Power Quality Problems in Factories: 10 Common Issues, Causes and Solutions

By editor Updated 25 min read
Waveform showing a voltage sag and a transient spike, with the title Power Quality Problems in Factories.
Quick answer

Power quality problems are faults in the voltage, current or frequency supplied to your equipment. They make machines trip, reset, overheat or wear out early. In factories, the 10 most common are voltage sags, voltage swells, interruptions, transients, harmonics, interharmonics and noise, voltage unbalance, flicker, over and undervoltage, and frequency variation.

How to check: log the supply with a Class A power quality analyser (IEC 61000-4-30) for at least one full week of production, at the incomer and at the problem machines.

How to fix: match the cure to the measured problem. For example, ride-through or a UPS for sags, surge protective devices for transients, filters and reactors for harmonics, and load balancing for unbalance.

Most factory electrical faults that nobody can explain turn out to be power quality problems. A drive trips for no clear reason. A PLC resets overnight. A transformer runs hotter than its load suggests. This guide explains each of the 10 problems in plain English, shows what causes it, what it does to your equipment, how to detect it and which fix works.

It also covers how to measure power quality, how it differs from power factor, and which standards apply. UK rules are called out where they differ from IEEE or IEC practice.

€150 bn
yearly losses to the industrial sectors in the 2008 European Power Quality Survey (an extrapolated estimate)
68%
of recorded disturbance events were voltage sags in a 1990 factory automation study
216.2–253 V
UK statutory range for a 230 V low voltage supply
1% or less
voltage unbalance NEMA expects at three-phase motor terminals

What Is Power Quality?

Power quality is how closely the voltage, current and frequency at a point in your plant match what your equipment needs to work properly. The IEC definition says much the same: it compares the characteristics of voltage, current and frequency at a given point with agreed technical reference values.

Good power quality means the supply has these five features:

  • Stable voltage that stays close to its declared value.
  • Constant frequency (50 Hz in the UK).
  • Clean waveforms that look like smooth sine waves.
  • A balanced three-phase supply with equal voltages on each phase.
  • Continuity, meaning no unwanted interruptions.

IEC 61000-4-30 lists the parameters you can measure: power frequency, voltage magnitude, flicker, dips and swells, interruptions, transients, unbalance, harmonics and interharmonics, and rapid voltage changes.

How IEEE 1159 classifies power quality problems

IEEE 1159 sorts disturbances by how long they last and how big they are. Voltages are written in per unit (pu), where 1.0 pu is the normal voltage. So 0.9 pu means 90% of nominal.

CategoryTypical durationTypical magnitudeFactory examples
TransientsNanoseconds to millisecondsCan reach several times nominalLightning, capacitor switching
Short-duration variations: sag0.5 cycle to 1 minute0.1–0.9 puMotor starting, grid faults
Short-duration variations: swell0.5 cycle to 1 minute1.1–1.8 puLarge load switched off
Short-duration variations: interruptionUp to 1 minuteBelow 0.1 puBreaker trip, utility fault
Long-duration variationsMore than 1 minuteUnder 0.9 pu or over 1.1 pu; sustained interruption at 0 puWrong transformer tap, long outage
Voltage imbalanceSteady statePercentage difference between phasesUneven single-phase loads
Waveform distortionSteady stateHarmonics, interharmonics, notching, noiseDrives, rectifiers, welders
Voltage fluctuations (flicker)IntermittentSmall, repeated voltage changesArc furnaces, presses
Power frequency variationsShort termFrequency moves from nominalGenerators, weak grids
Values are taken from public summaries of the IEEE 1159 tables. Check the current edition before quoting exact boundaries.
Six waveforms: normal supply, voltage sag, voltage swell, interruption, transient and harmonic distortionNormal supplyClean 50 Hz sine waveVoltage sagDrops to 0.1–0.9 puVoltage swellRises above 1.1 puInterruptionFalls below 0.1 puTransientBrief, sharp spikeHarmonic distortionWave shape no longer a sine
The six waveform shapes you will meet most often. Amber marks the disturbance; the dashed grey line shows the normal wave.

Why Are Power Quality Problems Increasing in Modern Industries?

The supply has not necessarily got worse. Modern plants are simply less tolerant of it, and they also create more disturbance themselves.

  • Sensitive electronics. PLCs, robots, sensors and servo drives react to disturbances that old relay panels ignored.
  • More VFDs. Variable frequency drives save energy but draw current in pulses and can trip on a short sag.
  • Nonlinear loads. Rectifiers, LED drivers, switch-mode power supplies and welders all distort the current.
  • Renewables and on-site generation. Inverters add harmonics, and weak or islanded supplies drift in voltage and frequency.
  • Continuous production. A one-second dip now costs a full restart, not a flicker of the lights.
  • Reliability expectations. Equipment is run closer to its limits, so small stresses add up faster.

Sensitivity is measurable. A classic Detroit Edison study of an automated plant found that voltage sags were the most common disturbance, at 68% of recorded events. The most sensitive control components malfunctioned when voltage dropped below 80–86% of rated. The plant as a whole was disrupted by a sag below 87% of nominal lasting more than 8.3 ms (Wagner et al., IEEE Transactions on Industry Applications, 1990). That is a sag most people would never notice.

Share of disturbance events that were voltage sags in a 1990 factory automation study68%Voltage sags: 68% of recorded eventsAll other disturbances: 32%One automated plant, one monitoring study (1990).Not an industry average.
Disturbance events recorded at one representative automated plant. Source: Wagner, Andreshak and Staniak, IEEE Trans. Industry Applications, 1990.

The cost side is harder to pin down. The Leonardo Power Quality Initiative surveyed 62 sites in eight European countries in 2005–2006. It estimated that the industrial sectors it covered lose more than €150 billion a year because their electrical installations are not reliable or resilient enough. Treat that as a dated, extrapolated estimate, not a precise figure for your site.

What Are the 10 Most Common Power Quality Problems?

Each problem below follows the same pattern: what it is, what causes it, what it does, how to detect it and how to fix it. Fixes are families of solutions. The right choice always depends on measured data from your own plant.

1. Voltage sags (voltage dips)

A voltage sag is a short drop in RMS voltage to between 10% and 90% of nominal, lasting from half a cycle to one minute. It is the most common problem in factories and the one that stops production most often.

  • Causes: faults on the utility network (lightning, storms, equipment failure), starting large motors, switching big loads and energising transformers.
  • Industrial sources: direct-on-line motor starts, compressors, crushers, heavy presses and arc furnaces.
  • Effects: VFDs trip on DC-bus undervoltage, motors stall, PLCs reset and contactors drop out, so the line stops. If you are unsure which starter you have, our guide to the types of motor starters shows how much current each one draws at start-up. Dropout is a common failure for coil-operated devices, and the difference is explained in contactor vs relay.
  • Detection: an analyser that logs RMS voltage events with magnitude, duration and residual voltage. Compare the results with your equipment’s ride-through curve (ITIC/CBEMA and SEMI F47 are common references).
  • Solutions: drive ride-through settings, a UPS or DC buffer for controls, a Dynamic Voltage Restorer (DVR) for a critical process, and soft starting to cut the sags you cause yourself. The trade-offs between the two main starting options are covered in VFD vs soft starter.
  • Watch out: a UPS is not automatically a sag fix for every load. Sizing, transfer time and battery condition all matter. A DVR needs enough stored energy for the depth and length of sag you expect.

2. Voltage swells

A voltage swell is the opposite of a sag: a short rise above 110% of nominal, lasting up to one minute.

  • Causes: a large load switching off suddenly, capacitor bank switching, poor voltage regulation, and earth faults that lift the healthy phases on some system types.
  • Effects: stress on insulation, power supply failures, drive overvoltage trips and capacitor overheating. Repeated swells age insulation quietly, so an insulation resistance test with a megger is a sensible check on equipment that has been exposed.
  • Detection: RMS logging that flags anything above 1.1 pu, with event time and duration.
  • Solutions: correct transformer tap settings, voltage regulation, controlled capacitor switching, surge protection for the peaks, and a UPS or DVR for critical loads.
  • Watch out: check the input voltage tolerance of any UPS before relying on it for swells.

3. Short and sustained power interruptions

An interruption is a complete loss of voltage, below 10% of nominal. A momentary interruption lasts up to about three seconds. A temporary one lasts three seconds to one minute. A sustained interruption lasts longer than one minute.

  • Causes: utility faults, circuit breaker trips, internal short circuits and damaged lines.
  • Effects: production stops, controls reboot, batch data is lost and uncoordinated restarts can be unsafe.
  • Detection: an event log with start time, end time, depth and affected phases.
  • Solutions: a UPS for critical automation, backup generators with an Automatic Transfer Switch (ATS), and dual feeders where the site justifies it. Good protection coordination also matters, because a fault on one feeder should not black out the whole plant.
  • Watch out: a generator does not remove the interruption. Start-up and transfer time decide what the plant actually experiences.

4. Electrical transients and power surges

A transient is a very fast, short disturbance. Impulsive transients are single spikes, usually from lightning. Oscillatory transients ring up and down, usually after capacitor or inductive switching.

  • Causes: lightning, capacitor switching, inductive load switching and breaker operations. Our comparison of a lightning arrester vs surge arrester explains where each device sits.
  • Effects: insulation breakdown, damaged semiconductors in drives and PLCs, corrupted data and premature ageing.
  • Detection: high-speed capture. Ordinary logging windows miss fast spikes, and transient capture is optional on some analysers, so check before you buy or hire.
  • Solutions: coordinated Surge Protective Devices (SPDs) at each distribution level, RC snubbers across inductive loads, sound bonding and separation of sensitive circuits from switching sources. See surge protection device types for Type 1, 2 and 3 selection. In the UK, BS 7671 covers protection against transient overvoltages.
  • Watch out: SPDs have energy limits and wear out. They do not fix poor earthing or all conducted noise.

5. Harmonic distortion

Harmonics are currents or voltages at whole-number multiples of 50 Hz. The 5th harmonic is 250 Hz and the 7th is 350 Hz. Nonlinear loads draw current in pulses, and those current harmonics flow through the supply impedance and distort the voltage that other equipment sees.

  • Industrial sources: VFDs, rectifiers, welding machines, switch-mode power supplies, UPS systems and induction furnaces.
  • Effects: extra heating in transformers and cables, overloaded neutrals (triplen harmonics add up in the neutral), nuisance breaker trips, motor vibration and failed capacitors. To see why transformer size and cooling matter here, read power vs distribution transformer.
  • Measuring it: Total Harmonic Distortion (THD) is the harmonic content as a percentage of the fundamental. Record voltage THD, current THD and the individual orders. IEC 61000-4-7 defines the method.
  • Solutions: line reactors, passive filters, active harmonic filters, multi-pulse rectifiers and low-harmonic drives.
  • Limits: IEEE 519 sets distortion limits at the Point of Common Coupling (PCC), not at every panel inside the plant. In the UK, connection of harmonic sources to the network is assessed under ENA Engineering Recommendation G5/5.
Bar chart comparing theoretical harmonic currents of 6-pulse and 12-pulse rectifiers0%5%10%15%20%25%Harmonic current (% of fundamental)Harmonic order20%0%5th (250 Hz)14.3%0%7th (350 Hz)9.1%9.1%11th (550 Hz)7.7%7.7%13th (650 Hz)5.9%0%17th (850 Hz)5.3%0%19th (950 Hz)Ideal 6-pulse driveIdeal 12-pulse drive
Theoretical harmonic currents for an ideal rectifier (each order is roughly 1 divided by its number). Real drives differ, and a small residual of the cancelled orders remains in practice. A 12-pulse arrangement removes the 5th and 7th, which is why it is a common low-harmonic choice.

6. Interharmonics, voltage notching and electrical noise

These three are related but different:

  • Interharmonics are frequencies that sit between the whole-number harmonics. Cyclic loads, cycloconverters and some converters create them.
  • Voltage notching is a repeating dip in the waveform each time a thyristor converter switches current from one phase to the next.
  • Electrical noise is high-frequency interference that couples in through cables, switching edges or radiated fields.
  • Effects: faulty zero-crossing detection, corrupted sensor signals, communication errors, erratic PLC behaviour and flicker in some cases.
  • Detection: spectrum analysis beyond ordinary harmonics, plus waveform capture with enough bandwidth to see the notches.
  • Solutions: line reactors, filters, isolation transformers, shielded cables and keeping power and signal cables apart.
  • Watch out: noise is not a single standard category. Good bonding helps with high-frequency interference, but it is no cure for harmonics or sags. If you are unsure how your site is earthed, start with types of earthing systems, and see earthing vs grounding for the terminology.

7. Voltage unbalance

Voltage unbalance means the three phase voltages are not equal. NEMA defines it as 100 × (largest deviation from the average voltage ÷ the average voltage). For example, with line voltages of 396 V, 400 V and 410 V the average is 402 V and the largest deviation is 8 V, so unbalance is about 2%.

  • Causes: uneven single-phase loads, loose or high-resistance connections, open phases and unequal phase loading.
  • Effects: a small voltage unbalance causes a much larger current unbalance in induction motors. The result is rotor heating, torque ripple and shortened insulation life. Read motor failure causes for how heat drives most winding failures.
  • Detection: phase voltage and current readings on an analyser, which can calculate unbalance directly. NEMA expects 1% or less at motor terminals and does not recommend running above 5%.
  • Solutions: spread single-phase loads evenly, repair connections and fit phase-monitoring relays. Many motor overload devices also react to phase loss, as described in thermal overload relay. Voltage-monitoring relays use ANSI device numbers such as 47, listed in ANSI device numbers.
Bar chart showing approximate extra motor temperature rise at 1 to 5 percent voltage unbalance0%10%20%30%40%50%Approx. extra temperature rise (%)Voltage unbalance at motor terminals2%1%8%2%18%3%32%4%50%5%
Rule of thumb widely quoted from NEMA guidance: extra temperature rise ≈ 2 × (unbalance %)². Real motors vary, so use it to see the trend, not to predict one machine.

8. Voltage fluctuations and flicker

Voltage fluctuations are repeated changes in voltage. Flicker is what people see when those changes make lights vary in brightness. Fluctuations come first; flicker is the visible result.

  • Causes: electric arc furnaces, welders, crushers, heavy presses and any large load that cycles on and off.
  • Effects: visible lighting changes, operator fatigue and disturbance to sensitive controls.
  • Detection: a flickermeter per IEC 61000-4-15, which reports short-term (Pst, 10 minutes) and long-term (Plt, 2 hours) severity.
  • Solutions: Static Var Compensators (SVC), STATCOM systems, a dedicated feeder for the fluctuating load and load scheduling.
  • Watch out: performance depends on supply strength and the load’s behaviour, so get a site-specific study before buying compensation equipment.

9. Overvoltage and undervoltage

These are long-duration voltage deviations that last more than a minute. In IEEE terms, undervoltage is roughly 80–90% of nominal and overvoltage roughly 110–120%. In the UK, the statutory limits are tighter than most people expect.

UK statutory voltage band for a 230 V low voltage supply: 216.2 V to 253 V200 V210 V220 V230 V240 V250 V260 V270 V216.2 V (−6%)230 V declared253 V (+10%)Permitted supply rangeDeclared 230 V, 50 Hz low voltage supply under the Electricity Safety, Quality and Continuity Regulations 2002
UK low voltage supply limits: +10% and −6% around 230 V. Source: Electricity Safety, Quality and Continuity Regulations 2002, regulation 27.
  • Causes: wrong transformer tap settings, poor regulation, heavy load changes, generator settings and voltage drop inside the plant. An IET report for Ofgem found evidence that up to 5% of LV customers see sustained voltage above 253 V.
  • Effects: undervoltage raises motor current and can drop out contactors. Overvoltage stresses insulation and electronics.
  • Detection: RMS trends with minimum, maximum and average values over days, not minutes.
  • Solutions: adjust transformer taps, use Automatic Voltage Regulators (AVRs) on generators, fit voltage monitoring relays and reduce internal voltage drop. Undervoltage and overvoltage relays are ANSI 27 and 59; see types of protection relays.
  • Watch out: do not blame the utility first. Cable voltage drop and transformer settings inside the plant are often the real cause.

10. Power frequency variations

Frequency variation means the supply drifts away from 50 Hz. On the UK grid this is rare and small. The regulations allow up to 1% either side of the declared frequency, which is 49.5–50.5 Hz. EN 50160 uses a wider 100%-of-the-time band of +4% to −6%.

  • Causes: a mismatch between generation and load on the grid, weak networks, and on-site generators or islanded microgrids.
  • Effects: speed changes in motors, timing errors, and stress on synchronous machines and on-site generation.
  • Detection: frequency trend logging on a PQ meter or digital relay.
  • Solutions: generator governor control, automatic load shedding, correct synchronisation and frequency protection.
  • Watch out: for a grid-connected factory this is a minor risk. It matters mainly for standby generators and islanded sites.

What Are the Main Causes of Power Quality Problems in Factories?

Problems come from three places: your own loads, your own electrical design and the utility network. Most plants have a mix.

CauseProblems it tends to create
Nonlinear loads (VFDs, rectifiers, welders)Harmonics, notching, noise
Large motor startingVoltage sags, flicker
Poor electrical design or undersized cablesUndervoltage, voltage drop, sags that spread
Overloaded transformers and distributionUndervoltage, heating, harmonic losses
Capacitor banks installed without harmonic checksResonance, harmonic amplification, swells and transients when switching
Utility supply disturbancesSags, interruptions, swells
Uneven single-phase load distributionVoltage unbalance
Faulty or loose connectionsUnbalance, local heating, intermittent faults
Switching operations and lightningTransients and surges
A single plant often has several of these at once, which is why measurement comes before purchasing.

What Are the Effects of Poor Power Quality on Industrial Equipment?

Effects on electric motors

Unbalance and harmonics add heat. Undervoltage raises current. Sags can stall a motor. Together they shorten winding and bearing life.

Effects on transformers

Harmonic currents increase core and winding losses, so a transformer can overheat well below its nameplate rating. Cooling matters more as distortion rises, as covered in transformer cooling methods.

Effects on variable frequency drives (VFDs)

Drives are both victims and sources. They trip on sags and swells, and they push harmonics back onto the supply.

Effects on PLCs and automation systems

Brief sags, notches and noise cause resets, lost I/O and corrupted communications. These faults often look random, which makes them hard to trace without logging.

Effects on industrial control systems

Relays, contactors and power supplies drop out or misoperate during sags. Nuisance tripping of breakers can follow harmonics and transients; see types of circuit breakers for how trip units respond.

Effects on electrical cables and capacitors

Harmonics overheat cables and neutral conductors. Capacitors suffer most: they can resonate with the network and fail early.

Effects on production efficiency and equipment life

The pattern is the same everywhere: more stoppages, more scrap, more maintenance and shorter equipment life. Quoted downtime figures vary widely, so measure your own losses before building a business case.

How to Measure and Check Power Quality in Industrial Plants

A power quality audit is a structured survey: you log the supply for a period, review the events and trends, and link them to what went wrong in production. The instrument is a power quality analyser, which records RMS voltage and current, frequency, THD, unbalance, sags, swells, interruptions, flicker and transients.

Step-by-step: how to check whether your power is good

  1. List the symptoms and the times they happened, using production and maintenance logs.
  2. Choose measurement points (see the diagram below).
  3. Connect a Class A analyser. Only a competent person should do this.
  4. Log for at least one week that includes normal production and start-ups. Log longer if events are rare.
  5. Review the event list, RMS trends, THD, unbalance and flicker.
  6. Trace each disturbance to its source (see below).
  7. Apply a fix, then measure again to prove it worked.
Where to place a power quality analyser in a factory: incomer, main distribution board, machine feeders and critical control suppliesUtility supply1Main incomer andmain LV switchboard(usual PCC forstandards)2Drive and motor feeder (VFDs,large motors)3Welder, press or furnace feeder3Control and PLC supply (UPS-backed)4Measure at1 Supply side / PCC2 Main distribution3 Machine feeders4 Critical controlsSimplified single-line view. Real plants have more levels, so repeat points 3 and 4 wherever a problem shows up.
Where to take power quality measurements in a typical factory.

Where and how long to measure

  • Main incomer or PCC: shows what the supply gives you and what you send back.
  • Main distribution board: shows how disturbances spread through the plant.
  • Machine feeders: reveal which load is creating a problem.
  • Critical control supplies: show what your most sensitive equipment actually sees.

One week is the usual minimum because standards such as EN 50160 judge compliance over weekly periods. Choose a week that matches normal production, not a holiday shutdown.

Why use an IEC 61000-4-30 Class A instrument?

IEC 61000-4-30 defines how each parameter must be measured. Class A gives accurate, repeatable results that can be compared between instruments, which matters for compliance checks and disputes with a supplier. Class S is a survey class with lower accuracy and is fine for general troubleshooting. Both aggregate readings over 10-minute intervals.

How to read the report and find the source

  • Start with the event list: time, type, magnitude and duration. Match event times against production stoppages.
  • Check trends for voltage level, unbalance and THD, usually at the 95th percentile.
  • Compare results with the right reference: EN 50160 for supply voltage, IEEE 519 or G5/5 at the PCC for harmonics, and your equipment’s ride-through data.
  • To find the source, compare points. If a sag shows at the incomer and downstream, it came from the supply. If it appears only downstream, it started inside the plant. For harmonics, the point where the most harmonic current flows out of the load shows the source.
Safety first

Connecting analysers and fitting corrective equipment means working near live conductors. Follow the Electricity at Work Regulations 1989 and your site rules. Read about arc flash, electrical safety and PPE and the lockout tagout procedure before you start.

Power Quality Problems and Their Solutions: Quick Reference Table

ProblemMain causeCommon effectDetectionRecommended solution
Voltage sagMotor starting, grid faultsEquipment tripsRMS event logRide-through, UPS, DVR, soft start
Voltage swellLoad reduction, capacitor switchingEquipment damageRMS above 1.1 puVoltage regulation, controlled switching
InterruptionGrid or equipment faultsProduction stopsInterruption logUPS, generator with ATS
TransientsLightning, switchingElectronic damageHigh-speed captureCoordinated SPDs, snubbers, bonding
HarmonicsNonlinear loadsOverheating, nuisance tripsTHD and spectrumActive or passive filters, reactors
Interharmonics and noisePower electronicsControl interferenceSpectrum and waveform captureFiltering, shielding, cable separation
Voltage unbalanceUnequal phase loadsMotor overheatingPhase voltage and currentLoad balancing, phase relays
FlickerRapid load changesLighting fluctuationFlickermeter (Pst, Plt)SVC, STATCOM, dedicated feeder
Over and undervoltagePoor regulation, wrong tapsEquipment stressRMS trendsAVRs, tap adjustment, monitoring relays
Frequency variationGeneration-load imbalanceMotor speed changesFrequency trendGovernor control, load shedding
Quick reference for the 10 power quality problems covered in this guide.

Not sure where to begin? Use the flowchart to go from what you see on the shop floor to the problem and the first measurement to take.

Symptom to solution flowchart for factory power quality problemsWhat you seeLikely problemFirst measurementFix familyDrives trip on DC-bus undervoltagewhen a big motor startsVoltage sagCapture RMS sag at the driveand the incomerSoft start, drive ride-through, UPS or DVRTransformers or cables run hot;capacitor fuses blowHarmonics (possiblyresonance)THD and harmonic spectrum atthe PCC and the loadReactors, filters,detuned capacitor banksLights pulse when a welder or pressrunsFlickerFlicker severity (Pst and Plt)at the supply pointDedicated feeder, SVC orSTATCOMOne motor runs hotter than similarmotorsVoltage unbalancePhase voltages and phasecurrentsBalance loads, repairconnectionsPLCs reset during storms or whenplant switchesTransients or noiseHigh-speed capture; inspectbonding and cable routesCoordinated SPDs,bonding, cable separationPlant voltage is always too low ortoo highUnder or overvoltageRMS trend; transformer tap andloading reviewTap change, regulation,load managementGenerator or islanded supply driftsin speedFrequency variationFrequency trend and event logGovernor settings, loadshedding
Symptom-to-solution guide for common factory power quality problems.

Power Quality Improvement Techniques: Choosing the Right Solution

Active harmonic filters vs passive harmonic filters

A passive filter is a tuned inductor-capacitor circuit that gives one harmonic frequency an easy path. An active harmonic filter (AHF) measures the load current and injects an equal and opposite current to cancel the harmonics.

FeaturePassive filterActive harmonic filter
How it worksTuned LC circuit at chosen ordersInjects cancelling current in real time
Harmonics coveredSpecific orders (for example 5th, 7th)Broad range, adapts as load changes
Power factorProvides some reactive powerCan correct some, but not its main job
Resonance riskYes, if network impedance changesMuch lower
CostLowerHigher
Best forSteady, predictable loadsVariable loads and mixed harmonic sources
Choose by load behaviour and budget, after measuring the actual harmonic spectrum.

Dynamic Voltage Restorers (DVR) vs UPS systems

A UPS supplies a protected load from stored energy, usually batteries. A DVR sits in series and injects the missing voltage during a sag, so it protects a whole process rather than one rack.

FeatureUPSDVR
ConnectionIn line with the protected loadSeries injection transformer
Protects againstSags, swells, interruptionsSags and some swells
Typical useControls, IT, small critical loadsWhole production lines or critical process
LimitsBattery runtime, bypass and sizingCannot cover long outages or deep, long sags beyond its storage
The UPS covers outages; the DVR is aimed at sags.

Shunt compensation vs series compensation

In industrial power quality, shunt devices connect in parallel with the load. Capacitor banks, filters and STATCOMs are examples. Series devices connect in line with the supply, and the DVR is the usual example. In transmission, “series compensation” can instead mean series capacitors in a line, so check the context.

FeatureShunt compensationSeries compensation
ConnectionParallelIn series with the supply
Mainly correctsReactive power, harmonic current, voltage supportLoad voltage during sags
ExamplesCapacitor banks, passive and active filters, STATCOMDVR, series voltage restorer
Typical usePower factor, harmonics, flickerProtecting a sensitive process

Detuned capacitor banks and harmonic resonance

A capacitor bank and the supply inductance can form a resonant circuit. If that resonance sits near a harmonic your drives produce, such as the 5th or 7th, the harmonic current is amplified and capacitors and fuses fail. A detuned bank adds a series reactor so the resonant frequency falls below the lowest harmonic present. Before installing a bank in a plant with VFDs, check the harmonic spectrum and choose a detuned design.

Other power quality improvement methods

  • Surge protection at the main board, sub-boards and sensitive equipment.
  • Voltage regulation through tap changing, AVRs or voltage optimisation.
  • Grounding and bonding for safety and electromagnetic compatibility, not as a universal cure.
  • Phase balancing and sensible allocation of single-phase loads.
  • Load management such as staggered starts and scheduling heavy cycles.
  • Better equipment immunity: specify drives and controls with proper ride-through.

Switchgear changes are sometimes part of the fix, for example adding automatic transfer or upgrading incomers. Our overview of what switchgear is and the substation it feeds will help you plan this.

Power Factor vs Power Quality: What Is the Difference?

Power factor is the ratio of real power (kW) to apparent power (kVA). It shows how efficiently current is used. Power quality is about whether voltage, frequency and waveform are good enough for equipment to work. They are different things, though they affect each other.

FeaturePower factorPower quality
DefinitionReal power divided by apparent powerHow well voltage, current and frequency match equipment needs
PurposeEfficient use of supply capacityReliable, undamaged equipment and continuous production
Measured byPower factor, kvar, kVASags, THD, unbalance, flicker, interruptions
Improved withCapacitor banks, synchronous condensers, drive controlFilters, UPS, DVR, SPDs, regulation, load balancing
Common mistakeAssuming high power factor means clean powerAssuming capacitors fix every problem
  • Low power factor means more current for the same useful power, which brings extra losses and, in many tariffs, charges.
  • Harmonics distort the current and can lower true power factor, so the two are linked.
  • Power factor correction capacitors do not fix sags, transients or harmonics.
  • Capacitors can make harmonic problems worse through resonance, as explained above.

Power Quality Standards and Regulations

Standards do different jobs: some classify, some say how to measure and some set limits. Few of them are universal legal requirements, so check which one applies to your measurement and your country.

StandardWhat it coversWhere it appliesWatch out
IEEE 519-2022Harmonic voltage and current limitsAt the user PCC, mainly North American practiceNot a limit for every internal bus
IEEE 1159Monitoring and classification of power qualityWorldwide engineering referenceA classification guide, not a compliance limit
IEC 61000-4-30Measurement methods, Class A and Class SInternationalA measurement standard, not a performance limit
IEC 61000-4-7Harmonic and interharmonic measurementInternationalDefines how, not how much
IEC 61000-4-15Flickermeter specificationInternationalGives Pst and Plt method
EN 50160 (BS EN 50160 in the UK)Voltage characteristics at public supply terminalsPublic networks in Europe and the UKIndustrial networks are outside its scope
ENA Engineering Recommendation G5/5Harmonic voltage distortion and connection of harmonic sourcesUK distribution and transmission networksApplies when connecting to the network
ESQCR 2002Statutory voltage and frequency limitsGreat Britain230 V +10% and −6%; frequency ±1%
NEMA MG 1Motor performance and unbalance guidanceMotors, North American originGuidance on derating above 1% unbalance
BS 7671Wiring regulations including surge protection requirementsUK installationsNot a power quality measurement standard
IEEE standards are common in North America, IEC and EN standards in Europe and the UK. Always follow your local utility’s connection rules.

Poor power factor is one of the most common power quality costs. Our guide to leading vs lagging power factor explains the causes, capacitor sizing and the risks of overcorrection.

Frequently Asked Questions About Power Quality Problems

What are the major power quality problems?

Voltage sags, swells, interruptions, transients, harmonics, interharmonics and noise, unbalance, flicker, over and undervoltage, and frequency variation.

What are the five main causes of poor power quality?

Nonlinear loads, large motor starting, utility supply disturbances, poor system design or overloaded equipment, and switching operations or lightning.

What is power quality in simple words?

It is how clean, steady and reliable your electricity is. Good power lets equipment run normally. Poor power makes it trip, overheat or fail early.

What are the 10 common power quality problems in factories?

Voltage sags, swells, interruptions, transients, harmonics, interharmonics and noise, unbalance, flicker, over and undervoltage, and frequency variation. Each is covered in the section above.

What are the effects of poor power quality?

Unplanned stoppages, tripped drives, reset PLCs, overheated motors and transformers, damaged electronics, more maintenance and shorter equipment life.

How can power quality problems be prevented?

Measure first, then match the fix to the problem. Typical measures are surge protection, filters, ride-through, load balancing, correct transformer taps and suitable equipment specification.

How do you check the quality of electrical power?

Log the supply with a Class A power quality analyser at the incomer and at problem machines for at least one week, then review events, THD, unbalance and flicker.

What causes voltage sags in industrial plants?

Utility faults, starting large motors, switching big loads and energising transformers.

What are harmonics and why are they harmful?

Harmonics are currents or voltages at multiples of 50 Hz, created by nonlinear loads such as drives and rectifiers. They overheat transformers, cables and motors, overload neutrals and can destroy capacitors.

What is the difference between power factor and power quality?

Power factor measures how efficiently current is used. Power quality measures whether voltage, frequency and waveform suit your equipment. A high power factor does not guarantee clean power.

Why are power quality concerns increasing in modern industries?

Plants use more sensitive electronics, drives and automation, create more nonlinear load and cannot afford stoppages.

Can capacitor banks cause power quality problems?

Yes. Without detuning, a capacitor bank can resonate with the supply and amplify harmonics, which can destroy the capacitors.

What is the role of an active harmonic filter?

It measures load current and injects an equal and opposite current to cancel harmonics before they reach the transformer and supply.

Which instrument is used to measure power quality?

A power quality analyser. For accurate, comparable results choose one that meets IEC 61000-4-30 Class A.

What is the difference between shunt and series compensation?

Shunt devices connect in parallel and handle reactive power, harmonic current and voltage support. Series devices, such as a DVR, connect in line and restore load voltage during sags.

Conclusion: How to Maintain Good Power Quality in Industrial Plants

Power quality problems rarely announce themselves. They show up as trips, resets, hot equipment and short equipment life. The most damaging disturbances in factories are sags, harmonics, transients and unbalance, and each has a different cure.

The key habit is to find the cause before buying the cure. Run a power quality audit, log for a full week, trace each event to its source and then choose a fix. Measure again afterwards, and repeat the audit whenever you add drives, motors or capacitor banks.