NEC 250.66: Grounding Electrode Conductor Sizing Table

By editor Updated 7 min read
Service panel connected by a 4 AWG grounding electrode conductor to a ground rod, with a 3/0 conductor cross-section

NEC Table 250.66 sizes the grounding electrode conductor (GEC) for AC systems from the largest ungrounded conductor, or the equivalent area of parallel conductors. Find your conductor size in the left columns and read the GEC size on the right. For example, 3/0 AWG copper service conductors require a 4 AWG copper or 2 AWG aluminum GEC. Smaller limits can apply to the part of the conductor that goes only to a rod, concrete-encased electrode or ground ring.

Largest ungrounded: copper (AWG/kcmil)Largest ungrounded: Al or CCA (AWG/kcmil)GEC: copperGEC: Al or CCA
2 or smaller1/0 or smaller8 AWG6 AWG
1 or 1/02/0 or 3/06 AWG4 AWG
2/0 or 3/04/0 or 2504 AWG2 AWG
Over 3/0 through 350Over 250 through 5002 AWG1/0 AWG
Over 350 through 600Over 500 through 9001/0 AWG3/0 AWG
Over 600 through 1100Over 900 through 17502/0 AWG4/0 AWG
Over 1100Over 17503/0 AWG250 kcmil
Table 250.66 values as printed in the NFPA Article 250 grounding and bonding fact sheet. CCA means copper-clad aluminum.
Check locally: Your local authority enforces its adopted NEC edition and any amendments. Confirm the requirement before you design or change a grounding system.
8 AWG
Smallest copper GEC
3/0 AWG
Largest copper GEC
6 AWG
Copper limit to a rod
4 AWG
Copper limit to concrete

GEC Size Calculator

Choose the conductor material, the largest ungrounded conductor and the number of parallel sets. The calculator adds the parallel area and reads the matching row of Table 250.66.

Table 250.66 GEC Size Calculator
IndustrialBasics calculator for Table 250.66 only. It does not apply the smaller electrode limits in 250.66(A), (B) or (C).

How to Read Table 250.66

  1. Identify the largest ungrounded conductor supplying the system.
  2. If conductors are in parallel, add the areas of the corresponding conductors in each set.
  3. Use the column for the ungrounded conductor material.
  4. Read across to the GEC column for the GEC material you will install.
  5. Check whether 250.66(A), (B) or (C) allows a smaller conductor for the electrode connection.

The GEC is not sized from the breaker rating. That is a common mix-up with the equipment grounding conductor chart, which uses the overcurrent device rating. If the terms are unfamiliar, our guide to earthing vs grounding explains the difference.

Reader tip: Note 2 to the table covers installations with no service-entrance conductors. In that case, size the GEC from the equivalent largest service-entrance conductor required for the load served.

Smaller Limits for Specific Electrodes

Table 250.66 is the general rule, but three electrode types have their own limit. Each limit applies only when the conductor does not extend on to another electrode type that requires a larger conductor.

SectionElectrodeConductor not required to be larger than
250.66(A)Rod, pipe or plate6 AWG copper or 4 AWG aluminum
250.66(B)Concrete-encased4 AWG copper
250.66(C)Ground ringThe conductor used for the ground ring
Electrode-specific sizing limits from the NFPA fact sheet.
Grounding electrode conductor sizes by electrodeA 3/0 copper service with a 4 AWG copper conductor to a water pipe and concrete-encased electrode, a ground ring connection up to the ring size, and a 6 AWG copper connection to a rod.GEC and jumper sizes for a 3/0 AWG copper serviceService equipment3/0 AWG Cu conductorsWater pipeTable 250.664 AWG CuConcrete-encased250.66(B) limit4 AWG CuGround ringRing at least 2 AWGUp to ring sizeRod250.66(A) limit6 AWG CuIndustrialBasicsindustrialbasics.com
Figure 1: Based on the NFPA Article 250 exhibit. The NEC does not set a mandatory connection order.

Routing matters. If a GEC runs from the service to a ground rod first and then continues to a water pipe, the section to the rod must be sized from Table 250.66 as if it ran directly to the water pipe. The 6 AWG limit no longer applies because the conductor extends to an electrode that needs a larger size. Bonding jumpers between electrodes are sized through 250.53(C), which refers back to 250.66.

Worked Examples

Example 1: Single 3/0 copper service

The largest ungrounded conductor is 3/0 AWG copper, which falls in the 2/0 or 3/0 row. The GEC is 4 AWG copper or 2 AWG aluminum. A jumper that serves only a ground rod is not required to be larger than 6 AWG copper.

Example 2: Parallel 500 kcmil copper

An 800 A, three-phase service uses two 500 kcmil copper conductors per phase.

2 × 500 kcmil = 1000 kcmil

1000 kcmil falls in the Over 600 through 1100 row, so the GEC is 2/0 AWG copper.

Equivalent area for parallel conductorsTwo 500 kcmil copper conductors per phase add to 1000 kcmil, which falls in the over 600 through 1100 row and requires a 2/0 AWG copper grounding electrode conductor.Parallel sets: add the areas, then read the table500500+2 sets, copper1000 kcmilEquivalent area2/0 AWG copper GECOver 600 through 1100IndustrialBasicsindustrialbasics.com
Figure 2: The NFPA parallel conductor example for an 800 A service.

Example 3: Parallel aluminum

Four 250 kcmil aluminum conductors per phase equal 1000 kcmil aluminum. That is in the Over 900 through 1750 row, so the GEC is 2/0 AWG copper or 4/0 AWG aluminum.

Service conductorsEquivalent areaTable rowGEC
3/0 AWG Cu3/0 AWG2/0 or 3/04 AWG Cu or 2 AWG Al
750 kcmil Al750 kcmilOver 500 through 9001/0 AWG Cu or 3/0 AWG Al
2 × 500 kcmil Cu1000 kcmilOver 600 through 11002/0 AWG Cu or 4/0 AWG Al
4 × 250 kcmil Al1000 kcmilOver 900 through 17502/0 AWG Cu or 4/0 AWG Al
Example results from Table 250.66.

Table 250.66 vs Other Article 250 Tables

TableSizesBased on
250.66Grounding electrode conductorLargest ungrounded conductor or equivalent area
250.102(C)(1)Grounded conductor, main, system and supply-side bonding jumpersLargest ungrounded conductor or equivalent area
250.122Equipment grounding conductorOvercurrent device rating
Use the table that matches the conductor you are sizing.

The tables look similar but are not interchangeable. NFPA specifically warns that Table 250.102(C)(1) is not for sizing grounding electrode conductors. For the wider system context, see our guide to types of earthing systems. Phase conductor capacity is covered separately in our AWG wire ampacity chart.

Common Sizing Mistakes

MistakeWhy it is wrongCorrect approach
Sizing from the breakerTable 250.66 uses conductor sizeUse the largest ungrounded conductor
Ignoring parallel setsThe table uses equivalent areaAdd the corresponding conductors
Using 6 AWG to every electrodeThe limit applies only to certain connectionsCheck where the conductor continues
Reading the wrong material columnCopper and aluminum rows differMatch both conductor materials
Using Table 250.102(C)(1)It sizes bonding jumpers and grounded conductorsUse Table 250.66 for the GEC
Frequent errors when sizing a GEC.
Safety note: Grounding conductors can carry dangerous voltage during a fault, and service conductors may remain live with the main switched off. Work must be done by a qualified person following the lockout/tagout procedure. This guide is educational and does not replace the NEC or your local authority.

If your service uses parallel sets or has no service-entrance conductors, see our focused guide to Table 250.66 Note 1 and Note 2.

Table 250.66 is one of three sizing tables in the grounding article; our NEC Article 250 guide maps which table sizes each grounding and bonding conductor.

Frequently Asked Questions

What is NEC Table 250.66 used for?

It sizes the grounding electrode conductor for AC systems at a service, at a building supplied by a feeder or branch circuit, and at a separately derived system.

What size GEC is required for 3/0 copper service conductors?

Table 250.66 requires 4 AWG copper or 2 AWG aluminum or copper-clad aluminum. A connection only to a rod, pipe or plate electrode may be limited to 6 AWG copper or 4 AWG aluminum.

Is a 6 AWG copper GEC enough for a ground rod?

Yes, when that conductor connects to a rod, pipe or plate electrode and does not extend on to another electrode type that requires a larger conductor.

What size GEC goes to a concrete-encased electrode?

It is not required to be larger than 4 AWG copper, provided the conductor does not extend on to another electrode type that requires a larger size.

How do you size a GEC for parallel conductors?

Add the areas of the corresponding conductors in each set, then use that total in the table. Two 500 kcmil copper conductors per phase equal 1000 kcmil, which requires a 2/0 AWG copper GEC.

What is the largest GEC required by Table 250.66?

The largest size in the table is 3/0 AWG copper or 250 kcmil aluminum or copper-clad aluminum. It applies above 1100 kcmil copper or 1750 kcmil aluminum.

What is the difference between Table 250.66 and Table 250.122?

Table 250.66 sizes the grounding electrode conductor from the largest ungrounded conductor. Table 250.122 sizes the equipment grounding conductor from the overcurrent device rating.

Can I install a GEC larger than the table requires?

Yes. NFPA notes that using bonding jumpers or grounding electrode conductors larger than those required by 250.66 is not prohibited.

Sources and Further Reading

About the author

editor

Leave a Comment