Dry Contact Relay: Form A, B and C vs Wet Contacts

By editor Updated 6 min read
Relay contact symbols for Form A normally open, Form B normally closed and Form C changeover

A dry contact relay provides a voltage-free switch: it opens or closes a path, while the device reading it supplies the voltage. A wet contact already carries voltage from its own device. Form A, B and C describe something different: normally open, normally closed and changeover contacts. Any of these forms can be dry or wet, depending on how the relay is wired.

TermMeaningAlso called
Dry contactNo voltage from the device with the contactVolt-free, potential-free
Wet contactCarries voltage from its own devicePowered contact
Form ANormally openSPST-NO, make
Form BNormally closedSPST-NC, break
Form CCommon switches between NC and NOSPDT, changeover
Contact terms at a glance.
Safety first: Never assume a relay contact is voltage-free. Isolate the circuit, check the wiring diagram and prove it dead using your lockout/tagout procedure. A “dry” contact may be switching a live circuit supplied from elsewhere.
Volt-free
Dry contact
A / B / C
Contact forms
11-12-14
EN 50005 markings
1 mA at 6 V
TE gold contact minimum

Dry vs Wet Contacts

Dry and wet contact comparisonWith a dry contact, the input supplies the voltage through a voltage-free switch. With a wet contact, the field device sends its own voltage to the input.Who supplies the voltage?Dry contactField deviceInputSupplies VThe reading device supplies voltageWet contactField deviceInput24 V insideSenses voltageDevice sends its own voltageIndustrialBasicsindustrialbasics.com
Figure 1: Dry and wet describe the source of the signal, not the shape of the contact.

The difference is where the voltage comes from. With a dry contact, the reading device, such as a PLC input, supplies the voltage and senses whether the path is closed. With a wet contact, the field device provides the voltage.

FactorDry contactWet contact
Voltage sourceThe connected circuitThe device with the contact
Input type neededInput that supplies wetting voltage, or an external supplyInput that senses voltage
Main wiring riskNo signal if no supply is providedVoltage connected to the wrong input
FlexibilityCan switch a separate circuit within its ratingTied to the device’s supply
Comparing dry and wet contacts.
Reader tip: The same relay can be dry on one product and wet on another. If the manufacturer connects its common terminal to an internal supply, the output is no longer volt-free.

Form A, B and C Contacts

Form A, B and C contactsForm A is normally open, Form B is normally closed, and Form C has a common terminal that changes between normally closed and normally open.Relay contact forms, shown de-energizedForm ASPST-NOCOMNOCloses when energizedForm BSPST-NCCOMNCOpens when energizedForm CSPDT changeoverCOMNONCChanges over when energizedIndustrialBasicsindustrialbasics.com
Figure 2: A contact’s form says nothing about whether it is dry or wet.

Contact drawings show the relay de-energized. Form C is the most flexible because it offers both a normally open and a normally closed path from one common terminal.

FormUSAEUEN 50005 terminals
ASPST-NONO11 (common), 14 (NO)
BSPST-NCNC11 (common), 12 (NC)
CSPDTCO11 (common), 12 (NC), 14 (NO)
Designations and terminal markings from Finder’s technical guide. American products may number terminals differently.

The coil terminals are normally marked A1 and A2. For a fail-safe alarm, a relay is often kept energized while healthy, so a power loss also causes an alarm. To see how relays fit into a control panel, read our comparison of contactors and relays.

Wetting Current and Minimum Load

Relay contacts can develop a thin film of oxide or contamination. A contact needs a certain minimum voltage and current to break through it. If the signal is too small, a closed contact may read as open or become intermittent. This is why a big power relay can be unreliable on a tiny PLC input.

Contact materialTE recommended minimum load
Gold or gold plated1 mA at 6 V DC
AgNi10 mA at 12 V DC
AgCdO or AgSnO2100 mA at 12 V DC
From the TE Industrial Relays Quick Reference Guide. Other makers publish different values.

Finder suggests no less than 50 mW, 5 V / 2 mA for gold contact variants. These figures differ by manufacturer and product, so always use the datasheet for your relay.

Worked example: relay on a PLC input

Finder explains that a minimum of 300 mW, 5 V / 5 mA means all three values must be met. A 24 V input drawing 5 mA is only:

P = 24 V × 5 mA = 120 mW

The voltage and current pass, but 120 mW is below 300 mW, so this relay is not suitable. At 24 V it would need at least 12.5 mA. A gold-contact relay with a 50 mW, 5 V / 2 mA minimum would be suitable for the same input.

Relay Minimum Load Checker
IndustrialBasics check. Use the minimum load from the datasheet for your exact relay.

Wiring Mistakes to Avoid

MistakeResultFix
Connecting voltage to a dry-contact inputInput damageCheck the input type first
Expecting voltage from a dry contactNo signalProvide a supply through the contact
Using a power relay for a tiny signalIntermittent readingUse a suitable low-level contact
Using NO and NC backwardsInverted logicCheck the de-energized state
Switching a coil with no suppressionContact wear and noiseAdd suitable suppression
Common contact wiring errors.

If the relay is driven from a PLC output, see our guide to the interposing relay. For input planning, see how to select a PLC. If you need logic as well as switching, compare programmable relays.

Safety note: This guide is educational. Follow the relay and control equipment datasheets and the applicable electrical code.

For NO vs NC symbols, ladder logic and why stop buttons are normally closed, see normally open vs normally closed.

Frequently Asked Questions

What is a dry contact relay?

It is a relay output with voltage-free contacts. The relay only opens or closes the path, and the connected circuit supplies the voltage.

What is the difference between dry and wet contacts?

A dry contact has no voltage of its own. A wet contact already carries voltage from the device that owns it.

What is a Form C relay contact?

Form C is SPDT changeover. A common terminal connects to the normally closed terminal when de-energized and to the normally open terminal when energized.

What is the difference between Form A and Form B?

Form A is normally open and closes when energized. Form B is normally closed and opens when energized.

What is wetting current?

It is the minimum current a contact needs to switch reliably by breaking through surface oxide or contamination.

Why does a closed relay contact read open?

At very low current, a contaminated contact may not conduct reliably. Check the relay’s minimum load and consider a gold-contact type for signal circuits.

Can I connect 24 V to a dry contact input?

Usually not. An input designed for a dry contact often supplies its own wetting voltage, so adding external voltage can damage it. Check the manual.

Should I use gold contacts for PLC inputs?

For low-level signals, gold contacts are often a better fit because their minimum load is lower. Confirm the value in the datasheet.

Sources and Further Reading

About the author

editor

Leave a Comment