Interposing Relay: Wiring and Protection for PLC Outputs

By editor Updated 7 min read
PLC output driving a small interposing relay whose contact switches a 120 volt AC contactor

An interposing relay is a small relay placed between a PLC output and a field load, so the PLC switches only the relay coil while the relay contact switches the load. It is used when the load needs more current or a different voltage than the output card can provide, or when the field circuit should be kept separate from the PLC. For a DC coil, wire the PLC output across the coil, add suppression, and connect the load through the relay’s common and normally open contacts.

ReasonWhat the relay doesExample
CurrentLets a small coil control a larger contactPLC output switching a heavier load
VoltageShifts between control and field voltage24 V DC output controlling a 120 V AC coil
SeparationKeeps control and load wiring apart24 V DC wiring segregated from AC
ProtectionKeeps the load’s transient off the outputLarge DC contactor coil
SpeedCan shorten DC contactor opening timeAbout 45 ms vs over 100 ms in DigiKey’s test
Why engineers add an interposing relay.
Safety first: Isolate all control and field supplies before wiring. A relay can have a different voltage on its contacts than on its coil, so prove both circuits dead using your lockout/tagout procedure.
24 V DC
Typical PLC control side
100 mA
Example 2.4 W coil
45 ms
Measured with relay
100+ ms
Without relay

How an Interposing Relay Works

Interposing relay between PLC and loadA PLC output energizes the small relay coil, and the relay contact switches a separate field load such as a contactor or solenoid.Where an interposing relay sitsPLC output24 V DC, low currentInterposing relaySmall coil, isolated contactField loadContactor or solenoidCoilContactControl sideLoad sideIndustrialBasicsindustrialbasics.com
Figure 1: The PLC only drives the small relay coil. The contact handles the field circuit.

The PLC output sees only the relay coil. When the output turns on, the coil pulls in and the normally open contact closes the separate load circuit. Because the coil and contact are electrically separate, they can operate at different voltages. For the basics of each device, see our comparison of contactors and relays.

When you need one

  • The load current is close to or above the output point rating.
  • The field device uses a different voltage from the output card.
  • The load is a large inductive coil.
  • Field wiring should stay separate from the PLC cabinet section.
  • A failed field device should not damage an expensive output card.

If you are still choosing hardware, our guide on how to select a PLC covers output types and I/O planning.

Protecting the Output: Flyback Suppression

A relay coil is an inductor. When a DC output turns off, the collapsing magnetic field tries to keep current flowing and creates a voltage spike. Without protection, that energy can damage the output transistor or disturb nearby electronics.

Effect of a flyback diodeWithout a diode, the collapsing coil field drives a voltage spike toward the PLC output. With a diode across the coil, current circulates through the diode and coil until it decays.What the flyback diode doesWithout a diodePLC outputNow offCoilVoltage spike hits the outputWith a diodePLC outputNow offCoilCoil current circulates safelyIndustrialBasicsindustrialbasics.com
Figure 2: A diode protects the output, but the slower current decay also delays release.

Place the diode directly across the relay coil, as close to the relay as possible, with reverse polarity to the supply. Many relay bases and modules include suppression, so check before adding another device. For a 24 V DC coil, Altium suggests a diode rated at 50 V or higher, with forward current above the coil current.

SuppressionClamp levelRelease speed
Diode onlySupply + diode dropSlowest
Diode + series resistorSupply + diode drop + I × RModerate
Diode + series ZenerSupply + Zener voltageFaster
TVS diodeDepends on the deviceFastest
Coil suppression options, from Altium. Faster release means a higher transient at the output.
Reader tip: Check the output card’s voltage rating before using a Zener or TVS. A faster release comes from allowing a higher voltage across the switching device.

How to Wire It to a PLC Output

Relay coil wiring for sourcing and sinking outputsWith a sourcing output, the PLC output connects to A1 and A2 connects to 0 volts. With a sinking output, plus 24 volts connects to A1 and A2 connects to the PLC output. In both, the diode cathode is on the positive side of the coil.Wiring a DC relay coil to a PLC outputSourcing outputPLC outputCoilA1 (+)A2 (−)0 VDiodeSinking output+24 VCoilA1 (+)A2 (−)PLC outputDiodeIndustrialBasicsindustrialbasics.com
Figure 3: The diode is reverse-biased in normal operation. Confirm terminal names and polarity on your relay.
ConnectionSourcing outputSinking output
Coil A1 (+)PLC output+24 V DC
Coil A2 (−)0 V DCPLC output
Diode cathodeA1A1
Diode anodeA2A2
Relay COM and NOIn series with the loadIn series with the load
DC coil wiring. Terminal labels vary, so check the relay and base datasheet.
  1. Confirm the output type and the relay coil voltage.
  2. Wire the coil to the output and its correct return.
  3. Fit or confirm coil suppression.
  4. Wire the load circuit through COM and NO, with its own overcurrent protection.
  5. Keep control and field conductors segregated.
  6. Force the output only when it is safe, then confirm that the relay and load operate correctly.

Worked Example: Checking the Coil Current

DigiKey’s test used a Crouzet PLC with a 500 mA solid-state output and a Schneider contactor with a 2.4 W, 24 V DC coil.

I = P ÷ V = 2.4 W ÷ 24 V = 0.1 A = 100 mA

At 100 mA, the coil is well within the 500 mA output limit, so current alone does not require a relay. The problem was speed. With a simple flyback diode, the contactor took over 100 ms to open, and slow opening extends the arc.

ConfigurationRelay releaseContactor openingTotal
PLC drives contactor directlyNot usedOver 100 msOver 100 ms
PLC drives interposing relayAbout 8 msAbout 37 ms laterAbout 45 ms
Results from DigiKey’s bench test. Timing varies with the coil and suppression.

The interposing relay helped because the contactor’s own suppression could clamp at about 48 V DC once it was no longer limited by the diode at the PLC output.

Checks and Troubleshooting

SymptomLikely causeWhat to check
Relay never pulls inNo output, wrong polarity or open coilOutput LED, voltage across A1 and A2
Relay stays on after output turns offLeakage or a shorted outputOff-state leakage and relay drop-out current
PLC resets when relay turns offFlyback noiseCoil suppression and wiring routes
Output point has failedUnsuppressed coil or overloadCoil current and suppression
Slow load releaseDiode-only suppressionSuppression type
Contacts wear quicklyInductive or DC load arcingContact rating and contact protection
Common interposing relay faults.

Leakage matters with solid-state outputs. Rockwell’s 1769-OB16, for example, lists a maximum off-state leakage of 1.0 mA. Compare your module’s value with the relay’s drop-out current before choosing a very small coil.

Contact ratings also depend on the load. Weschler’s example relay is rated 10 A at 250 V AC resistive, but only 6 A at 30 V DC resistive, and DC contacts wear faster because there is no current zero crossing. Check the inductive rating for your load. If the load is a motor, see our guide to motor starters.

Safety note: A standard interposing relay does not make a safety function safe. Use a design and devices rated for the hazard level. See our guides to NFPA 79 and safety relays. This guide is educational and does not replace manufacturer data or applicable standards.

For a deeper look at coil suppression choices, see relay snubber diodes: diode vs zener vs TVS vs RC.

Frequently Asked Questions

What is an interposing relay?

It is a relay placed between a control device, usually a PLC output, and a field load. The PLC energizes its small coil, and the relay contact switches the load.

Why use an interposing relay with a PLC?

It can increase switching capacity, allow a 24 V DC output to control a 120 V or 277 V AC coil, separate control and field wiring, and protect the PLC output from the load.

How do you wire an interposing relay to a PLC output?

Connect the PLC output and its return across the relay coil, then wire the load circuit through the relay’s common and normally open contacts.

Does an interposing relay need a flyback diode?

A DC coil needs suppression unless it is built in. Place the diode directly across the coil, with its cathode on the positive side.

Which way does a flyback diode go on a relay coil?

It goes in reverse polarity to the supply: cathode to the positive coil terminal and anode to the negative terminal.

Does a flyback diode slow relay release?

Yes. Coil current decays more slowly through a simple diode. A diode with a Zener or a TVS device can release faster, but allows a higher transient voltage.

Can leakage current keep a relay energized?

It can with solid-state outputs and small loads. Compare the module’s off-state leakage with the relay’s drop-out current from its datasheet.

Can I use an interposing relay for an emergency stop?

Not as a standard control relay. Safety functions need a design and devices rated for the hazard level.