS-232. The Unitronics Jazz supports RS-232 modems but needs 20.4 to 28.8 V DC. So most 12 V modem projects use either an Ethernet modem or a 24 V PLC behind a DC-DC converter.
| Requirement | What to check | Example from data sheets |
|---|---|---|
| Runs on 12 V | Permissible DC range, not just “rated voltage” | LOGO! 12/24RCE: 10.8 to 28.8 V DC |
| Low battery drain | Current at 12 V for the base and each module | LOGO! 12/24RCE: 50 to 165 mA at 12 V |
| Serial modem link | A real RS-232 port, and how it is powered | Jazz RS-232 port powered by modem DTR/RTS, 5 to 15 V |
| Remote messaging | Modem, SMS or protocol support | Jazz JZ20-R31: SMS to and from 6 GSM numbers |
| Ride-through | Voltage failure buffering | LOGO! 12/24RCE: typ. 2 ms at 12 V |
What Makes a Micro PLC Different
A micro PLC packs the CPU, power supply and a small set of I/O into one housing. Siemens’ LOGO! 12/24RCE, for example, has 8 digital inputs (4 usable as 0 to 10 V analog inputs) and 4 relay outputs rated up to 10 A resistive, on a 4-module-wide DIN rail housing. That makes it a good fit for remote pump stations, gates and small machines, but it limits expansion and communication options compared with a modular controller.
If you are still deciding between a micro PLC and a smart relay, see programmable relays vs PLC. For a general selection method, read how to select a PLC.
Check the 12 V Supply Range First
“12/24 V” on the front of a PLC does not tell you enough. What matters is the permissible range. Siemens gives the LOGO! 12/24RCE and 12/24RCEo a range of 10.8 to 28.8 V DC, with reverse polarity protection. Unitronics gives its Jazz JZ20 and JZ10 controllers 20.4 to 28.8 V DC with less than 10% ripple, so they cannot run directly from a 12 V battery.
Inputs need checking too. On the LOGO! 12/24RCE, a digital input reads signal 0 below 5 V DC and signal 1 above 8.5 V DC, so 12 V field devices work. Jazz digital inputs need 17 to 28.8 V DC for a logic 1, which suits 24 V field wiring only.
RS-232 and Modem Support
Here is the main trade-off. The Siemens data sheet for the LOGO! 12/24RCEo lists integrated Ethernet, an integrated web server and data logging, but no RS-232 port. That suits a modern cellular router with an Ethernet port, but not an older serial or dial-up modem.
Unitronics documents a different approach. The Jazz RS-232 programming port add-on supports devices that supply active DTR and RTS signals, “such as most modems”, and takes its power from those signals over a 5 to 15 V range. Unitronics notes that modems require an appropriate adapter, and where the supply is 12 V a 68 Ω, 1 W series resistor is used in the power-in line. The JZ20-R31 specification also lists GSM SMS support and MODBUS master-slave.
For RS-232 wiring, handshaking lines and null modem cables, see our DB9 pinout guide. If the modem link drops messages, our guide to radio link timeouts covers timeout and retry settings.
Battery Power Budget Calculator
The default values use Siemens’ maximum 12 V figures: 165 mA for a LOGO! 12/24RCE base and 90 mA for one DM8 12/24R expansion module. The modem value is a placeholder. Replace it with the average current from your modem’s data sheet, since a cellular modem’s draw changes while it transmits.
Worked Example: Remote Pump Station
A pump station runs from a 12 V, 40 Ah battery charged by a small solar panel. The owner wants alarms sent by modem.
| Item | Choice and reason |
|---|---|
| PLC | LOGO! 12/24RCE, because it runs from 10.8 to 28.8 V DC |
| I/O | 8 DI and 4 relay outputs on the base, plus a DM8 12/24R if more are needed |
| Modem link | Ethernet cellular router, because the LOGO! has Ethernet and no RS-232 |
| Load | 165 + 90 + 150 mA = 405 mA (modem figure assumed) |
| Runtime at 50% usable capacity | 20 Ah ÷ 0.405 A ≈ 49 hours without sun |
If the site already has an RS-232 modem and a SCADA system that polls over serial, option B is simpler: a 24 V micro PLC with an RS-232 port, powered through a 12 to 24 V DC-DC converter. Size the battery cable with our 12V wire size calculator so voltage drop does not push the PLC below its range.
Selection Checklist
- Lowest battery voltage under load is above the PLC’s permissible minimum.
- Highest charging voltage is below the permissible maximum.
- Input thresholds work with 12 V sensors.
- Port type matches the modem: RS-232, RS-485 or Ethernet.
- Protocol matches the SCADA or messaging system, for example MODBUS or SMS.
- Current budget includes the PLC, modules, modem and any converter losses.
- Programming software and cable are available.
For how a PLC fits into larger systems, see what is a PLC and PLC vs DCS vs SCADA.
Frequently Asked Questions
What is a micro PLC?
A small, low-cost controller with a fixed set of built-in I/O, often a few dozen points or fewer, sometimes with an integrated display. It suits pump stations, small machines and remote sites.
Can a micro PLC run on 12 V DC?
Some can. The Siemens LOGO! 12/24RCE is rated for 12 or 24 V DC with a permissible range of 10.8 to 28.8 V DC. Many others, such as the Unitronics Jazz JZ20, need 20.4 to 28.8 V DC.
Does the LOGO! 12/24RCE have an RS-232 port?
Its Siemens data sheet lists integrated Ethernet, not RS-232. For a dial-up or serial modem you would need another route, such as an Ethernet-based modem or router.
How much current does a LOGO! 12/24RCE draw at 12 V?
Siemens lists 50 mA to 165 mA at 12 V DC for the base module, and 20 mA to 90 mA for a DM8 12/24R expansion module.
Can a PLC RS-232 port power a modem link?
On the Unitronics Jazz RS-232 programming port, the port takes power from the modem’s active DTR and RTS signals, 5 to 15 V. Unitronics notes that modems need an appropriate adapter.
What happens if a 12 V battery drops below 10.8 V?
It is below the LOGO! 12/24RCE permissible range, so the PLC may reset or stop. Siemens gives only about 2 ms of voltage failure buffering at 12 V.
Should I use a 12 to 24 V converter instead?
It is a valid option if you need a specific 24 V PLC with RS-232. Size the converter for the PLC, I/O and modem together, and include its own losses in your battery budget.
Is GSM or SMS support available on micro PLCs?
Some support it. The Unitronics JZ20-R31 specification lists SMS messages to and from 6 GSM phone numbers.
Sources and Further Reading
- Siemens: Product Information for LOGO! System Manual 06/2023 edition (A5E53808149-AA, 05/2024): 12/24 V technical data.
- Siemens: Data sheet 6ED1052-2MD08-0BA3, LOGO! 12/24RCEo: supply range, I/O, Ethernet.
- Unitronics: Jazz JZ20-R31 technical specifications: supply range, GSM and MODBUS.
- Unitronics: JZ-PRG RS-232 programming port guide: modem support and port power.
- Unitronics: Jazz JZ10-11 technical specifications: supply range.