FLA Electrical Meaning: Full Load vs Running vs Starting Amps

By editor Updated 7 min read
Clamp meter reading motor current beside an electric motor nameplate with full load amps highlighted

FLA stands for Full Load Amps: the current a motor draws when it delivers its rated horsepower at rated voltage and frequency. You will find it on the motor nameplate. Running amps are what the motor actually draws at its present load, usually less than FLA. Starting amps, or locked rotor amps (LRA), are the much larger current drawn while the motor accelerates, typically around six times running current.

TermMeaningWhere it comes fromUsed for
FLARated current at full loadMotor nameplateOverload protection
FLCStandard full-load currentNEC Tables 430.248 and 430.250Conductors and short-circuit protection
Running ampsActual current right nowClamp meterChecking load and faults
LRACurrent with the rotor stoppedDatasheet or code letterStarting and voltage dip
Peak inrushFirst half-cycle transientMeasurement or datasheetNuisance trip analysis
SFACurrent at service factor loadNameplate, if listedUnderstanding overload margin
Motor current terms compared.
Reader tip: Do not use a single “motor amps” number for everything. The wire, breaker and overload are each sized from different values.
FLA
Nameplate rating
FLC
NEC table value
~6×
Typical starting current
125%
Common overload limit at SF 1.15

What Is Full Load Amps (FLA)?

FLA is a rated value measured by the manufacturer. It tells you how much current the motor is designed to draw when delivering its full rated output under rated conditions. It is not a limit on what the motor will try to draw. If the load increases, the current rises above FLA, and the motor heats up.

Example motor nameplate showing FLA, service factor and code letterAn example 10 horsepower 460 volt motor nameplate with FLA 13 amps, service factor 1.15 and code letter G highlighted.Where to find the currents on a nameplate3-PHASE INDUCTION MOTOR (EXAMPLE)HP10VOLTS460FLA13.0RPM1770HZ60SF1.15CODEGDESIGNBDUTYCONTFLA setsthe overloadSF affectsoverload %Code givesstarting kVAIndustrialBasicsindustrialbasics.com
Figure 1: An illustrative nameplate. Layouts vary by manufacturer.

How to estimate FLA

When you do not have the nameplate, you can estimate three-phase current from the horsepower, voltage, efficiency and power factor.

I = (HP × 746) / (√3 × V × η × PF)

For a 10 HP, 460 V motor with an assumed efficiency of 0.90 and power factor of 0.85:

I = (10 × 746) / (1.732 × 460 × 0.90 × 0.85) ≈ 12.2 A

Treat this as an estimate. Actual efficiency and power factor vary by motor, and it is not a substitute for the nameplate or the NEC table.

Running Amps vs FLA vs Starting Amps

A motor passes through all of these currents on a normal start. The first peak lasts only a fraction of a cycle. Current then stays near the locked rotor value until the motor approaches operating speed, and finally falls to a running value set by the load.

Motor current during an across-the-line startCurrent rises to a brief peak inrush, settles at locked rotor current during acceleration, then falls to running current, shown below the full load amps line.Motor current during an across-the-line startTime (not to scale)CurrentFLA (rated full load)Peak inrush (within half a cycle)Locked rotor current (LRA)Holds during accelerationRunning amps at actual loadIndustrialBasicsindustrialbasics.com
Figure 2: Running current depends on load. Here the motor is running below its rated load.

The U.S. Department of Energy notes that NEMA recognizes two parts of starting current: instantaneous peak inrush, which occurs within half an AC cycle, and locked rotor current, the RMS current that follows. In everyday speech, “inrush” often means locked rotor current, so check which one a document is describing.

NEC Table FLC vs Nameplate FLA

This is the distinction that matters most in design. NEC 430.6(A)(1) generally requires the table current for sizing conductors and short-circuit protection, even if the nameplate shows a lower figure. That way, the circuit still works if the motor is later replaced. The nameplate FLA is used to set overload protection.

Which motor current to use for each design taskUse the NEC table current for conductors and short-circuit protection, nameplate FLA for overload protection, the code letter for starting current, and measured amps for actual load.Which current to use for which jobNEC table FLCConductors and short-circuit protectionNameplate FLAOverload protectionCode letter / LRAStarting current and voltage dipMeasured running ampsActual load and troubleshootingIndustrialBasicsindustrialbasics.com
Figure 3: Mixing up these values is a common motor sizing error.
Three-phase HP230 V table FLC460 V table FLC
14.2 A2.1 A
515.2 A7.6 A
1028 A14 A
2568 A34 A
50130 A65 A
100248 A124 A
Selected values from NEC Table 430.250 for induction motors. Check the edition adopted locally.
Exception: Some motors are exceptions to the table rule, including certain multispeed, low-speed, torque, and shaded-pole or PSC fan motors. Check NEC 430.6 for your motor type.

Worked Example: 10 HP, 460 V Motor

Take a continuous-duty, three-phase motor with a nameplate FLA of 13 A, service factor 1.15 and code letter G.

StepCalculationResult
Table FLCNEC Table 430.250, 10 HP at 460 V14 A
Conductor ampacity14 A × 125%17.5 A minimum
Overload (SF 1.15)13 A × 125%16.25 A maximum
Locked rotor kVA10 HP × 5.6 to 6.29 kVA/HP56 to 62.9 kVA
Locked rotor ampskVA × 1000 / (1.732 × 460)About 70 to 79 A
One motor needs three different current values.
LRA = (HP × kVA/HP × 1000) / (√3 × V)

Once you know the ampacity you need, use our AWG wire ampacity chart to choose the conductor. A correctly set thermal overload relay then protects the motor, while the breaker or fuse handles short circuits.

NEMA code letters

Code letterLocked rotor kVA per HP
E4.5 to 4.99
F5.0 to 5.59
G5.6 to 6.29
H6.3 to 7.09
J7.1 to 7.99
K8.0 to 8.99
Common NEMA locked rotor code letters. The code letter is not the same as the motor design letter.

What Running Amps Tell You

Comparing measured current with FLA is one of the quickest motor health checks. Measure all three phases with a true RMS clamp meter while the motor runs under normal load.

ReadingWhat it may meanWhat to check
Well below FLALight loadOversized motor or a broken coupling
Close to FLANormal full-load operationTemperature and trend over time
Above FLAOverload or supply problemMechanical load, bearings and voltage
Unequal phase currentsUnbalance or winding faultSupply voltage and connections
Stays high after startMotor is not reaching speedLoad, voltage drop and starter
Using running current for troubleshooting.

High starting current can cause voltage dips and nuisance trips. A VFD or soft starter reduces it, and our guide to motor starters compares the options. For repeat failures, see motor failure causes.

Safety note: Measuring motor current involves energized equipment. Use a rated meter, keep the panel safe, assess arc flash risk and wear suitable electrical PPE. This guide is educational and does not replace the NEC or the motor manufacturer’s data.

To compare a motor’s running current with its FLA, you need a correct current reading; our guide on how to check amps with a multimeter covers the series method, jacks, fuses and clamp meters.

To work out what a motor is actually delivering, see how to calculate motor horsepower from amps, torque or pump duty.

Frequently Asked Questions

What does FLA mean in electrical terms?

FLA stands for Full Load Amps. It is the current a motor draws when producing its rated horsepower at rated voltage and frequency, and it is marked on the nameplate.

What is the difference between FLA and FLC?

FLA usually means the nameplate current of the actual motor. FLC often refers to the standard full-load current in the NEC tables. The NEC uses the table value for conductors and short-circuit protection, and the nameplate value for overload protection.

What is the difference between FLA and running amps?

FLA is a rating. Running amps are what the motor actually draws at the moment, which depends on load and voltage. A lightly loaded motor usually draws less than FLA.

What is LRA?

LRA stands for Locked Rotor Amps. It is the steady RMS current a motor draws at rated voltage with its rotor stopped, and the motor stays near this current during acceleration.

How much higher is starting current than FLA?

For across-the-line starting, it is typically around six times running current, and commonly quoted in a range of about 5 to 8 times. Use the code letter or manufacturer data for a real motor.

Is it bad if a motor draws more than FLA?

Sustained current above FLA means the motor is overloaded, or the supply has a problem, unless it is within the service factor allowance. It causes extra heat and shortens insulation life, so find the cause.

Can I size wire from the nameplate FLA?

For most general-purpose motors, no. NEC 430.6(A)(1) requires the table current for conductors and branch circuit protection. There are exceptions, including some multispeed and low-speed motors, so check the code.

What are service factor amps?

Service factor amps are the current at the motor’s service factor load, such as 1.15 times rated power. They describe a limited overload capability and are not a reason to reduce the circuit size.

Sources and Further Reading

About the author

editor

Leave a Comment