Types of Electrical Cables: Different Types, Uses and Applications

By editor Updated 29 min read
Types of electrical cables: cross-section of a four-core armoured power cable, IndustrialBasics.

The main types of electrical cables are power, control, instrumentation, communication (data) and flexible cables. Each is built for a different job. Power cables carry energy, control cables carry on/off commands, instrumentation cables carry small measurement signals, data cables carry information and flexible cables move with machinery.

There is no single official number of cable types. A cable can be sorted by what it does, its voltage, how it is built, what insulates it and where it is installed, so one cable can be several things at once. For example, a cable can be a low-voltage, XLPE-insulated, steel wire armoured, multicore power cable. This guide keeps those labels apart so you can name, compare and choose cables without confusion. It focuses on industrial and commercial cables, with a shorter section on home wiring, and uses UK terms and standards first.

Short answer
  • 3 common industrial types: power, control and instrumentation (a common grouping, not an official one).
  • Other types: communication and data, flexible and trailing, VFD, fire-resistant, and special-purpose cables such as solar and marine.
  • Construction labels: single-core or multicore, armoured or unarmoured, shielded or unshielded.
  • Insulation labels: PVC, XLPE, EPR, PE and LSZH.
  • Size: mm² in the UK and IEC countries, AWG or kcmil in the US. They are not interchangeable.
Cable typeWhat it doesTypical core sizeTypical use
PowerCarries energy to equipment1.5 mm² up to 240 mm² and aboveMotors, panels, feeders
ControlCarries on/off and command signalsUsually 1.5 or 2.5 mm² per corePLC panels, contactors, relays
InstrumentationCarries small measurement signalsOften 0.5 to 1.5 mm² per coreSensors and transmitters
The three-type industrial grouping. Typical sizes are common practice, not rules. Final size comes from design calculations.
0.5 to 2,000 mm²
Nominal conductor sizes covered by IEC 60228
70 °C vs 90 °C
Typical maximum conductor temperature, PVC vs XLPE insulation
6 to 30 kV
Rated voltage range covered by IEC 60502-2 medium-voltage cables
USD 156.3 bn
Estimated global power and control cable market in 2025 (GM Insights)
Safety notice: This guide is general information. Cable selection, sizing and installation must follow BS 7671:2018+A4:2026 (the UK wiring rules) or your local code, and must be done or checked by a competent person. Isolate and prove dead before touching any cable, follow a lockout tagout procedure and wear suitable electrical PPE.

What Is an Electrical Cable?

An electrical cable is one or more insulated conductors held together inside a protective outer sheath. It carries electrical power or signals from one point to another, such as from a transformer to a distribution board or from a sensor to a controller. Cables are used in homes, offices, factories, substations and power networks.

Wire, cable, conductor and cord

TermMeaningExample
ConductorThe metal part that carries current, usually copper or aluminium, solid or strandedThe copper strands inside any cable
WireA single conductor, bare or insulatedA single insulated wire in conduit
CableOne or more insulated conductors under an overall sheath, sometimes with bedding, armour or a screenTwin and Earth, SWA cable
Cord or flexA flexible cable for portable or moving connectionsAn appliance lead
Everyday trade meanings. Exact definitions vary by standard and country.

Demand for cable is large and still growing. One market estimate puts power and control cable at USD 156.3 billion in 2025, rising to a forecast USD 296.2 billion by 2035. Other analysts give different totals because they define the market differently, so treat these as a guide to scale, not an exact figure.

Global power and control cable market sizeBar chart: USD 156.3 billion in 2025, USD 168.3 billion in 2026 and a forecast USD 296.2 billion in 2035, a compound annual growth rate of 6.5 per cent.Global power and control cable market, USD billion156.32025estimate168.32026estimate296.22035forecast6.5%growth a year,2026 to 2035Largest regionAsia PacificFastest growingMiddle Eastand Africa
Figure 1: Global power and control cable market. Source: GM Insights, Power and Control Cable Market, February 2026, checked 15 November 2026.

How Are Electrical Cables Classified?

Cables are classified in several independent ways. Mixing them in one list is the most common mistake in online guides. Armoured, XLPE, single-core and power cable are not four types of the same thing. They are labels from different axes.

Classification axisQuestion it answersExamples
FunctionWhat does the cable do?Power, control, instrumentation, data, flexible
Voltage classHow much voltage is it built for?ELV, LV, MV, HV
ConstructionHow is it built?Single-core, multicore, armoured, screened
Insulation and sheathWhat covers the conductor?PVC, XLPE, EPR, PE, LSZH
Fire performanceHow does it behave in a fire?Flame-retardant, LSZH, fire-resistant
InstallationWhere and how is it used?Fixed, buried, on tray, moving, hazardous area
Six ways to classify a cable. They are different axes, not different types.
One cable, five different labelsA single armoured power cable described on five axes: power cable by function, low voltage, XLPE insulation, steel wire armoured protection and multicore construction.The same cable carries five different labelsONE REAL CABLEXLPE / SWA / PVC4 cores, 16 mm²0.6/1 kVA typical UK armouredpower cableFUNCTIONPower cableVOLTAGE CLASSLow voltage (LV)INSULATIONXLPEMECHANICAL PROTECTIONArmoured (steel wire)CORE COUNTMulticore (4 cores)
Figure 2: One real cable carries a label on every axis at once.

Classification by function

The six functional groups are power, control, instrumentation, communication and data, flexible and trailing, and special-purpose cables. The next section explains each one.

Classification by voltage

Cables are rated as extra-low voltage (ELV), low voltage (LV), medium voltage (MV) or high voltage (HV). The limits vary by region and standard, so the voltage section below shows each range with its source.

Classification by construction

Construction labels come in pairs: single-core or multicore, armoured or unarmoured, shielded or unshielded. Each pair has its own comparison later in this guide.

What are the 3 types of electrical cables? In industry, the usual three are power, control and instrumentation cables. Some writers mean power, control and data cables. In US home wiring, people often mean NM-B (non-metallic sheathed), UF-B (underground feeder) and MC (metal-clad) cable. There is no official three-type system, so check which axis the writer is using.

Different Types of Electrical Cables and Their Uses

This is the main list. Each type below is a functional or special-purpose family. Construction labels such as armoured and shielded are covered after this section. The diagram shows where each type sits in a typical plant.

Where each cable type sits in a typical plantSimplified plant diagram. MV power cable runs from MV switchgear to a transformer, LV power cable runs to the LV panel and on to a variable frequency drive, a VFD cable runs to the motor, instrumentation cable runs from sensors to the PLC, control cable runs from the PLC to the drive and data cable links the PLC to the network.Where each cable type sits in a typical plantMV switchgearTransformerLV panel / MCCSensor /transmitterPLC / DCSVFD (drive)HMI / networkMotorMV power cableLV power cableLV power cableVFD (motor) cableInstrumentationcableControl cableData cableSimplified. Real plants also use earthing, lighting, fire alarm and safety circuits.
Figure 3: Where power, control, instrumentation, VFD and data cables sit in a simplified plant.

Power cables

A power cable carries electrical energy from a source to equipment. It is the most common industrial cable. Low-voltage (LV) power cables feed motors, panels and machines. Medium-voltage (MV) power cables connect substations, transformers and large motors.

  • Construction: copper or aluminium conductors, PVC or XLPE insulation, and often bedding, armour and an outer sheath. MV cables add conductor and insulation screens to control the electric field inside the cable.
  • Typical uses: motor feeders, distribution boards, transformer connections, plant feeders, and outdoor or buried runs.
  • Watch out for: sizing for current, voltage drop and short-circuit withstand, and protection by the right circuit breakers. Faults on large feeders can cause an arc flash, so isolate before any work.

Control cables

A control cable carries commands, interlocks and low-power control signals between panels and equipment. It tells things to start, stop, open or close. It does not carry the main load current.

  • Construction: multicore, commonly from 2 up to 48 cores of 1.5 mm² or 2.5 mm², with PVC insulation and sheath, and a copper braid screen or armour when needed. UK catalogues often list YY (unscreened), CY (copper braid screen) and SY (steel wire braid) types.
  • Typical uses: PLC panels, the coils of a contactor or relay, motor starter circuits, limit switches and interlocks.
  • Watch out for: using it for bulk power, and running it next to power or VFD cables without a screen.

Instrumentation cables

An instrumentation cable carries small, sensitive signals from field devices. A typical signal is a 4 to 20 mA loop from a pressure or temperature transmitter. These signals are easily disturbed by electrical noise, so the cable is built to block it.

  • Construction: twisted pairs or triads (the twist cancels noise), an individual foil screen on each pair, an overall screen, a drain wire for the screen connection and a tough sheath. Cores are often 0.5 to 1.5 mm².
  • Typical uses: sensors and transmitters, thermocouple and RTD signals, and links to PLC, DCS and SCADA systems. Thermocouples need extension or compensating cable that matches the thermocouple type.
  • Watch out for: screen earthing (usually at one end only, as the project specification says), routing away from power cables, and lightning surges on long outdoor runs, which is where surge protection devices help.

Power, control and instrumentation cable compared

Power cableControl cableInstrumentation cable
CarriesLoad currentCommands and interlocksMeasurement signals
CoresUsually 1 to 5Many, often 4 to 48Pairs or triads
Conductor sizeLarge, up to 240 mm² and aboveSmall, 1.5 to 2.5 mm²Small, often 0.5 to 1.5 mm²
ScreenNot usually (MV and VFD cables excepted)SometimesAlmost always
Signal levelHighest energyMediumLowest, most sensitive
Example circuitMotor feederStart/stop circuit4 to 20 mA pressure loop
How the three common industrial cable types differ. Sizes and core counts are typical, not rules.

Communication and data cables

Communication and data cables carry information, not power. In industry they link PLCs, drives, HMIs, cameras and plant networks.

  • Construction: twisted-pair copper (Ethernet), coaxial, fibre optic, and industrial Ethernet or fieldbus cables (such as Profibus, Modbus RS-485 or CAN) with tougher jackets and screening.
  • Typical uses: industrial networks, CCTV (coaxial), long links between buildings (fibre), and device networks on machines.
  • Watch out for: matching the cable to the protocol, data rate and distance, and keeping copper data cable away from power and VFD cable. Fibre is not affected by electrical noise.

Flexible and trailing cables

A flexible cable has very fine strands so it bends easily and can move. Trailing cables are flexible cables built to be dragged, reeled or flexed again and again.

  • Construction: Class 5 or Class 6 conductors (IEC 60228) with rubber or special sheaths. A common example is H07RN-F, a heavy-duty rubber cable rated 450/750 V that resists oil and suits medium mechanical stress.
  • Typical uses: cranes, robots, portable tools, site equipment, mobile plant and drag chains.
  • Watch out for: flexing life, bend radius, twisting and tension limits. These differ by cable, so check the datasheet for the movement you need.

VFD and inverter cables

A VFD cable connects a variable frequency drive (VFD) to a motor. Drives switch voltage on and off very fast, which creates electrical noise and voltage spikes in the motor cable.

  • Construction: a symmetrical layout (often three phase cores plus three earth conductors laid evenly) and a copper tape or braid screen that contains the noise.
  • Typical uses: any motor fed by a drive, especially on long runs or near noise-sensitive equipment.
  • Watch out for: ordinary unscreened cable, which can radiate noise onto nearby control and data cables and is linked to motor bearing currents. Bearing damage is one of the many motor failure causes worth designing out. Screens need 360° termination, and there is no single universal VFD cable standard, so follow the drive maker’s manual. If you are still deciding between a drive and a soft starter, read VFD vs soft starter first.

Fire-resistant cables

A fire-resistant cable is designed to keep a circuit working during a fire for a stated time. It is also called a circuit-integrity cable.

  • Construction: a mica-glass tape barrier around the conductors, then insulation and usually an LSZH sheath.
  • Typical uses: emergency lighting, fire alarms, fire pumps, smoke extraction and other life-safety circuits.
  • Watch out for: confusing it with flame-retardant or LSZH cable. They are different properties, compared in the insulation section. Check the required test (IEC 60331) and survival time.

Special-purpose industrial cables

  • Solar (PV) cables: single-core, flexible tinned copper with cross-linked, UV-resistant, halogen-free insulation and sheath. A common type is H1Z2Z2-K to EN 50618, used for DC up to 1,500 V.
  • Welding cables: very flexible, fine-strand cables with a tough rubber-type sheath for welding machines.
  • Mining cables: heavy-duty flexible rubber-sheathed cables for mobile mining machines.
  • Marine cables: built for ships and offshore units, often LSZH and resistant to oil and sea water.
  • Hazardous-area cables: used where explosive gas or dust may be present. The cable, gland and installation must all meet the hazardous-area rules, which are based on IEC 60079.
  • Oil and chemical-resistant cables: special sheath compounds, such as PUR, for workshops and process plants.

Electrical Cable Types Chart

Use this chart to compare cable families at a glance. It is a reference chart, not a current-rating table, so it carries no ampacity figures. Armoured cable is a construction category, not a function like power or control cable.

Cable typeAxisMain purposeTypical applicationsWatch out for
LV power cableFunction and voltageCarries power up to about 1 kVMotors, panels, distribution boards, machinesSize and install to the wiring rules; PVC has the lower temperature rating
MV power cableFunction and voltageCarries power from about 1 kV to 35 kVSubstations, transformers, large motorsNeeds MV design, terminations and testing skills
Control cableFunctionCarries commands and interlock signalsPLC panels, contactors, relays, startersNot for bulk power; screen it near noisy cables
Instrumentation cableFunction and signal qualityCarries small measurement signalsSensors, transmitters, PLC, DCS, SCADAScreen earthing and routing decide performance
Communication and data cableFunction and protocolCarries dataEthernet, fieldbus, CCTV, plant networksMust match protocol and distance; keep copper away from power
Flexible and trailing cableMechanical dutyMoves with equipmentCranes, robots, portable tools, site equipmentFlexing life varies by design; check bend radius
VFD (motor) cableApplication-specificConnects a drive to a motorMotors fed by variable frequency drivesNeeds 360° screen termination at both ends
Fire-resistant cableFire performanceKeeps a circuit working in a fireEmergency lighting, fire alarms, fire pumpsMust meet the specified test and survival time
LSZH / LSOH cableFire emissionsGives low smoke and no halogen acid gasTunnels, public buildings, offshoreNot automatically fire-resistant
Armoured cableMechanical protection (construction)Resists impact and crushingBuried, outdoor and exposed plant routesNeeds the right glands and earthing
Solar (PV) cableApplication-specificCarries DC from solar modulesSolar strings and inverter linksUse PV-rated cable only (DC up to 1,500 V)
Twin and Earth cableFunction and constructionFixed wiring in buildingsLighting and socket circuits in homesNot for unprotected outdoor or damage-prone routes
Master cable types chart. Every cable can appear on several axes at once.

The PDF adds construction and standard columns. It is a classification chart only. It is not a sizing or ampacity chart.

Cable Construction: Main Parts Explained

Most industrial cables are built in layers. The diagram shows a four-core armoured power cable from the centre outwards.

Cross-section of a four-core steel wire armoured cableLabelled diagram: stranded copper conductor, XLPE insulation, bedding, steel wire armour and outer sheath.Outer sheathPVC or LSZH. Keeps out water,oil and abrasion.InsulationXLPE. Keeps each core apartand from earth.ConductorStranded copper or aluminium.Carries the current.ArmourSteel wires. Protect againstimpact and crushing.BeddingCushions the cores and givesthe armour a smooth base.Not every cable has every layer. Layers depend on voltage, function and standard.
Figure 4: Cross-section of a four-core steel wire armoured (SWA) power cable. Original diagram.

Conductor

The conductor carries the current. Copper is the usual choice because it conducts well and is easy to terminate. Aluminium is lighter and cheaper for large cables but needs suitable lugs and connectors. IEC 60228 groups conductors into classes. Class 1 (solid) and Class 2 (stranded) are for fixed installations. Class 5 (flexible) and Class 6 (extra-flexible) are for cables that move, and Class 6 uses finer wires than Class 5 for the same size.

Conductor insulation

Insulation surrounds each conductor. It stops current leaking to earth and stops short circuits between conductors. The common materials are PVC, XLPE and EPR, compared in the next section.

Bedding or inner sheath

Bedding is a plastic layer over the cores. It cushions them and gives the armour a smooth, round base. Armoured cables have it. Many simple cables do not.

Armour layer

Armour is a metal layer for mechanical protection. Steel wire armour (SWA) is used on multicore cables. Steel tape armour (STA) also protects against impact and crushing. Aluminium wire armour (AWA) is used on single-core AC cables because non-magnetic armour avoids induced heating.

Shield or screen

A screen wraps the cores or pairs to block electromagnetic interference (EMI). It can be copper tape, copper braid or aluminium foil, often with a drain wire. Screens are used on instrumentation, data and VFD cables, and on MV cables to control the electric field.

Outer sheath

The outer sheath is the final layer. PVC is the common general-purpose choice. PE (polyethylene) is tough and moisture resistant and is used outdoors. LSZH is used where low smoke and no halogen acid gas matter. The sheath protects against moisture, chemicals, abrasion and weather. Not every cable has every layer.

Types of Electrical Cables Based on Insulation Materials

The insulation and sheath material decides how hot a cable can run, how it behaves in a fire and where it can be used. Whatever the material, insulation ages, and an insulation resistance test shows whether it is still healthy.

Maximum conductor temperature by insulation materialGrouped bar chart. PVC: 70 degrees Celsius continuous and 160 short circuit. XLPE: 90 continuous and 250 short circuit. EPR: 90 continuous and 250 short circuit.Maximum conductor temperature, °C (typical IEC 60502-1 values)Continuous operationShort circuit (up to 5 seconds)05010015020025070160PVC90250XLPE90250EPR (rubber)Typical values for standard compounds. Always check the cable datasheet.
Figure 5: Typical maximum conductor temperatures for PVC, XLPE and EPR insulation under IEC 60502-1. Values vary by compound.
PropertyPVCXLPEEPRLSZH compound
Material typeThermoplasticThermoset (cross-linked)Thermoset rubberLow-smoke, halogen-free compound
Continuous conductor temperature70 °C90 °C90 °C (typical)Depends on the compound
Short-circuit temperature160 °C250 °C250 °C (typical)Depends on the compound
Moisture resistanceModerateExcellentExcellentGood
FlexibilityGoodStifferVery flexibleGood
In a fireDense smoke and hydrogen chloride gasNeeds an LSZH sheath for low smokeNeeds flame-retardant compoundingLow smoke, no halogen acid gas
Typical useBuilding wiring, general power and controlIndustrial power, buried and high-load cablesTrailing, mining, marine, portable cablesTunnels, public buildings, offshore
Insulation materials compared. Temperatures are typical IEC 60502-1 values for standard compounds. Check the datasheet.

PVC cable

PVC (polyvinyl chloride) is a thermoplastic, so it softens when hot. It is cheap, flexible and widely used in building wiring and general power and control cables. Its limit is 70 °C at the conductor. In a fire it gives off dense smoke and hydrogen chloride gas.

XLPE cable

XLPE (cross-linked polyethylene) is a thermoset. Its molecules are chemically linked, so it holds its shape when hot. It runs at 90 °C continuously and withstands 250 °C in a short circuit. It resists moisture well, which suits buried and outdoor cables. For the same conductor size and installation, an XLPE cable can usually carry more current than a PVC cable because of its higher temperature rating. In UK practice, XLPE cores often sit inside a PVC or LSZH sheath, so an XLPE cable may still have a PVC outer.

EPR cable

EPR (ethylene propylene rubber) is a flexible thermoset rubber. It is used for trailing, mining, marine and portable cables because it stays flexible. It needs flame-retardant compounding where fire performance matters. Exact temperature and chemical limits depend on the compound, so check the datasheet.

LSZH cable

LSZH stands for low smoke zero halogen. It is also written LSOH or LSHF. The compound gives off little smoke and no halogen acid gases when it burns. It is used in tunnels, public buildings, data centres and offshore platforms, where people may be slow to escape. BS 6724 is the UK standard for LSZH armoured cable. LSZH describes smoke and gas, not how long a circuit survives, so it is not the same as fire-resistant cable.

Flame-retardant, LSZH and fire-resistant cables are different thingsThree cards. Flame-retardant cables resist flame spread (IEC 60332). LSZH cables give low smoke and no halogen acid gas (IEC 60754, IEC 61034). Fire-resistant cables keep a circuit working in a fire (IEC 60331).Flame-retardantANSWERSDoes fire spreadalong the cable?TEST OR STANDARDIEC 60332WATCH OUTCan still give off smokeand fail early in a fireLSZH / LSOHANSWERSHow much smoke andacid gas in a fire?TEST OR STANDARDIEC 60754, IEC 61034BS 6724 (UK armoured)WATCH OUTNot the same asfire-resistantFire-resistantANSWERSDoes the circuit keepworking in a fire?TEST OR STANDARDIEC 60331circuit integrity testsWATCH OUTNeeds the right ratingand survival timeA cable can meet none, one, two or all three.
Figure 6: Three different fire properties. A cable can have any combination of them.

PE cable

PE (polyethylene) is a tough, moisture-resistant plastic. It is used as the outer sheath on outdoor and buried cables and as insulation in some data and coaxial cables. PE is not flame-retardant unless it is specially compounded, so it needs care indoors.

Armoured vs Unarmoured Electrical Cables

An armoured cable has a metal layer, usually steel wire, between the bedding and the outer sheath. An unarmoured cable does not, so it relies on its sheath and on containment such as tray, conduit, trunking or duct.

Armoured cableUnarmoured cable
Extra layerSteel wire, steel tape or aluminium wire armourNone
Mechanical protectionHigh: resists impact, crushing and diggingLow: needs containment
Typical placesBuried, outdoors, exposed plant routesIndoors, in tray, conduit or trunking
Weight and handlingHeavier and stifferLighter and easier to install
TerminationNeeds armoured cable glandsStandard glands or clips
Earth pathArmour can act as the earth conductor if design checks are metNeeds a separate earth conductor
UK examplesXLPE/SWA/PVC to BS 5467; LSZH version to BS 6724Twin and Earth to BS 6004; PVC power cable in trunking
Armoured and unarmoured cables compared.

Choose armoured cable where it could be hit, crushed or dug up, and for buried or outdoor runs with no other protection. Choose unarmoured cable where tray, conduit or trunking already protects it. Always terminate armour with the right glands. Whether the armour can serve as the earth conductor depends on the design and the earthing system in use.

Single-Core vs Multicore Electrical Cables

Single-core cableMulticore cable
What it isOne insulated conductor in one sheathTwo or more insulated conductors under one sheath
Typical useLarge power feeders and transformer connectionsLV power circuits, control and instrumentation cables
InstallationEasier to pull in large sizes. Each phase is a separate cable, so more cleats and careOne pull for the whole circuit
ArmourNon-magnetic aluminium wire armour on AC circuits, or unarmouredSteel wire armour is fine
Magnetic effectsNeeds care: induced currents and heating if laid wronglyFields cancel out inside the cable
LimitsCores of one circuit must be grouped togetherLarge sizes become heavy and stiff
Single-core and multicore cables compared.

Use single-core cable when the current is large and a multicore cable would be too heavy to handle. Use multicore cable for most other circuits, and for all control and instrumentation work.

Shielded vs Unshielded Electrical Cables

A shielded (screened) cable has a conductive layer around the cores or pairs that blocks electromagnetic interference. An unshielded cable does not. Shielding works both ways: it keeps outside noise out of a signal, and it keeps a noisy cable from disturbing its neighbours.

Shielded cableUnshielded cable
Extra layerFoil, braid or tape screen, often with a drain wireNone
Best forInstrumentation, data, VFD and control cables near noiseSimple power circuits in a clean environment
Cost and sizeHigher cost, slightly largerLower cost, smaller
NeedsCorrect screen earthing and terminationSeparation from noisy cables
Shielded and unshielded cables compared.

Types of cable shielding

  • Aluminium foil with drain wire: full coverage, thin and cheap. Best for fixed runs because foil can crack if flexed.
  • Copper braid: tougher and more flexible. Good where the cable moves and for lower-frequency noise.
  • Copper tape: a wrapped copper layer, common on VFD cables and MV cables.
  • Foil plus braid: combines full coverage with strength. Used where noise is severe.

Use shielded cable for instrumentation, data and VFD circuits, for long runs, and near high-power equipment or radio sources. A screen that is earthed wrongly can make noise worse, so follow the project specification for where each screen is connected.

Types of Electrical Cables and Their Sizes

Understanding cable sizes

Cable size means the cross-sectional area of the conductor. In the UK and most other countries it is measured in square millimetres (mm²), for example 2.5 mm². IEC 60228 lists standard sizes from 0.5 mm² to 2,000 mm². In the US and Canada, small conductors use American Wire Gauge (AWG), where a smaller number means a thicker wire. Very large conductors use kcmil (thousand circular mils). Metric and American sizes do not match exactly.

Metric mm² sizes compared with AWG and kcmil sizesTwo cards. Metric sizes use cross-sectional area in square millimetres, where a bigger number is a bigger conductor. AWG uses gauge numbers, where a smaller number is a bigger conductor. They are related but not interchangeable.Metric: mm²USED INUK, Europe, IEC marketsMEASURESConductor cross-sectional areaTYPICAL SIZES1.5, 2.5, 4, 6, 10 … 240 mm²RULEBigger number = bigger conductorAWG and kcmilUSED INUSA and Canada (NEC, CEC)MEASURESGauge; kcmil for large sizesTYPICAL SIZES14, 12, 10 AWG … 250 kcmilRULESmaller number = bigger wire≠Related, not interchangeable. Use the datasheet or code table,not a rounded conversion.
Figure 7: Metric and American sizing systems are related but not interchangeable.

Common electrical cable sizes

These are the metric sizes you will meet most often. The diameter column is calculated from the area as a solid circle, so real stranded conductors are slightly larger.

Nominal sizeEquivalent diameter (calculated)Where you often see it (general guide only)
1.5 mm²1.4 mmUK lighting circuits; control cable cores
2.5 mm²1.8 mmUK socket circuits; control cable cores
4 mm²2.3 mmLarger appliance circuits and small motors
6 mm²2.8 mmCooker and similar circuits in homes
10 mm²3.6 mmShowers and small sub-mains
16 mm²4.5 mmSub-mains and small motors
25 mm²5.6 mmSub-mains and medium motors
35 mm²6.7 mmLarger sub-mains and motors
50 mm²8.0 mmMotor feeders and plant sub-mains
70 mm²9.4 mmIndustrial feeders
95 mm²11.0 mmIndustrial feeders and larger motors
120 mm²12.4 mmLarge feeders
240 mm²17.5 mmMain feeders; often used in parallel
Common metric conductor sizes. The last column is a general guide. It is not a current rating.

Factors affecting cable size selection

  • Current-carrying capacity: how much current the cable can carry without overheating.
  • Operating voltage: sets the insulation rating.
  • Cable length and voltage drop: long runs lose voltage and may need a larger conductor.
  • Conductor material: copper and aluminium carry different currents at the same size.
  • Insulation temperature rating: 90 °C XLPE can run hotter than 70 °C PVC.
  • Installation method: buried, in conduit, on tray or clipped direct all change cooling.
  • Ambient temperature: hot surroundings reduce capacity.
  • Grouping and derating: cables bundled together run hotter, so capacity falls.
  • Short-circuit withstand: the cable must survive the fault current until its protective device trips.

The cable must also be protected from overload and short circuit by a fuse or circuit breaker (see fuse vs circuit breaker). For motor circuits, a thermal overload relay guards against overload.

Warning: Cable size alone does not decide current capacity. Capacity depends on the installation method, temperature, grouping and insulation. In the UK, final sizing follows BS 7671 and its current-carrying capacity tables. Elsewhere, use the local electrical code. Do not choose a size from a rule of thumb.

Voltage Classification of Electrical Cables

Voltage class decides how much insulation a cable needs. The figure shows the classes on a log scale. A rating written as 0.6/1 kV means 0.6 kV between a conductor and earth and 1 kV between conductors.

Cable voltage classes on a log scaleExtra-low voltage below 50 volts AC, low voltage 50 volts to 1 kilovolt, medium voltage 1 to about 35 kilovolts, high voltage above about 35 kilovolts. IEC 60502-1 and IEC 60502-2 ranges are marked underneath.Voltage classes (AC, log scale)ELVbelow 50 VLV50 V to 1 kVMV1 kV to about 35 kVHVabove about 35 kVcontinues to hundreds of kV10 V100 V1 kV10 kV100 kV1 MVIEC 60502-10.6/1 and 1.8/3 kVIEC 60502-26 to 30 kVMV and HV limits vary by region and standard. Check the rules that apply to your site.
Figure 8: Cable voltage classes. ELV and LV limits follow BS 7671 and IEC 60038. MV and HV limits vary by region.

Extra-low voltage cables

Extra-low voltage (ELV) is up to 50 V AC or 120 V ripple-free DC in UK and IEC practice. It is used for 24 V control circuits, alarms, instrument loops and low-voltage lighting. These cables need less insulation but often need screening to protect the signal.

Low-voltage cables

Low voltage (LV) is 50 V to 1,000 V AC, or 120 V to 1,500 V DC, under IEC 60038. This covers most building and plant wiring, such as 230 V single-phase and 400 V three-phase supplies in the UK. Typical ratings are 300/500 V or 450/750 V for building wiring and flexible cables, and 0.6/1 kV for power cables. IEC 60502-1 covers extruded power cables rated 0.6/1 kV and 1.8/3 kV. In North America, 600 V is a common LV ceiling.

Medium-voltage cables

Medium voltage (MV) is above 1 kV and up to about 35 kV under European practice (EN 50160). IEC 60502-2 covers extruded solid-insulated cables from 6 kV to 30 kV. In the UK, 11 kV and 33 kV are common distribution voltages. MV cables use XLPE or EPR insulation with conductor, insulation and metallic screens to control the electric field. Terminations and joints need MV-trained staff.

High-voltage cables

High voltage (HV) is above about 35 kV and runs to hundreds of kV. It is used for transmission and large grid connections. HV cables follow other standards, for example IEC 60840 for higher voltage ranges, and are specialist designs with metallic sheaths and special accessories. Most readers will never specify one.

How to Choose the Right Electrical Cable

Five steps to choose the right electrical cableFlowchart: identify the job, check voltage and current, work out the conductor size, match the environment, choose insulation, fire rating and standard, then have a competent person check the design.1Identify the jobPower, control, signal, data, drive output or movement?2Check voltage and currentSupply voltage, load current, fault level and cable length.3Work out the conductor sizeCurrent, voltage drop, short circuit and installation method.4Match the environmentHeat, moisture, oil, UV, impact, burial, movement, hazardous area.5Choose insulation, fire rating and standardPVC, XLPE, LSZH, armour, screen, fire-resistant, BS or IEC.A competent person checks the designagainst BS 7671 or the local code
Figure 9: A five-step cable selection process. Original diagram.
  1. Identify the cable’s purpose. Is it for power, control, a measurement signal, data, a drive output or a moving machine?
  2. Check voltage and current requirements. Note the supply voltage, load current and fault level.
  3. Calculate the required conductor size. Allow for current, voltage drop, short circuit and installation method.
  4. Consider environmental and mechanical conditions. Think about heat, moisture, oil, UV, impact, burial and movement.
  5. Check insulation, fire performance and applicable standards. Choose PVC, XLPE or LSZH, armour or screen, and any fire-resistant rating the building needs.

Extra checks that catch people out

  • Indoor or outdoor: outdoor cable needs a UV-resistant sheath and protection from damage.
  • Direct burial: use armoured cable or run cable in duct, and follow the burial depth and marking rules in BS 7671.
  • Industrial or residential: plant work often needs armour, screens and higher fault ratings. Homes usually use Twin and Earth in protected routes.
  • Hazardous areas: the cable, gland and installation must all meet the hazardous-area rules.
  • Termination and compatibility: glands, lugs and terminals must match the cable size, metal and armour, including at switchgear connections.
  • Fault level: check the cable survives the fault current until its protective device trips. This is part of protection coordination.

Electrical Cable Standards and Regulations

Standards set how cables are built, tested and installed. Requirements depend on the country, the cable application and the installation conditions, and the standards below are not interchangeable.

StandardRegionMain purpose
IEC 60228InternationalConductors for insulated cables, including classes and sizes
IEC 60502InternationalPower cable construction and testing (Part 1 to 3 kV, Part 2 for 6 to 30 kV)
IEC 60332InternationalFire tests for flame propagation
IEC 60331InternationalCircuit-integrity tests under fire conditions
IEC 60038InternationalStandard voltage values
BS 7671UKIET Wiring Regulations: installation, sizing, protection and earthing
BS 5467UKArmoured power cables with thermosetting insulation (PVC sheath)
BS 6724UKLow-smoke, halogen-free armoured cables
BS 6004UKPVC insulated and sheathed cables for fixed wiring, including Twin and Earth
EN 50618Europe and UK tradeSolar (PV) cables such as H1Z2Z2-K
NEC / NFPA 70United StatesElectrical installation requirements
ULUnited StatesCable product safety and listing standards
Common cable standards by region.

The current UK edition is BS 7671:2018+A4:2026. It was published on 15 April 2026, and the previous version was withdrawn six months later, on 15 October 2026. US documents use the word grounding where UK documents use earthing. The two systems are explained in earthing vs grounding.

Residential and Commercial Electrical Cable Types

Home and office wiring uses a short list of cables. This section is brief because the industrial types above cover most of the detail.

CableWhere it is usedNotes
Twin and Earth (6242Y)Lighting and socket circuitsFlat PVC cable with two insulated cores and a bare earth, to BS 6004. Rated 300/500 V
Single-core building wireInside conduit or trunkingIndividual insulated wires for fixed wiring
SWA cableOutbuildings, garages, outdoor and underground feedersArmoured. Often XLPE/SWA/PVC to BS 5467
Flexible cord (flex)Appliances and portable equipmentFine-strand conductors for moving connections
Fire-resistant cableFire alarms and emergency lightingKeeps working in a fire
US only: NM-B, UF-B, MC, THHN/THWNUS homes and buildingsNames come from the NEC and apply to US installations only
Common home and commercial cable types. Check the local wiring rules before using any of them.

In buildings, these cables feed lighting circuits, socket circuits, air conditioning, distribution boards and outdoor installations. In every case the size, protection and route must be designed to BS 7671 or the local code.

Frequently Asked Questions About Types of Electrical Cables

What are the different types of electrical cables?

By function: power, control, instrumentation, communication and data, and flexible cables. Special types include VFD, fire-resistant and solar cables. Construction labels such as armoured or shielded sit on top of these.

What are the 3 main types of electrical cables?

The common industrial three are power, control and instrumentation cables. This is a widely used grouping, not an official standard.

How many types of electrical cables are there?

There is no fixed number. The count depends on whether you classify by function, voltage, construction, insulation, fire performance or installation. One cable can fit several categories.

What are the most commonly used electrical cables?

In UK homes, Twin and Earth is the most common. In industry, XLPE/SWA/PVC power cable and multicore control cable are widely used.

What is the difference between a wire and a cable?

A wire is a single conductor. A cable is one or more insulated conductors inside an overall sheath.

What is the difference between power and control cables?

Power cables carry the load current and use few, large cores. Control cables carry commands and use many small cores, often 1.5 or 2.5 mm².

What is the difference between armoured and unarmoured cables?

Armoured cable has a metal layer, usually steel wire, for protection against impact and crushing. Unarmoured cable relies on tray, conduit or trunking.

What is an XLPE cable?

An XLPE cable uses cross-linked polyethylene insulation. It runs at 90 °C continuously and resists moisture well. The outer sheath may still be PVC or LSZH.

What is the difference between PVC and XLPE cables?

PVC is a thermoplastic rated at 70 °C. XLPE is a thermoset rated at 90 °C, so it can usually carry more current for the same size and installation.

What is an instrumentation cable used for?

It carries small measurement signals, such as 4 to 20 mA loops, from sensors and transmitters to PLC, DCS and SCADA systems. Twisted pairs and screens protect the signal from noise.

What is a VFD cable?

A VFD cable connects a variable frequency drive to a motor. It has a symmetrical layout and a screen to contain noise and reduce bearing currents.

What does LSZH mean in electrical cables?

LSZH means low smoke zero halogen. The cable gives off little smoke and no halogen acid gas when it burns.

What are single-core and multicore cables?

A single-core cable has one insulated conductor. A multicore cable has two or more insulated conductors in one sheath.

How do I choose the correct electrical cable size?

Size depends on current, voltage drop, short-circuit withstand, insulation rating, installation method, ambient temperature and grouping. Use BS 7671 or your local code, and have a competent person check it.

Can mm² and AWG cable sizes be interchanged?

No. They are different systems with different step sizes. Use the cable datasheet and the code table, not a rounded conversion.

Which cable is best for underground installation?

Armoured cable, such as XLPE/SWA/PVC to BS 5467, is the usual choice. Cable in a duct is another option. The route, depth and marking must follow BS 7671.

What is the difference between fire-resistant and flame-retardant cables?

Flame-retardant cable resists the spread of flame along it. Fire-resistant cable keeps a circuit working during a fire for a stated time. They are different properties.

What are the common electrical cable standards?

Common ones are IEC 60228 and IEC 60502 (international), BS 5467, BS 6724 and BS 7671 (UK), and NEC/NFPA 70 and UL (US).

Conclusion

The main types of electrical cables are power, control, instrumentation, communication and flexible cables, with special types for drives, fire safety and solar systems. Voltage, construction, insulation and environment then decide the exact cable for each job.

  • Name the cable on each axis: function, voltage, construction, insulation, fire performance and installation.
  • Size the cable from current, voltage drop, short-circuit withstand and installation conditions, never from cable type alone.
  • Follow BS 7671 or your local code, and ask a qualified electrical professional to select and install the cable.

Sources

Facts and figures last checked 15 November 2026. Temperature values, sizes and examples are typical. Always confirm against the current edition of the standard and the cable datasheet.