AWG Wire Ampacity Chart: NEC Tables vs Real-World Current

By editor Updated 8 min read
Three copper conductors growing from 10 to 6 AWG with ampacity tags beside a temperature gauge

8 AWG copper wire is rated 40 A at 60°C, 50 A at 75°C and 55 A at 90°C under NEC Table 310.16. For THHN or THWN landed on standard 75°C terminals, the usual answer is 50 A. For 8 AWG NM-B (Romex) cable, it is 40 A. Those values assume no more than three current-carrying conductors and a 30°C (86°F) ambient, so hot locations and full conduits reduce them.

Copper AWG60°C75°C90°CLargest standard breaker within the 75°C value
14 AWG15 A20 A25 A15 A
12 AWG20 A25 A30 A20 A
10 AWG30 A35 A40 A30 A
8 AWG40 A50 A55 A50 A
6 AWG55 A65 A75 A60 A
4 AWG70 A85 A95 A80 A
Copper ampacity from NEC Table 310.16. Breaker values for 14 to 10 AWG reflect the 240.4(D) limits. Check the edition adopted locally.
Reader tip: Use the 75°C column only when the breaker, lugs and equipment at both ends are rated for it. If any termination is rated 60°C, use the 60°C column.
40 A
8 AWG at 60°C
50 A
8 AWG at 75°C
55 A
8 AWG at 90°C
30°C
Table ambient temperature

8 AWG, 6 AWG and 10 AWG Ampacity Compared

These three sizes cover many feeders, ranges, heaters, welders and EV circuits. Each has three table values because insulation can tolerate different temperatures. A higher column is not automatically usable, since the wire is only one part of the circuit.

Copper ampacity of 10, 8 and 6 AWG by temperature column10 AWG is 30, 35 and 40 amps. 8 AWG is 40, 50 and 55 amps. 6 AWG is 55, 65 and 75 amps at 60, 75 and 90 degrees Celsius.Copper ampacity by temperature column60°C75°C90°C30 A35 A40 A10 AWG40 A50 A55 A8 AWG55 A65 A75 A6 AWGIndustrialBasicsindustrialbasics.com
Figure 1: The same wire has three table values. The terminals and insulation decide which one you can use.
WireCommon insulationTypical usable valueWhy
10 AWG THHN90°C30 A240.4(D) limits the overcurrent device
8 AWG THHN90°C50 A75°C terminals
8 AWG NM-B90°C conductors40 A334.80 limits NM-B to the 60°C value
6 AWG THHN90°C65 A75°C terminals
6 AWG NM-B90°C conductors55 A334.80 limits NM-B to the 60°C value
Typical values before any correction or adjustment.

Why the NEC Has Three Temperature Columns

Ampacity is the current a conductor can carry continuously without exceeding its temperature rating. The column depends on the insulation, but NEC 110.14(C) adds a second limit: the conductor must not run hotter than the lowest-rated termination it connects to.

Circuit or terminalDefault columnException
100 A or less, or 14 to 1 AWG terminals60°C75°C or 90°C if the equipment is listed and identified for it
Over 100 A, or terminals larger than 1 AWG75°CHigher only if the equipment is listed for it
A summary of the NEC 110.14(C) termination rule.

In practice, many modern breakers and lugs are listed for 75°C, which is why the 75°C column is so often used. Read the marking on the device instead of assuming. The same logic applies when you size a wire for a 50 amp circuit.

How to Calculate Real-World Ampacity

The table value holds only for its stated conditions. On a real job, work through these five steps.

Five steps to find usable wire ampacityStart with the insulation column, correct for ambient temperature, adjust for bundled conductors, cap at the terminal rating, then select the breaker.How to find usable ampacity1StartInsulation column2CorrectAmbient temperature3AdjustConductors bundled4CapTerminal rating5ProtectBreaker sizeIndustrialBasicsindustrialbasics.com
Figure 2: The table value is only the first step.

Correct for ambient temperature

Ambient °C60°C wire75°C wire90°C wire
26–301.001.001.00
31–350.910.940.96
36–400.820.880.91
41–450.710.820.87
46–500.580.750.82
51–550.410.670.76
56–60Not usable0.580.71
Ambient correction factors for a 30°C base, NEC 310.15(B).

Adjust for bundled conductors

Current-carrying conductorsPercent of value
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%
Adjustment factors from NEC 310.15(C)(1). Equipment grounding conductors are not counted.

Worked example: 8 AWG THHN in a hot conduit

Six current-carrying 8 AWG THHN conductors run through a 40°C space and land on 75°C terminals.

55 A × 0.91 × 0.80 = 40.04 A
Terminal limit = 50 A
Usable ampacity = 40 A
Derating 8 AWG THHN from 55 amps to 40 ampsAn 8 AWG THHN conductor starts at 55 amps, falls to 50.05 amps at 40 degrees Celsius, and to 40.04 amps with six current-carrying conductors. The 75 degree terminal limit is 50 amps.8 AWG THHN derating example90°C table value55.00 AAfter 40°C correction (× 0.91)50.05 AAfter 6-conductor adjustment (× 0.80)40.04 A75°C terminal limit: 50 AIndustrialBasicsindustrialbasics.com
Figure 3: Derating starts from the 90°C value, and the result must also stay within the terminal limit.

The table below applies the same conditions to other sizes: THHN at 40°C with four to six current-carrying conductors.

Copper AWG90°C baseAfter 0.91 × 0.80Usable with 75°C terminals
14 AWG25 A18.2 A18.2 A
12 AWG30 A21.8 A21.8 A
10 AWG40 A29.1 A29.1 A
8 AWG55 A40.0 A40.0 A
6 AWG75 A54.6 A54.6 A
4 AWG95 A69.2 A69.2 A
Derating example for 90°C wire. Small conductors remain subject to the 240.4(D) overcurrent limits.

Breaker Size and Continuous Loads

Ampacity and breaker size are separate checks. For 14, 12 and 10 AWG copper, NEC 240.4(D) generally caps the overcurrent device at 15 A, 20 A and 30 A, even though the table shows higher numbers. Specific equipment, such as motor circuits, has its own rules. Our guide to types of circuit breakers explains how the protective device itself works.

For a continuous load, one expected to run for three hours or more, branch circuit conductors are generally sized for 125% of that load under NEC 210.19.

40 A continuous × 1.25 = 50 A → 8 AWG copper at 75°C
Remember: A wire that passes the ampacity check can still fail the terminal, breaker or continuous-load check. All of them must pass.

Voltage Drop: The Limit Ampacity Does Not Show

Ampacity protects the wire from overheating, but it says nothing about the voltage reaching the load. On long runs, voltage drop often forces a larger wire. For a single-phase circuit, a simple estimate uses the DC resistance from NEC Chapter 9 Table 8.

Vdrop = 2 × L × R × I / 1000
40 A, 240 V, 100 ft one wayResistance (Ω/1000 ft)Voltage dropPercent
10 AWG1.249.92 V4.1%
8 AWG0.7786.22 V2.6%
6 AWG0.4913.93 V1.6%
Stranded copper at 75°C. The 10 AWG row shows voltage drop only, because 10 AWG is not suitable for a 40 A circuit.

Long motor circuits deserve extra care, because low voltage at startup can cause nuisance trips and overheating. See our guides to motor failure causes and types of electrical cables when choosing a conductor for a demanding load.

Common Ampacity Mistakes

MistakeWhy it is a problemCorrect approach
Using 55 A for 8 AWG on a 75°C breakerThe terminal can overheatLimit the load to 50 A
Treating NM-B as 90°C wireIts final ampacity is limited to 60°CUse 90°C only as a derating start
Ignoring attic or rooftop heatThe conductor runs hotter than the table assumesApply the ambient correction factor
Counting only one circuit in a conduitHeat from all conductors adds upCount all current-carrying conductors
Forgetting continuous loadThe conductor may be undersizedApply 125% where required
Using chassis wiring chartsThey assume different conditionsUse the NEC table for premises wiring
Mistakes that lead to overheated connections or failed inspections.
Safety note: Isolate the circuit and prove it dead before working on conductors, following your lockout/tagout procedure. In industrial panels, also assess arc flash risk. This guide is educational, and local code and your inspector have the final say.

Small control wires need their own check. Our guide to 22 AWG amps at 12V DC explains its limit and includes a voltage drop calculator.

Once the wire size is chosen, make sure the box is big enough too: the NEC box fill chart gives the cubic-inch allowance for each conductor, device and ground.

Above 4/0, sizes are in kcmil: see our guide to 500 MCM wire and kcmil sizes.

Frequently Asked Questions

What is the ampacity of 8 AWG copper wire?

Under NEC Table 310.16, 8 AWG copper is rated 40 A in the 60°C column, 50 A in the 75°C column and 55 A in the 90°C column. For most breaker and lug connections rated 75°C, the usable value is 50 A before any derating.

Can 8 AWG wire carry 50 amps?

Yes, copper THHN or THWN can carry 50 A when both ends use terminals rated 75°C and no derating applies. 8 AWG NM-B cable cannot, because it is limited to the 60°C value of 40 A.

What is the ampacity of 6 AWG copper wire?

6 AWG copper is rated 55 A at 60°C, 65 A at 75°C and 75 A at 90°C.

What is the ampacity of 10 AWG copper wire?

10 AWG copper is rated 30 A at 60°C, 35 A at 75°C and 40 A at 90°C. NEC 240.4(D) generally limits its overcurrent protection to 30 A.

Why can’t I use the 90°C ampacity?

You can usually use it as the starting point for derating, but the final load is still limited by the lowest temperature rating in the circuit. Most terminals are rated 60°C or 75°C.

What size wire do I need for a 40 amp continuous load?

Size the conductor for 125% of the continuous load, which is 50 A. 8 AWG copper at 75°C meets that if no derating applies and the terminals are rated 75°C.

Does conduit fill reduce wire ampacity?

Yes. With more than three current-carrying conductors in a raceway or cable, the ampacity is reduced. For example, four to six conductors use 80% of the value.

Is NEC ampacity the same as the maximum current a wire can survive?

No. Ampacity is the continuous current a conductor can carry under its conditions of use without exceeding its temperature rating. It is a safe operating limit, not a melting or fusing point.