What Size Wire for 50 Amp? NEC Chart, THHN Sizing and Derating

By editor 11 min read
Three-conductor cable cross-section labelled 50 A with 8 AWG and 6 AWG

For a 50 amp circuit, use at least 8 AWG copper THHN/THWN-2 when every termination is rated 75°C, or 6 AWG aluminum under the same conditions. Use 6 AWG copper if you are running NM-B (Romex-style) cable, if any terminal is only rated 60°C, or if you want extra margin for heat and distance. Those answers assume no more than three current-carrying conductors and an ambient temperature of about 30°C (86°F).

Wiring situationMinimum wire sizeAmpacity usedWorks on 50 A?
Copper THHN, 75°C terminals8 AWG50 AYes, with no derating
Copper NM-B cable6 AWG55 A (60°C column)Yes
Copper, 60°C terminals6 AWG55 AYes
Aluminum, 75°C terminals6 AWG50 AYes, with AL-rated terminals
Copper, 4 to 6 conductors in conduit6 AWG60 A after 80% adjustmentYes
Continuous 50 A load6 AWG copper65 A against 62.5 A requiredNeeds a larger breaker, usually 70 A
Quick answer based on NEC Table 310.16 values. Your local code edition and equipment instructions take priority.
Reader tip: Size for the real installation, not just the breaker number. The same 50 A breaker can need 8 AWG in one job and 4 AWG in another once heat, bundling and distance are counted.
8 AWG Cu
Minimum copper at 75°C
6 AWG Cu
Minimum for NM-B cable
6 AWG Al
Minimum aluminum at 75°C
10 AWG Cu
Minimum copper equipment ground

50 Amp Wire Size Chart

This chart shows the conductors people most often compare for a 50 A circuit. Read across to the temperature column that matches your lowest-rated termination, not the insulation printed on the wire.

Conductor60°C75°C90°C50 A verdict
8 AWG copper40 A50 A55 AOnly with 75°C terminals
6 AWG copper55 A65 A75 AYes, most versatile
4 AWG copper70 A85 A95 AYes, for long or hot runs
6 AWG aluminum40 A50 A55 AOnly with 75°C terminals
4 AWG aluminum55 A65 A75 AYes
3 AWG aluminum65 A75 A85 AYes, for long runs
Allowable ampacity for not more than three current-carrying conductors at 30°C ambient, as reproduced from NEC Table 310.16.
Conductor ampacity compared with a 50 amp breakerAt 75 degrees Celsius, 8 AWG copper and 6 AWG aluminum reach 50 amps. In the 60 degree column 8 AWG copper reaches only 40 amps and 6 AWG copper reaches 55 amps. 8 AWG aluminum reaches 40 amps.Usable ampacity against a 50 A breaker0 A20 A40 A60 A8 AWG Cu, 60°C (NM-B)8 AWG Cu, 60°C (NM-B): 40 A, below 50 A40 A ✗8 AWG Al, 75°C8 AWG Al, 75°C: 40 A, below 50 A40 A ✗6 AWG Al, 75°C6 AWG Al, 75°C: 50 A, meets 50 A50 A ✓8 AWG Cu, 75°C (THHN)8 AWG Cu, 75°C (THHN): 50 A, meets 50 A50 A ✓6 AWG Cu, 60°C (NM-B)6 AWG Cu, 60°C (NM-B): 55 A, meets 50 A55 A ✓6 AWG Cu, 75°C (THHN)6 AWG Cu, 75°C (THHN): 65 A, meets 50 A65 A ✓50 AIndustrialBasicsindustrialbasics.com
Figure 1: Which common conductors reach 50 A, before any derating.

Why the Answer Changes: 8 AWG or 6 AWG?

Most disagreement online comes from people quoting different columns of the same table. Three things decide which number applies to your circuit.

1. Terminal temperature rating

NEC 110.14(C) says the ampacity you use must not exceed the temperature rating of the lowest-rated part connected to the conductor. On circuits of 100 A or less, assume the 60°C column unless the equipment is listed and marked for 75°C. Most modern circuit breakers are marked 60/75°C, but check the label instead of assuming.

Termination temperature chainA circuit runs from a 75 degree breaker through 90 degree THHN wire and a 75 degree lug to equipment with a 60 degree terminal. The 60 degree rating limits 8 AWG copper to 40 amps.The lowest temperature rating sets the columnBreaker75°C terminalTHHN wire90°C insulationLug / splice75°C ratingEquipment60°C terminalWeakest link is 60°C, so 8 AWG copper is limited to 40 A on this circuitIndustrialBasicsindustrialbasics.com
Figure 2: THHN is rated 90°C, but the final ampacity cannot exceed what the weakest termination allows.

2. Cable type

THHN is a single conductor normally pulled through conduit. NM-B has 90°C conductors inside, but NEC 334.80 limits its final ampacity to the 60°C column. That single rule is why 8 AWG THHN can serve a 50 A breaker while 8 AWG NM-B cannot. Our guide to types of electrical cables explains how the common constructions differ.

3. Installation conditions

Heat and bundling stop a conductor from shedding heat. Above 30°C, or with more than three current-carrying conductors together, you must reduce the allowable ampacity. A wire that passes in a cool basement can fail in a hot attic or a crowded conduit.

How to Size Wire for 50 Amps

Follow these steps in order. They work for most general branch circuits and feeders. Motors, welders and some other equipment have their own NEC articles, covered further down.

Five-step wire sizing methodFind the load, multiply continuous load by 1.25, identify the termination temperature column, apply derating, then choose a wire that passes both checks.Five steps to size a 50 A circuit1Find the loadNameplate amps2Continuous?If 3 h or more, × 1.253Termination limit60°C or 75°C column4DerateStart at 90°C for THHN5Pick the wireSmaller result must passIndustrialBasicsindustrialbasics.com
Figure 3: The sizing order used in the worked examples below.
  1. Find the load current. Use the equipment nameplate or a load calculation.
  2. Add 25% for continuous loads. A continuous load is expected to run for three hours or more. Multiply that portion by 1.25.
  3. Choose the breaker. The breaker must suit the calculated load and the equipment instructions.
  4. Check the termination column. The conductor must carry the calculated load using the 60°C or 75°C value that your terminals allow.
  5. Apply correction and adjustment. For 90°C wire such as THHN, you may start derating from the 90°C value.
  6. Take the smaller result. Compare the derated ampacity with the termination-limited ampacity. The lower number is what you can use.
  7. Check voltage drop. Increase the size for long runs, then size the equipment ground to match.
Usable ampacity = smaller of
(90°C ampacity × temperature factor × conductor-count factor)
and (termination-column ampacity)

THHN Derating for a 50 Amp Circuit

Derating has two parts. The temperature correction factor accounts for hot surroundings, and the adjustment factor accounts for more than three current-carrying conductors in a raceway or cable.

Ambient temperature75°C wire factor90°C wire factor
26 to 30°C (79 to 86°F)1.001.00
36 to 40°C (97 to 104°F)0.880.91
41 to 45°C (106 to 113°F)0.820.87
46 to 50°C (115 to 122°F)0.750.82
Selected temperature correction factors for a 30°C base, NEC Table 310.15(B)(1).
Current-carrying conductorsAdjustment factor
1 to 3100%
4 to 680%
7 to 970%
10 to 2050%
Adjustment factors, NEC Table 310.15(C)(1).

The next table does the arithmetic for THHN with 75°C terminations. A tick means the conductor can still carry 50 A.

THHN and ambient1 to 3 conductors4 to 6 conductors7 to 9 conductors
8 AWG Cu at 30°C50.0 A ✓44.0 A38.5 A
8 AWG Cu at 40°C50.0 A ✓40.0 A35.0 A
8 AWG Cu at 45°C47.9 A38.3 A33.5 A
8 AWG Cu at 50°C45.1 A36.1 A31.6 A
6 AWG Cu at 30°C65.0 A ✓60.0 A ✓52.5 A ✓
6 AWG Cu at 40°C65.0 A ✓54.6 A ✓47.8 A
6 AWG Cu at 45°C65.0 A ✓52.2 A ✓45.7 A
6 AWG Cu at 50°C61.5 A ✓49.2 A43.0 A
4 AWG Cu at 30°C85.0 A ✓76.0 A ✓66.5 A ✓
4 AWG Cu at 40°C85.0 A ✓69.2 A ✓60.5 A ✓
4 AWG Cu at 45°C82.7 A ✓66.1 A ✓57.9 A ✓
4 AWG Cu at 50°C77.9 A ✓62.3 A ✓54.5 A ✓
Calculated from the 90°C ampacity, then capped at the 75°C termination value.
Key point: The 90°C column is a starting point for derating, not a higher rating you can use at the breaker. This is the single most common THHN mistake.

Worked Examples

Example 1: 8 AWG THHN in a warm room

You have three current-carrying 8 AWG copper THHN conductors, 75°C terminals and a 40°C ambient.

55 A × 0.91 = 50.05 A
Termination limit = 50 A
Usable ampacity = 50 A ✓

8 AWG passes, but with no margin. Any more heat or another conductor in the conduit would fail it.

Example 2: Four conductors in one conduit

Now the conduit holds four current-carrying conductors at 30°C.

8 AWG: 55 A × 0.80 = 44 A ✗
6 AWG: 75 A × 0.80 = 60 A ✓

8 AWG is no longer enough, so move up to 6 AWG. Its 60 A result is below its 65 A termination limit, so 60 A is the usable value.

Example 3: Hot location with six conductors

Six current-carrying conductors run through a 45°C space.

6 AWG: 75 A × 0.87 × 0.80 = 52.2 A ✓

6 AWG still supports the 50 A breaker. At 50°C the same calculation gives 49.2 A, so you would need 4 AWG.

Example 4: A true 50 A continuous load

A heater draws 50 A continuously.

50 A × 1.25 = 62.5 A minimum

8 AWG is out. 6 AWG copper at 75°C gives 65 A, which covers it. A 50 A breaker is too small for this load. The next standard size that covers 62.5 A is 70 A, which NEC 240.4(B) can permit on a 65 A conductor when its conditions are met. Check the heater instructions for the maximum overcurrent device.

Voltage Drop and Long Runs

Ampacity tells you the wire will not overheat. It does not tell you the equipment will get enough voltage. The NEC includes an informational recommendation of no more than 3% drop on a branch circuit and 5% overall.

Voltage drop (single-phase) = 2 × L × I × R ÷ 1000

Here, L is the one-way length in feet, I is the current, and R is resistance in ohms per 1,000 ft. For a 240 V circuit, a 3% limit is 7.2 V.

Copper conductorR (Ω/1000 ft)Max run at 30 AMax run at 40 AMax run at 50 A
8 AWG Cu0.778154 ft115 ft92 ft
6 AWG Cu0.491244 ft183 ft146 ft
4 AWG Cu0.308389 ft292 ft233 ft
Approximate one-way distance for 3% drop at 240 V, using stranded DC resistance at 75°C from NEC Chapter 9, Table 8. AC circuits in conduit vary slightly.

Quick example: a 40 A load 150 ft away on 8 AWG drops 2 × 150 × 40 × 0.778 ÷ 1000 = 9.3 V, or 3.9%. On 6 AWG it drops 5.9 V, or 2.5%, so the larger wire is the better choice.

50 Amp Wire Size by Application

ApplicationTypical wiringWhat to watch
Electric range6 AWG NM-B, or 8 AWG THHN in conduitOften needs a neutral, so use a 3-wire plus ground circuit
40 A EV charger6 AWG copper is the common choiceContinuous load; follow the charger manual
RV outlet (120/240 V)6 AWG copper, 4-wireNeeds two hots, neutral and ground
Subpanel feeder6 AWG copper, 4-wireKeep neutral and ground separate at the subpanel
Hot tub or spaPer manufacturerWet-location and bonding rules apply
WelderPer nameplateNEC Article 630 has its own sizing rules
MotorPer FLC tablesNEC Article 430 applies, not the simple 50 A rule
Typical examples only. The equipment listing and local code decide the final design.

Motors deserve special care. Their branch conductors are based on full-load current from the NEC tables, and the short-circuit device may be larger than the wire ampacity because a separate thermal overload relay provides overload protection. See our guide to motor starters for how those parts work together.

In a panel, conductor sizing also has to fit the wider protection scheme. If you are choosing the device itself, compare MCB, MCCB and ACB ratings, and read about protection coordination on larger systems so the nearest device clears a fault first.

Ground Wire and Neutral Size for 50 Amps

NEC Table 250.122 sizes the equipment grounding conductor from the overcurrent device rating. For a 50 A breaker, it falls in the 60 A row.

Overcurrent deviceCopper EGCAluminum EGC
Up to 60 A10 AWG8 AWG
Up to 100 A8 AWG6 AWG
Minimum equipment grounding conductor sizes, NEC Table 250.122.

If you increase the hot conductors for voltage drop, NEC 250.122(B) generally requires a proportional increase in the grounding conductor. The neutral must be sized for the neutral load. If you are working across US and UK documents, our explainer on earthing vs grounding clears up the terminology.

Common 50 Amp Wiring Mistakes

  • Using the 90°C value at the breaker. THHN at 55 A does not mean 8 AWG can carry 55 A on 75°C terminals.
  • Putting 8 AWG NM-B on a 50 A breaker. It is limited to 40 A.
  • Forgetting the 125% continuous-load rule. This matters most for EV chargers and heaters.
  • Ignoring conduit fill and heat. Extra circuits in one conduit can quietly remove your margin.
  • Using aluminum on copper-only terminals. Terminals must be marked for aluminum, usually AL/CU.
  • Not torquing terminals. Loose connections overheat. Use a calibrated tool and the value on the equipment label.
  • Using THHN in a wet location without a wet rating. Check that the conductor is also marked THWN-2 or another wet-rated type.
Safety note: De-energize and verify before working on a circuit. Follow a proper lockout/tagout procedure and use suitable electrical PPE. Permits and licensed work may be required in your area. This guide is educational and does not replace the NEC edition adopted locally, your inspector, or the equipment instructions.

Frequently Asked Questions

What size wire do I need for a 50 amp breaker?

Use at least 8 AWG copper THHN/THWN-2 with 75°C terminations, or 6 AWG aluminum with 75°C terminations. Use 6 AWG copper for NM-B cable, because NM-B is limited to the 60°C column.

Can 8 gauge wire handle 50 amps?

Yes, 8 AWG copper is rated 50 A in the 75°C column, so it works in conduit with 75°C terminals and no derating. It is only rated 40 A in the 60°C column, so 8 AWG NM-B cannot be used on a 50 A breaker.

Is 6 gauge wire good for 50 amps?

Yes. 6 AWG copper is rated 55 A at 60°C and 65 A at 75°C. It is the safer general choice for 50 A circuits and leaves margin for heat, bundling and voltage drop.

Can I use 6/2 NM-B on a 50 amp breaker?

Yes, 6 AWG copper NM-B is rated 55 A in the 60°C column. Choose 6/3 if the load needs a neutral, such as many ranges and subpanels.

What size aluminum wire is needed for 50 amps?

Use 6 AWG aluminum with terminals listed for aluminum and rated 75°C. 8 AWG aluminum reaches only 40 A at 75°C, so it is too small.

What size ground wire is required for a 50 amp circuit?

NEC Table 250.122 gives 10 AWG copper or 8 AWG aluminum for an overcurrent device up to 60 A. Increase it proportionally if you upsized the ungrounded conductors for voltage drop.

How far can you run 8 AWG wire on a 50 amp circuit?

At 240 V and a full 50 A, 8 AWG copper reaches about 92 ft one way before voltage drop passes 3%. At 40 A it reaches about 115 ft. For longer runs, move up to 6 AWG or 4 AWG.

Does a 40 amp EV charger need a 50 amp circuit?

Yes. EV charging is treated as a continuous load, so 40 A × 1.25 = 50 A. Follow the charger installation manual for the required conductor and breaker.